FläktGroup ISYteq 3030 OM / GB Installation guide

Category
Thermostats
Type
Installation guide
ISYteq 3030
OPERATION MANUAL
LIMITS OF RESPONSIBILITIES
Although FläktGroup has tested and reviewed the documentation contained in this manual, FläktGroup makes no warranty, neither expressed nor
implied, with respect to this manual, including its quality, performance, or fitness for a particular purpose. FläktGroup shall under no circumstances
be liable for direct, indirect, special, incidental or consequential damage arising from the use or the inability to use information contained in this
manual. FläktGroup reserves the right to revise this publication at any time and to make changes to its content without prior notice and has no duty
to provide notice to previous or current owners with respect to such revisions or changes.
3
FläktGroup DC-10650-GB 2022-08_R0 • Subject to modifications
ISYteq 3030
1 Overview of Units and Packaged Content ..................................4
1.1 Using ISYteq 3030 control panels .................................................. 4
1.2 Packaged content ................................................................................ 4
2 Safety and user instructions ..........................................................5
2.1 Availability of the operating manual .............................................. 5
2.2 Scope of the operating manual ......................................................5
2.3 Symbols used ....................................................................................... 5
2.4 Safety instructions: warning and danger symbols .................. 6
2.5 Security symbols used .......................................................................7
2.6 Safety-conscious work procedures...............................................7
2.7 Proper use ..............................................................................................7
2.8 Modifications and changes .............................................................. 8
2.9 Spare parts ............................................................................................ 8
2.10 Disposal ................................................................................................ 8
2.11 Selection and qualification of personnel .................................... 8
3 Technical Description ........................................................................9
3.1 Product features and functions .......................................................9
3.2 ISYteq 3030 connection assignment ......................................... 12
3.3 ISYteq 3030 controller indications .............................................. 15
3.4 FläktGroup Controller Dimensions ............................................. 16
3.5 Models of ISYteq 3030 Display Panels ..................................... 18
4. Assembly and Installation ...........................................................20
4.1 Planning of mounting ........................................................................20
4.2 Electrical connection ........................................................................ 21
4.3 Electrical connection – Network connections .........................24
5 Commissioning .................................................................................26
5.1 Switch on unit ......................................................................................26
5.2 Operation ISYteq 3030-Web ..........................................................26
5.3 Menu bar ...............................................................................................28
5.4 Tile menu ..............................................................................................29
5.5 Tile menu configuration ...................................................................39
5.6 Operating Data .................................................................................... 48
CONTENTS
6 Commissioning of the HMI ........................................................... 56
6.1 ISYteq 3030 Touch 2.1 ......................................................................56
6.2 Commissioning of the ISYteq LCD FSE50 ................................57
7 Operation of the HMI .......................................................................59
7.1 ISYteq 3030 Touch 2.1 ......................................................................59
7.2 Operation ISYteq LCD FSE50 .........................................................68
8 Service and Maintenance .............................................................. 71
8.1 Maintenance ..........................................................................................71
8.2 Disassembly and Disposal .............................................................71
4
FläktGroup DC-10650-GB 2022-08_R0 • Subject to modifications
ISYteq 3030
1 OVERVIEW OF UNITS AND PACKAGED CONTENT
1.1 USING ISYTEQ 3030 CONTROL PANELS
In combination with the ISYteq 3030 controller, the control panels let the user specify setpoint values for the
room air conditioning as well as the display of status and error messages. The features are summarised as
follows:
The assignment of
setpoints such as room or supply-air temperature
fan operating modes such as automatic operation
operating modes of the unit, such as day-night operation
switching times
system parameters
The display of...
actual values
unit status
error messages
1.2 PACKAGED CONTENT
ISYteq 3030 Touch 2.1
Control panel for flush- or surface-mounted socket installation (protection type IP20) consisting of a front frame
and a mounting plate.
Operation manual – document comprising all relevant operations of the controller.
Switchable 120 Ohm terminating resistor for the Modbus line.
Quick installation guide.
ISYteq 3030 LCD FSE50
Control panel for flush- or surface-mounted socket installation (protection type IP20) consisting of a front frame
and a mounting plate.
Operation manual – document comprising all relevant operations of the controller.
120 Ohm terminating resistor for the Modbus line.
Quick installation guide.
