USER MANUAL
k.Air
+030220981 - ENG
Up to date version available on
www.carel.com
k.Air
Air handling unit controller
ENG
LEGGI E CONSERVA
Q
UESTE ISTRUZIONI
READ AND SAVE
THESE INSTRUCTIONS
ENG
GENERAL WARNINGS
!
CAREL bases the development of its products on decades of
experience in HVAC/R, on continuous investments in technological
innovations to products, procedures and strict quality processes
with in-circuit and functional testing on 100% of its products, and
on the most innovative production technology available on the
market. CAREL and its subsidiaries/affiliates nonetheless cannot
guarantee that all the aspects of the product and the software
included with the product respond to the requirements of the
final application, despite the product being developed according
to start- of- the- art techniques. The customer (manufacturer,
developer or installer of the final equipment) accepts all liability
and risk relating to the configuration of the product in order to
reach the expected results in relation to the specific final
installation and/or equipment. CAREL may, based on specific
agreements, act as a consultant for the successful commissioning of
the final unit/application, however in no case does it accept
liability for the correct operation of the final equipment/system.
The CAREL product is a state-of-the-art product, whose operation
is specified in the technical documentation supplied with the
product or can be downloaded, even prior to purchase, from the
website www.carel.com. Each CAREL product, in relation to its
advanced level of technology, requires
setup/configuration/programming/commissioning to be able to
operate in the best possible way for the specific application.
Failure to complete such operations, which are
required/indicated in the user manual, may cause the final
product to malfunction; CAREL accepts no liability in such cases.
Only qualified personnel may install or carry out technical service
on the product. The customer must only use the product in the
manner described in the documentation relating to the product.
In addition to observing any further warnings described in this
manual, the following warnings must be heeded for all CAREL
products:
l prevent the electronic circuits from getting wet. Rain,
humidity and all types of liquids or condensate contain
corrosive minerals that may damage the electronic circuits. In
any case, the product should be used or stored in
environments that comply with the temperature and humidity
limits specified in the manual;
l do not install the device in particularly hot environments. Too
high temperatures may reduce the life of electronic devices,
damage them and deform or melt the plastic parts. In any case,
the product should be used or stored in environments that
comply with the temperature and humidity limits specified in
the manual;
l do not attempt to open the device in any way other than
described in the manual.
l do not drop, hit or shake the device, as the internal circuits and
mechanisms may be irreparably damaged.
l do not use corrosive chemicals, solvents or aggressive
detergents to clean the device.
l do not use the product for applications other than those
specified in the technical manual.
All of the above suggestions likewise apply to the controllers,
serial cards, programming keys or any other accessory in the
CAREL product portfolio.
CAREL adopts a policy of continual development. Consequently,
CAREL reserves the right to make changes and improvements to
any product described in this document without prior warning.
The technical specifications shown in the manual may be changed
without prior warning. The liability of CAREL in relation to its
products is specified in the CAREL general contract conditions,
available on the website www.carel.com and/or by specific
agreements with customers; specifically, to the extent where
allowed by applicable legislation, in no case will CAREL, its
employees or subsidiaries/affiliates be liable for any lost earnings
or sales, losses of data and information, costs of replacement goods
or services, damage to things or people, downtime or any direct,
indirect, incidental, actual, punitive, exemplary, special or
consequential damage of any kind whatsoever, whether
contractual, extra-contractual or due to negligence, or any other
liabilities deriving from the installation, use or impossibility to use
the product, even if CAREL or its subsidiaries/affiliates are warned
of the possibility of such damage.
DISPOSAL
Fig.1
F
ig. 2
Please read and keep.
With reference to European Union directive 2012/19/EU issued on
4 July 2012 and related national legislation, please note that:
1. Waste Electrical and Electronic Equipment (WEEE) cannot be
disposed of as municipal waste but must be collected separately
so as to allow subsequent recycling, treatment or disposal, as
required by law;
2. users are required to take Electrical and Electronic Equipment
(EEE) at end- of- life, complete with all essential components, to
the WEEE collection centres identified by local authorities. The
directive also provides for the possibility to return the equipment
to the distributor or retailer at end-of-life if purchasing equivalent
new equipment, on a one- to- one basis, or one- to- zero for
equipment less than 25 cm on their longest side;
3. this equipment may contain hazardous substances: improper
use or incorrect disposal of such may have negative effects on
human health and on the environment;
4. the symbol (crossed-out wheeled bin – Fig.1) even if, shown on
the product or on the packaging, indicates that the equipment
must be disposed of separately at end-of-life;
5. if at end-of-life the EEE contains a battery (Fig. 2), this must be
removed following the instructions provided in the user manual
before disposing of the equipment. Used batteries must be taken
to appropriate waste collection centres as required by local
regulations;
6. in the event of illegal disposal of electrical and electronic waste,
the penalties are specified by local waste disposal legislation.