Optional:
Sensor – Room-temperature sensor R= 10 kOhm/25 °C
Sensor – Contact sensor for water-inlet temperature type R= 10 kOhm/25 °C
Sensor – Outdoor-temperature sensor type R= 10 kOhm/25 °C
Sensor – CO
2
sensor for air quality type 0-10 V = 0….2000 ppm with Non-Dispersive InfraRed
5
FläktGroup DC-10650-GB 2022-08_R0 • Subject to modifications
ISYteq 3030
2 SAFETY AND USER INSTRUCTIONS
The monitoring and controlling system ISYteq 3030 is built according to the state of technology and the recognized
safety engineering rules.
Operate the ISYteq 3030 System only in fully acceptable technical condition for its intended use. Observe all
relevant safety instructions and precautions in the operating manual. Use proper safety measures to prevent
hazardous situations which, if not avoided, could result in a threat to life and limb of the user or third parties or
damage the system itself, connected units, or other property!
Have all faults repaired by an authorized specialist without delay!
All remarks in this chapter are important and relevant to safety. Yet not all information in this chapter is marked
with special safety symbols.
2.1 AVAILABILITY OF THE OPERATING MANUAL
This operating manual contains important instructions regarding safe and proper operation of the unit.
This operating manual applies to installation companies, operators, building technicians, technical personnel or
instructed persons as well as electricians.
This operating manual must always be available at the location of the unit. When working on the equipment,
observe all instructions and precautions in the current operating manual, the chapter on safety.
2.2 SCOPE OF THE OPERATING MANUAL
This operating manual provides information about the following:
– Assembly/disassembly
– Installation
Commissioning and testing
– Operation
Maintenance and troubleshooting
2.3 SYMBOLS USED
The following symbols to highlight particular text sections are used in this operating manual:
This symbol is used to indicate normal lists.
This symbol indicates handling instructions.
9This symbol indicates the result of an action.
Note!
Additional information about using the ISYteq 3030 control panels is specified here.
6
FläktGroup DC-10650-GB 2022-08_R0 • Subject to modifications
ISYteq 3030
2.4 SAFETY INSTRUCTIONS: WARNING AND DANGER SYMBOLS
The following symbols and notices are provided in appropriate places throughout this document to designate
the safety instructions.
2.4.1 DANGER - Death/serious irreversible injury
Indicates an extremely hazardous situation which will result in death or serious irreversible injury, if the safety
instruction is not followed.
Example:
Electrocution through hazardous voltage will lead to death or serious injury!
Disconnect the unit from the power supply and ensure the power cannot be switched back on.
Ensure the unit is voltage-free and isolated, earth and short circuit the unit, cover or shield off
neighboring live components.
2.4.2 WARNING – Environmental or material damage
Indicates actions that can result in damage to equipment or property.
Examples:
Environmental Damage!
Heavily contaminated filters can have a negative impact on production processes. Depending on
the filtered-out materials, contaminated filters are therefore classified as hazardous waste and
must be properly disposed of according to the prevailing guidelines and laws.
Damage to the unit!
If dampers are abruptly shut during unit operation, the unit can be damaged beyond repair as a
result of negative pressure or overpressure.
7
2.5 SECURITY SYMBOLS USED
Electrical hazard
This symbol indicates a risk of electric shock when working on the equipment.
Personal injury
This section specifies procedures and precautions for the prevention of personal injury.
Environmental damage
This symbol warns about possible damage to the environment.
Damage to the unit
This section specifies procedures and precautions regarding the prevention of equipment
damage.
Risk of electrostatic discharge
This symbol precedes activities where there is a danger of damage to the electronic equipment
by static discharge.
2.6 SAFETY-CONSCIOUS WORK PROCEDURES
When working within range of mains voltage:
Electrocution through hazardous voltage will lead to death or serious injury!
Disconnect the unit from the power supply and ensure the power cannot be switched back on.
Ensure the unit is voltage-free and isolated, earth and short circuit the unit, cover or shield off
neighboring live components.
For all kinds of work:
Risk of electrostatic discharge!
While carrying out adjustment work on the ISYteq 3030 control panel, make sure that you discharge
yourself statically before manipulating PC boards and installing electrical components.
Observe all assembly instructions for the ISYteq 3030 control panels.
Fluctuations and imbalances in the supply voltage may not exceed the tolerance limits specified in the technical
data, otherwise functional failures and limit states cannot be excluded.
2.7 PROPER USE
The ISYteq 3030 control system has been specifically designed to suit all related products within the FläktGroup portfolio,
and is primarily intended to perform the following functions:
to regulate the room/supply-air temperature
to regulate the fan speed
air heating and/or cooling
Proper use also includes observance of the operating manual and the inspection and maintenance conditions stipulated
by FläktGroup.