k.Air +030220981 rel. 1.1– 31.03.2020
|3
ENG
Warranty on materials: 2 years (from the production date,
excluding consumables).
Approval: the quality and safety of CAREL products are guaranteed
by the ISO 9001 certified design and production system, as well
as by the and marks e .
Dangerous voltage.
Caution, hot surface.
Important: this product is to be integrated and/or
incorporated into the final apparatus or equipment.
Verification of conformity to the laws and technical standards
in force in the country where the final apparatus or equipment
will be operated is the manufacturer’s responsibility. Before
delivering the product, Carel has already completed the
checks and tests required by the relevant European directives
and harmonised standards, using a typical test setup, which
however cannot be considered as representing all possible
conditions of the final installation.
4|
k.Air +030220981 rel. 1.1– 31.03.2020
ENG
Index
1. INTRODUCTION 7
1.1 Main features 8
1.2 Map of points and functional diagram 8
1.3 Series of accessories for k.Air 11
2. COMMUNICATION PORTS 17
3. HARDWARE INSTALLATION 19
3.1 Assembly and dimensions – mm (in) 19
3.2 Description of the c.pCO mini terminals 21
3.3 Installation 22
3.4 Power supply 24
3.5 pGDE terminal connection 24
3.6 Universal input/output connections 25
Insulation type on k.Air mini and c.pCOe 33
Insulation type on k.Air large 34
4. USER INTERFACE 36
4.1 Introduction 36
4.2 Keypad 36
4.3 Display 36
4.4 Programming mode 38
4.5 Setting the parameters 39
4.6 Quick access menu 40
5. TH-TUNE (ACCESSORY) 44
5.1 Introduction 44
5.2 Keypad 45
5.3 Display 45
5.4 Setting the time and day of the week 47
5.5 Setting the time bands 47
5.6 Main data display 49
5.7 Change set point 50
5.8 Party function 50
5.9 Fan speed control 51
5.10 Procedure for setting the time bands on th-Tune 51
6. PGDX AND WEB SERVER (ACCESSORY) 54
6.1 Introduction 54
7. MENU DESCRIPTION 57
7.1 Menu tree 57
7.2 Service parameters 58
7.3 Manufacturer parameters 60
8. COMMISSIONING 61
8.1 Choose pre-loaded configuration 61
8.2 Upload configuration from USB pen drive 62
8.3 Load from auto-backup 62
8.4 Manual configuration 62
8.5 Input/output configuration 63
8.6 Unit of measure 64
8.7 Hour counter setting for each device 64
8.8 FieldBus serial port configuration 66
8.9 Manual mode 66
8.10 Save configuration 66
9. FUNCTIONS 69
9.1 Dampers 69
9.2 Activation 71
9.3 Shutdown 73
9.4 Types of control 76
9.5 PID control 76
9.6 Temperature control 81
9.7 Cooling and heating 83
9.8 Set point compensation with outside air probe 85
9.9 Coils 86
9.10 Direct expansion with integrated management 90
9.11 Direct expansion managed by uChiller 95
9.12 Indirect evaporative cooling (IEC) 97
9.13 Humidity control 99
9.14 Humidification 101
9.15 Dehumidification 102
9.16 Freecooling/freeheating 104
9.17 Heat recovery 105
9.18 Fans 107
9.19 Air quality control 111
9.20 Auxiliary control 113
9.21 Frost protection 115
9.22 Heat recovery unit defrost 118
9.23 Evaporator defrost 121
9.24 Probe error management 126
9.25 Operating profiles 128
9.26 Time bands 134
9.27 VDI 6022-1 management 140
9.28 k.water integration 149
9.29 Network settings 152
k.Air +030220981 rel. 1.1– 31.03.2020
|5
ENG
10. PARAMETER TABLE 154
10.1 Parameter table 154
11.1 Supervisor variable table 200
12. ALARMS AND SIGNALS 245
12.1 Types of alarms 245
12.2 Alarm parameters 247
12.3 Generic alarm input and output contacts. 247
12.4 Alarm table 248
13. SOFTWARE UPDATE 254
13.1 Update via USB cable 254
13.2 Update via USB pen drive 255
13.3 Update with file transfer via FTP 255
6|
k.Air +030220981 rel. 1.1– 31.03.2020
1. Introduction
k.Air is a pre-programmed controller for air conditioning and ventilation units.