FläktGroup DC-10650-GB 2022-08_R0 • Subject to modifications
ISYteq 3030
8
FläktGroup DC-10650-GB 2022-08_R0 • Subject to modifications
ISYteq 3030
IMPROPER USE:
Any use other than that described above is considered improper. The manufacturer/supplier is not liable for any
damages arising from improper use. The user alone bears the risk.
PERSONAL INJURY!
It is forbidden to operate the ISYteq 3030 controls platform in the following conditions:
in areas subject to explosion risk
in environments with conductive dust
in environments with strong electromagnetic fields
in environments with corrosive and/or aggressive atmosphere
in humid rooms and wet areas
in areas with high dust content
2.8 MODIFICATIONS AND CHANGES
Changes, alterations or modifications of the ISYteq 3030 controls platform are forbidden. Any changes or
modifications will invalidate the CE conformity and void warranty.
2.9 SPARE PARTS
Only original FläktGroup spare parts are allowed, since FläktGroup is not liable if third-party spare parts are used.
2.10 DISPOSAL
Equipment and operating supply materials must be disposed of according to the material type in a safe and
environmentally friendly manner.
2.11 SELECTION AND QUALIFICATION OF PERSONNEL
Ensure that every person commissioned to work on the ISYteq 3030 control system has completely read and
understood this operating manual – especially the chapter on safety.
Read this document fully before commencing any work, and not while performing a task.
Electrical connections may only be carried out by qualified licensed staff or other individuals with proper
professional training and experience in the following areas:
Occupational health and safety regulations
Accident prevention regulations
Directives and recognized codes of practice
All skilled staff must be able to assess the work entrusted to them and must be able to recognize and avoid all
associated dangers.
9
FläktGroup DC-10650-GB 2022-08_R0 • Subject to modifications
ISYteq 3030
3 TECHNICAL DESCRIPTION
3.1 PRODUCT FEATURES AND FUNCTIONS
The ISYteq 3030 controller is a microprocessor-based, programmable electronic controller, featuring a multitasking
operating system, compatible with the FläktGroup decentral units. ISYteq 3030 has been developed to provide solutions
for decentral air conditioning. It can be connected via RS485, Ethernet LAN or WLAN with Modbus/BACnet protocols to
the BMS (Building Management System). The built-in web server supports HTML standards.
3.1.1 Controller board
Figure 1: Controller board
Electrical connection
Voltage supply AC 230 V, 50 …60 Hz recommended fuse protection 16 A
Max. power consumption AC 10.0 VA without external load
Communication
2× RS485 (X1) type of cable min. 2× 0.8 mm², wires twisted-pair and shielded
protocol MS/TP, Modbus RTU master, Modbus RTU slave
baud rate 9600, 19200, 38400, 57600, 76800, 115200
Interfaces
Wi-Fi TCP/UDP BACnet IP on UDP, Modbus IP, HTTP, FTP, ICMP, DHCP
802.11 b/g/n
802.11 n (2.4 GHz)
Bluetooth communication mode BLE (Bluetooth Low Energy) with app (Android)
Antenna connection
U.FL connector WLAN and Bluetooth U.FL / IPEX connector (male)
impedance: 50 Ohm
supported frequency range: 2.4 GHz to 2.5 GHz
10
FläktGroup DC-10650-GB 2022-08_R0 • Subject to modifications
ISYteq 3030
Input
Analog (X2, X3) 1× AI (U1) 0 … 10 V
input impedance: 200 k against G0
active sensor CO
2
/ temperature, humidity sensor
4× AI (U2, U3, U4, U5) NTC10k
input impedance: 200 k against G0, also usable as
NTC10k
input (Imax: 1 mA)
2× AI (U6, U7) 0 ... 10 V
input impedance: 1,6 k against internal 10 V, also usable
as DI for open collector outputs (Imax: 7 mA)
Digital (X3) 2× DI (I1, I2) low (0 - off) - open, high (1 - on) - close
internal 6.6 k against DC 24 V (Imax: 4 mA)
designed for switches connected to G0
2× DI (C1, C2) low (0 - off) - open, high (1 - on) - close
internal 1.6 k against DC 5 V (Imax: 3.2 mA)
designed for switches connected to G0
Output
Analog (X3) 2× AO (Y1, Y2) 0 … 10 V
max. 10 mA each
Digital (X5) 4× DO (V1 …V4) max. 1.2 A at AC 250 V each
solid-state relay - Triac (normally open contact)
internal connected to voltage supply AC 230 V (Imax: 1.2 A)
Digital (X6) 4× DO (S1, S2, S3; CP) relay contact (normally open contact)
max. 5 A at AC 250 V each
potential-loaded
internal connected to voltage supply AC 230 V (Imax: 5 A)
Memory
microSD flash card 4 GB for trend data, application, CAD drawing, languages, firmware
Operating conditions
Temperature -20 …+50 °C
Humidity 10 …95 % rH. non-condensing
Vibration 5.9 m/s² (0.6 G) max. 10 … 150 Hz
Air pressure 78 …106 kPa up to 2000 m above mean sea level
Storage conditions
Temperature -40 …+70 °C
Humidity 10 …95 % rH. non-condensing
Vibration
(transport)
5.9 m/s² (0.6 G) max. 10 … 150 Hz
Vibration (storage) 9.8 m/s² (1 G) max. 10 … 150 Hz
Air pressure 70 …106 kPa up to 3000 m above mean sea level
Housing
Dimensions 170.2 × 36.5 × 107.4 length × width × height (installation depth) in mm
Weight 200 g
CE conformity
see EU declaration of conformity
Table 1: Technical description of the controller board
11
FläktGroup DC-10650-GB 2022-08_R0 • Subject to modifications
ISYteq 3030
3.1.2 Ethernet extension card
Figure 2: Ethernet extension card
Electrical connection
Voltage supply DC 5 V
Max. power consumption 0.2 W
Interfaces
Ethernet 1 x xRJ45 connector
10/100 Base-T/TX
Transfer rates 10/100 Mbit/s
Switch half duplex/full duplex automatic recognition, automatic change
Operating conditions
Temperature -20 …+50 °C
Humidity 10 …95 % rH. non-condensing
Vibration 5.9 m/s² (0.6 G) max. 10 …150 Hz
Air pressure 78 …106 kPa up to 2000 m above mean sea level
Storage conditions
Temperature -40 …+70 °C
Humidity 10 …95 % rH. non-condensing
Vibration (transport) 5.9 m/s² (0.6 G) max. 10 …150 Hz
Vibration (storage) 9.8 m/s² (1 G) max. 10 …150 Hz
Air pressure 70 …106 kPa up to 3000 m above mean sea level
Housing
Dimensions 52.0 × 25.0 × 14.3 length × width × height (installation depth) in mm
Weight 8 g
Table 2: Technical description of the ethernet extension card
12
FläktGroup DC-10650-GB 2022-08_R0 • Subject to modifications
ISYteq 3030
3.2 ISYTEQ 3030 CONNECTION ASSIGNMENT
3.2.1 Controller board
Figure 3: Controller board
Position Designation Description
X1
124 DC 24 V out, total external load max 10 W, HMI ground
connection, 0 V
2G0
3A1 RS485-1 (BMS communication)
4B1
5A2 RS485-2 (internal communication)
6B2
X2
124 DC 24 V out, total external load max. 10 W, (active sensor
CO
2
/ temperature, humidity sensor)
ground connection, 0 V
2G0
3U1 analogue input, 0 …10 V
4 S RS485 shield
5A2 RS485-2 (internal communication)
6B2
X3
1I1 digital input, window contact (on/off switch)
2I2 digital input, presence contact (economy/comfort switch)
3 U2 analogue input, NTC Change-Over (INL temperature)
4U3 analogue input, NTC room temperature (IDA temperature)
5U4 analogue input, UNI outside air temperature (ODA
temperature)
6U5 analogue input, supply air temperature (SUP temperature)
7C1 digital input (counter), condensate pump DI-R On
13
FläktGroup DC-10650-GB 2022-08_R0 • Subject to modifications
ISYteq 3030
X3
8C2 digital input (counter), condensate pump DI-R alarm
9Y1 analogue output, 0 …10 V, fan EC-motor 1, set speed
10 Y2 analogue output, 0 …10 V, fan EC-motor 2, set speed
11 U6 analogue input, fan EC-motor 1, alarm
12 U7 analogue input, fan EC-motor 2, alarm
X4
1G0
ground connection, 0 V
2G0
3G0
4G0
5G0
6G0
75V DC 5 V
8G0
ground connection, 0 V9G0
10 G0
11 STP
not connected
12 STP
X5
1V4
valve heating, potential loaded with L-230V
2V3
3V2
valve cooling, potential loaded with L-230V
4V1
5N6
N-230V
6N5
X6
1CP digital output, condensate pump, F2 fused with 250 V
0.63 A, potential loaded with L-230V
2S3 digital output, fan AC S3, potential loaded with L-230V
3S2 digital output, fan AC S2, potential loaded with L-230V
4S1 digital output, fan EC/AC S1, potential loaded with L-230V
14
FläktGroup DC-10650-GB 2022-08_R0 • Subject to modifications
ISYteq 3030
X7
1EC digital output, fan EC S1, potential loaded with L-230V
2C0 C1, L AC 230 V output