k.Air ensures simple commissioning, application flexibility, advanced connectivity and usability, thanks to
the following features:
l preloaded configurations of air handling units, configuration tool or manual procedure;
l modular concept for the management of additional configurations by coupling together c.pCOe
expansion modules via a built-in serial card;
l management of high-efficiency direct expansion units
l application of energy saving and adiabatic humidification management algorithms;
l advanced connectivity, thanks to three serial ports and an Ethernet port, certified Bacnet protocol and
remote control via tERA.
l integrated web server interface.
k.Air is available in two sizes: mini P/N P+DA00FHD*FK and large P/N P+5A00SFC*LK. Both models share
the same software functions, however they differ in terms of the number and characteristics of the
available inputs/outputs and serial communication ports.
The number of inputs/outputs can be expanded using up to 4 c.pCOe expansion modules.
Fig.1.a
It is possible to connect CAREL temperature and humidity probes, active differential pressure probes,
flow switches and thermostats, with control functions or to signal alarms in the event of a fault.
The application offers numerous pre- set basic unit configurations (I/O map and related associated
functions); if the unit being configured deviates from these models (e.g. if the devices are connected to a
different input/output or the unit has other devices and functions), the software can be reconfigured on
the PGDE display or using the configuration tool.
ENG
k.Air +030220981 rel. 1.1– 31.03.2020
1. Introduction|7
ENG
1.1
Main features
Summary of main functions:
l parameter setting by level, user, installer or manufacturer, with password-protected access;
l temperature control with different set points based on the operating mode (Economy, PreComfort,
Comfort and/or cooling or heating);
l set point compensation with outside temperature probe;
l selection of daily time bands with corresponding operating mode;
l holiday and special day function;
l cascade control of heating/cooling devices in order to maximise energy savings (up to 6 devices);
l dehumidification by cooling coil (with dew point control) and reheating;
l control with 0- 10 V input for humidifier or Modbus connection for CAREL humiSonic and humifog
humidifiers;
l freecooling” and freeheating based on the temperature;
l heat recovery with cross-flow or thermal wheel;
l air quality control with CO2 probe;
l safety functions for frost protection, no air flow, humidifier alarm, etc.;
l heat recovery defrost from digital input;
l independent auxiliary control loop, with PI control algorithm and control probe;
l configuration wizard;
l configuration of inputs/outputs from PGDE terminal with free mapping on the main board, expansions
and serial probes;
l input/output test to verify correct wiring during installation;
l manual mode to manually control each device during normal operation.
l Two-circuit direct expansion units with On/Off and/or BLDC compressors using the main board and
unipolar driver (k.water mini) or via serial connection to uChiller.
l Customisable maintenance plan based on VDI 6022-1.
1.2 Map of
points and
functional
diagram
Fig.1.b
8|1. Introduction
k.Air +030220981 rel. 1.1– 31.03.2020
AI Analogue inputs DI Digital inputs DO Digitaloutputs AO Analogue outputs
0 Supply temperature 0 Supply air flow switch 0 Bypass damper 0 Supply fan
1 Supply humidity 1 Return air flow switch 3 Outside air damper 1 Return fan
2 Return temperature 2 Air flow switch 4 Exhaust damper 2 Bypass damper
3 Return humidity 3 Frost protection thermostat 5 Mixing damper 3 Mixing damper
4 Room temperature 4 Remote On/Off 6 Supply damper 4 Outside air damper
5 Room humidity 5 Supply fan 1 thermal protector 7 Return damper 5 Reheat coil
6 Outside temperature 6 Return fan 1 thermal protector 10 Supply fan 6 Preheat coil
7 Outside humidity 11 Fan thermal protector 11 Return fan 8 Main coil
8 Exhaust temperature 12 Compressor thermal protector 14 Compressor 9 Thermal wheel
9 Exhaust humidity 13 High pressure switch 15 Reversing valve 10 Humidifier
10 Frost protection temperature 14 Low pressure switch 16 Unit status 11 Exhaust damper
11 Saturation temperature 15 Heat recovery unit thermal protector 17 Heating/cooling status 12 Auxiliary loop 1 signal
12 Saturation humidity 16 Serious alarm 18 Global alarm 13 Auxiliary loop 2 signal
14 Supply pressure 17 Generic alarm 19 Minor alarm 14 Auxiliary loop 3 signal
15 Return pressure 18 Generic warning 20 Serious alarm 15 Auxiliary loop 4 signal
16 CO2 sensor 19 Filter alarm 21 Humidifier 16 IEC humidifier
18 Discharge pressure 20 Supply filter 1 alarm 22 Auxiliary loop 1 output 18 Supply damper
19 Drain temperature 21 Supply filter 2 alarm 23 Auxiliary loop 2 output 17 Modulating heat recovery unit
20 Suction pressure 22 Return filter alarm 24 Auxiliary loop 3 output 19 Return damper
21 Suction temperature 23 Humidifier alarm 25 Auxiliary loop 4 output
23 Preheating coil H2O temp. 24 Main coil pump 1 thermal protector 26 Open main coil valve
24 Main coil H2O temp. 25 Main coil pump 2 thermal protector 27 Open preheating coil valve
25 Reheating coil H2O temp. 26 Reheat coil pump 1 thermal protector 28 Open reheating coil valve
26 Auxiliary loop 1 sensor 27 Reheat coil pump 2 thermal protector 29 Main coil valve closing
27 Auxiliary loop 2 sensor 28 Preheat coil pump 1 thermal protector 30 Close preheating coil valve
28 Auxiliary loop 3 sensor 29 Preheat coil pump 2 thermal protector 31 Close reheating coil valve
29 Auxiliary loop 4 sensor 35 Main coil flow switch 32 Main coil step 1
33 Hepa 1 filter sensor 36 Preheating coil flow switch 33 Main coil step 2
34 Hepa 2 filter sensor 37 Reheating coil flow switch 34 Main coil step 3
39 Heat recovery unit dirty 35 Main coil step 4
40 Reheating alarm 36 Reheating coil step 1
41 Preheating coil alarm 37 Reheating coil step 2
42 Main coil alarm 38 Reheating coil step 3
44 Open door contact 39 Reheating coil step 4
45 Smoke-fire alarm 40 Preheating coil step 1
47 Heating/cooling contact 41 Preheating coil step 2
49 Eco contact 42 Preheating coil step 3
50 Pre-Comfort contact 43 Preheating coil step 4
51 Comfort contact 48 Preheat coil pump 1
52 Auxiliary loop 1 input 49 Preheat coil pump 2
53 Auxiliary loop 2 input 50 Main coil pump 1
54 Auxiliary loop 3 input 51 Main coil pump 2
55 Auxiliary loop 4 input 52 Reheat coil pump 1
56 Heat recovery unit defrost 53 Reheat coil pump 2
56 Filter alarm
57 On/off heat recovery unit
58 IEC humidifier
Tab.1.a
ENG
k.Air +030220981 rel. 1.1– 31.03.2020
1. Introduction|9
ENG
Fig.1.c
Addr. Modbus Devices
30 Supply fan
31 Return fan
1 to 4 c.PCOe
10 UChiller
1 Power+
5 Humisonic
6 to 7 Humifog
128 to 137 Serial probe
9 Th-Tune
Tab.1.b
10|1. Introduction
k.Air +030220981 rel. 1.1– 31.03.2020
Fig.1.d
1.3 Series of
accessories for
k.Air
Below is a list of devices that are suitable for use with k.Air. CAREL has passive and active temperature
probes and differential pressure probes, for duct installation, designed specifically for heat recovery units
and small air handling units.
Note: see manuals +040010025/+040010026 for guidelines on installing the sensors on the unit.
Duct temperature sensor
Fig.1.e
P/N Type Range
DPDT011000 NTC
-20T70°C
DPDT010000 0-1 V, 4-20 mA
Tab.1.c
ENG
k.Air +030220981 rel. 1.1– 31.03.2020
1. Introduction|11
ENG
NTC temperature sensor
Fig.1.f
P/N Type Range
NTC*HP* 10 kΩ ±1% @25°C, IP67 -50 to 105/50 °C (air/fluid)
NTC*WF* 10 kΩ±1%@25°C (Fast), IP67 -50 to 105°C
NTC*WH* 10 kΩ ±1% @25°C, IP68 -50 to 105°C
NTC*HF* 10 kΩ±1%@25°C,strap-on, IP67 -50 to 105°C
NTC*HT* 50 kΩ ±1% @25°C, IP67 -30 to 150°C (air)
NTC*HT* 50 kΩ±1%@25 °C, st. steel cap, IP67 -30 to 150°C (air)
Tab.1.d
Differential air pressure sensor
Fig.1.g
P/N Range Output
SPKD00U5N0
0-1000 Pa
4 to 20 mA
0-2500 Pa
0-3000 Pa
0-5000 Pa
Tab.1.e
Note: the k.Air mini +Vdc terminal provides a supply voltage of 12 Vdc ± 8%. If a higher voltage is
required, use an external power supply.
12|1. Introduction
k.Air +030220981 rel. 1.1– 31.03.2020
Differential air pressure switches/flow switches
Fig.1.h
PRESSURE SWITCHES
P/N Range Output
P/N Range Output
DCPD000100 0.5 to 5 mbars ON/OFF
DCPD001100 0.2 to 2 mbars ON/OFF
Tab.1.f
FLOW SWITCHES
P/N Range Output
P/N Range Output
DCFL000100 1-9 m/s ON/OFF
Tab.1.g
Air quality sensor for rooms and ducts
Fig.1.i
CO
2
SENSORS
P/N Range Output
P/N Range Output
DPWQ402000 0-2000 ppm 0-10 V
DPDQ402000 0-2000 ppm 0-10 V
Tab.1.h
ENG
k.Air +030220981 rel. 1.1– 31.03.2020
1. Introduction|13
ENG
pGDE graphic terminal
The pGDE graphic terminal part number PGNE000* allows complete graphics management, with icons
and international fonts.
Installation accessories:
l telephone connection cable for k.Air large P/N S90CONN00*;
l connection cable for k.Air mini P/N S90CONN0S0;
l junction card TCONN6J000 (for distances > 10 m, see technical leaflet +050002895).
See technical leaflet +050001425.
Fig.1.j
th-Tune terminal
th-Tune part number AT* is the room terminal that, together with the k.Air programmable controller,
allows the user to set the room temperature and humidity (when the corresponding probes are
available). Based on the model, the power supply can be chosen between 230 Vac and 24 Vac/Vdc. th-
Tune is compatible with the main recessed wall boxes on the market. The temperature set point can be
set simply and intuitively using the front knob. For assembly details, see the technical leaflet +0500016IE.
Fig.1.k
pGDX terminal
The 4.3-inch pGDx graphic terminal, P/N PGB04*** is part of the touch screen family, designed to make
the user interface with k.Air controllers simple and intuitive. The electronic technology used and the 65K
colour display enable management of high quality images and advanced features to ensure a high
aesthetic standard. The touch screen display guarantees simple human-machine interaction, making it
easier to browse between the various screens. The pGDx terminal can be used to fully browse the k.Air
webserver, thus acting as a unit terminal. In the version with built-in T/H probe, it can be used as a room
terminal, getting the temperature and humidity values directly from the main controller.
14|1. Introduction
k.Air +030220981 rel. 1.1– 31.03.2020
Fig.1.l
HumiSonic ultrasonic humidifier
Adiabatic ultrasonic humidifier for installation inside the air handling unit.
Installed directly in the air flow, humiSonic atomises water into very small droplets (5 µm on average),
which are instantly absorbed by the air flow. This is proposed as a high energy efficiency alternative to
steam humidification.
It is available in the Ventilation and Compact versions.
In the Ventilation version, it has capacity of 2 kg/h at 18 kg/h, and is designed for installation inside air
handling units or ducts.
It comprises an atomising production and distribution unit and an external electrical panel. For more
details see manual +0300063EN.
Fig.1.m
In the Compact version, it has a capacity of 0.5 kg/h to 1 kg/h, and is designed to be built into compact
units, such as heat recovery units, fan heaters, fan coils, etc. See manual +0300056EN.
Fig.1.n
ENG
k.Air +030220981 rel. 1.1– 31.03.2020
1. Introduction|15
ENG
Humifog high pressure sprayer
High pressure adiabatic humidifier for humidity control and evaporative cooling. humiFog combines an
intelligent pumping station with a modular distribution system, equipped with special nozzles capable
of maximising water atomisation and allowing a short absorption distance. Inverter modulation ensures
very accurate control of pump speed, reducing energy consumption and optimising water use. With
capacities from 100 to 1000 kg/h, it is designed for applications with high humidification demand, where
precision and hygiene are distinctive factors.
Fig.1.o
uChiller
μChiller is Carel’s solution for the complete management of direct expansion units. The maximum
configuration manages 2 compressors per circuit (On/Off or BLDC), up to a maximum of 2 circuits (using
an expansion card for circuit 2). The distinctive element of μChiller is complete control of high-efficiency
units through integrated management electronic expansion valves (ExV) and the brushless DC
compressors, guaranteeing
greater compressor protection and reliability and high unit efficiency. CAREL’s APPLICA” app, available
on Google Play for the Android operating system, makes it easier to configure parameters and
commission the unit. Operation of μChiller is described in the user manual +0300053EN
Fig.1.p
16|1. Introduction
k.Air +030220981 rel. 1.1– 31.03.2020
2. Communication ports
See the c.pCO manual +0300057EN for the hardware characteristics of the serial ports. The k.Air controller
manages the protocols on the serial ports shown in the table.
Ref. Type/connectors Model Specifications Protocol
A
J3 Disp.
k.Air
mini
l Integrated on main board
l HW driver: asynchronous half duplex RS485 pLAN
l Not optically-isolated
l Connectors: plug-in 4-pin pitch 3.81 (k.Air mini), 6-pin
telephone jack + plug-in 3-pin pitch 5.08 (k.Air large)
l Maximum cable length: 500 m
l Max data rate: 38400 bit/s
l Max. no. of connectable devices: 1 (th-tune); 1
powered by the controller, another 2 powered
externally (pGDE)
l pLAN
(pGDE)
l Modbus
Master
(th-Tune)
pLAN/J10, J11
k.Air
large
pLAN (pGDE)
B BMS 1 Serial Card
k.Air
large
l Not integrated on main board
l HW driver: not present
l Used for all c.pCO family BMS expansion cards
Modbus
Slave
C FieldBus 1 Serial Card
k.Air
large
l Not integrated on main board
l HW driver: not present
l Used for all c.pCO family BMS expansion cards
Modbus
Master
D BMS 2/ J25
k.Air
large
l Integrated on main board
l HW driver: asynchronous half duplex RS485 Slave
l Optically-isolated
l 3-pin plug-in connector, pitch 5.08 mm
l Maximum cable length: 1000 m
l Max data rate: 115200 bit/s
l Max. number of connectable devices: 16
Modbus
Slave
E
J4 FBus
k.Air
mini
l Integrated on main board
l HW driver: asynchronous half duplex RS485 Master.
l J4 not optically-isolated
l J26 optically-isolated
l J23 not optically-isolated
l Connectors: plug-in 3-pin pitch 3.81 (k.Air mini), pitch
5.08 (k.Air large)
Modbus
Master
FieldBus 2/ J26 and
J23
k.Air
large
F RJ45
k.Air
mini
1 Ethernet port, 10/100 Mbps
TCP/IP
k.Air
large
2 Ethernet ports, 10/100 Mbps (100-BASE TX), both
equivalent
Tab.2.a
ENG
k.Air +030220981 rel. 1.1– 31.03.2020
2. Communication ports|17
ENG
Fig.2.a
Fig.2.b
18|2. Communication ports
k.Air +030220981 rel. 1.1– 31.03.2020
3. Hardware installation
3.1 Assembly
and dimensions
mm (in)
The k.Air controllers are available in the DIN rail mounting version. See the technical documentation
+0300057EN. The th- Tune terminal is available in the flush-mounted and wall- mounted versions. For
assembly, see the technical leaflets +0500016IE, +0500017IE.
k.air large
Fig.3.a
k.air mini, c.PCOe
Fig.3.b
pGDE
Fig.3.c
ENG
k.Air +030220981 rel. 1.1– 31.03.2020
3. Hardware installation|19
ENG
th-Tune
Fig.3.d
pGDX
Fig.3.e
20|3. Hardware installation
k.Air +030220981 rel. 1.1– 31.03.2020
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100
  • Page 101 101
  • Page 102 102
  • Page 103 103
  • Page 104 104
  • Page 105 105
  • Page 106 106
  • Page 107 107
  • Page 108 108
  • Page 109 109
  • Page 110 110
  • Page 111 111
  • Page 112 112
  • Page 113 113
  • Page 114 114
  • Page 115 115
  • Page 116 116
  • Page 117 117
  • Page 118 118
  • Page 119 119
  • Page 120 120
  • Page 121 121
  • Page 122 122
  • Page 123 123
  • Page 124 124
  • Page 125 125
  • Page 126 126
  • Page 127 127
  • Page 128 128
  • Page 129 129
  • Page 130 130
  • Page 131 131
  • Page 132 132
  • Page 133 133
  • Page 134 134
  • Page 135 135
  • Page 136 136
  • Page 137 137
  • Page 138 138
  • Page 139 139
  • Page 140 140
  • Page 141 141
  • Page 142 142
  • Page 143 143
  • Page 144 144
  • Page 145 145
  • Page 146 146
  • Page 147 147
  • Page 148 148
  • Page 149 149
  • Page 150 150
  • Page 151 151
  • Page 152 152
  • Page 153 153
  • Page 154 154
  • Page 155 155
  • Page 156 156
  • Page 157 157
  • Page 158 158
  • Page 159 159
  • Page 160 160
  • Page 161 161
  • Page 162 162
  • Page 163 163
  • Page 164 164
  • Page 165 165
  • Page 166 166
  • Page 167 167
  • Page 168 168
  • Page 169 169
  • Page 170 170
  • Page 171 171
  • Page 172 172
  • Page 173 173
  • Page 174 174
  • Page 175 175
  • Page 176 176
  • Page 177 177
  • Page 178 178
  • Page 179 179
  • Page 180 180
  • Page 181 181
  • Page 182 182
  • Page 183 183
  • Page 184 184
  • Page 185 185
  • Page 186 186
  • Page 187 187
  • Page 188 188
  • Page 189 189
  • Page 190 190
  • Page 191 191
  • Page 192 192
  • Page 193 193
  • Page 194 194
  • Page 195 195
  • Page 196 196
  • Page 197 197
  • Page 198 198
  • Page 199 199
  • Page 200 200
  • Page 201 201
  • Page 202 202
  • Page 203 203
  • Page 204 204
  • Page 205 205
  • Page 206 206
  • Page 207 207
  • Page 208 208
  • Page 209 209
  • Page 210 210
  • Page 211 211
  • Page 212 212
  • Page 213 213
  • Page 214 214
  • Page 215 215
  • Page 216 216
  • Page 217 217
  • Page 218 218
  • Page 219 219
  • Page 220 220
  • Page 221 221
  • Page 222 222
  • Page 223 223
  • Page 224 224
  • Page 225 225
  • Page 226 226
  • Page 227 227
  • Page 228 228
  • Page 229 229
  • Page 230 230
  • Page 231 231
  • Page 232 232
  • Page 233 233
  • Page 234 234
  • Page 235 235
  • Page 236 236
  • Page 237 237
  • Page 238 238
  • Page 239 239
  • Page 240 240
  • Page 241 241
  • Page 242 242
  • Page 243 243
  • Page 244 244
  • Page 245 245
  • Page 246 246
  • Page 247 247
  • Page 248 248
  • Page 249 249
  • Page 250 250
  • Page 251 251
  • Page 252 252
  • Page 253 253
  • Page 254 254
  • Page 255 255
  • Page 256 256
  • Page 257 257
  • Page 258 258
  • Page 259 259
  • Page 260 260