3 L L-230V, F1 fused with 250 V 6.3 A
N-230V power supply
4 N
5 N
N-230V
6 N
7 N
8 N
9STP
not connected
10 STP
Other Designation Description
1U.FL connector
U.FL / IPEX connector (male) for WLAN and Bluetooth
Impedance: 50 Ohm
supported frequency range: 2.4 GHz to 2.5 GHz
2 - for ethernet adapter, e.g. MTC ETH-V (F 04 90 00); for further
data and mounting see corresponding documentation
3SD card slot for microSD flash card 4 GB
Table 3: Connection assignment of the controller board
3.2.2 Ethernet extension card
Figure 4: Ethernet extension card
Pos. Designation Description
1X1 Ethernet (RJ45)
2X2 Bus connection to controller
Table 4: Connection assignment of the ethernet extension card
15
FläktGroup DC-10650-GB 2022-08_R0 • Subject to modifications
ISYteq 3030
3.3 ISYTEQ 3030 CONTROLLER INDICATIONS
3.3.1 Controller board
Figure 5: Controller board
LED
Designation Display Description
LED Power
pos. 1
green
lighting: power supply available
LED Relay
pos. 2
yellow
lighting: relay active
LED Bluetooth
pos. 3
green
lighting: identification of the selected device via Bluetooth
LED Status 1
pos. 4
green
lIndication booting
blinking: cycle 40 Ms
Indication operation
lighting: no program enable
blinking: program execution runs in flashing rhythm. The
flashing slows down with increasing program execution time
(size).
LED Status 2
pos. 4
Indication operation
blinking: processing of timers
off: normal mode
LED Alarm
pos. 5
red
depends on application
LED Run
pos. 6
green
depends on application
Buzzer
Designation Display Description
Buzzer
pos. 7
-sound: identification of the selected device via “beep” sound
Table 5: Controller indications of the controller board
16
FläktGroup DC-10650-GB 2022-08_R0 • Subject to modifications
ISYteq 3030
3.3.2 Ethernet extension card
Figure 6: Ethernet extension card
LED
Designation Display Description
Speed
pos. 1
yellow
lighting: Ethernet 100 Mbit/s
off: Ethernet 10 Mbit/s
Link
pos. 2
green
lighting: Ethernet link available, no data exchange
flashing: Ethernet link available and data exchange
off: no Ethernet link available
Table 6: Controller indications of the ethernet extension card
3.4 FLÄKTGROUP CONTROLLER DIMENSIONS
3.4.1 Controller board
Figure 7: Controller board dimensions
All dimensions are shown in millimetres.
17
FläktGroup DC-10650-GB 2022-08_R0 • Subject to modifications
ISYteq 3030
3.4.2 Drilling holes
Figure 8: Drilling holes
All dimensions are shown in millimetres.
3.4.3 Ethernet extension card
Figure 9: Ethernet extension card dimensions
All dimensions are shown in millimetres.
18
FläktGroup DC-10650-GB 2022-08_R0 • Subject to modifications
ISYteq 3030
3.5 MODELS OF ISYTEQ 3030 DISPLAY PANELS
3.5.1 ISYteq 3030 Touch 2.1
This Touch 2.1 control panel is designed as a compact user interface to the FläktGroup controllers. Due to its size, it can
be integrated into rooms more inconspicuously. Despite its small size, it is a complete and powerful control panel that
supports almost all functions of FläktGroup controllers.
The user will only see the controls on the display whose functionality is reported by the controller. Operating elements
that are not required are hidden.
Figure 10: Touch 2.1 display with a white frame
3.5.1.1 Space requirements
The control panel is mechanically designed for indoor installation in a standard flush box (68 mm). If the room temperature
is to be measured via the integrated sensor in the control panel, an installation with a standard surface-mounted device
box is more suitable.
Figure 11: Space requirements
Touch 2.1 display
Length / width (mm) 86.7 / 86.7
Power supply 12-48 VDC
Backlight LED
Operating temperature 0 °C to +40 °C
Storage temperature -30 °C to +60 °C
Integrated temperature sensor Yes
Protection class IP20
Table 7: Touch 2.1 display
19
FläktGroup DC-10650-GB 2022-08_R0 • Subject to modifications
ISYteq 3030
3.5.2 ISYteq LCD FSE50
This LCD FSE50 control panel is designed as a simple and cost-efficient user interface to the FläktGroup controllers. It
supports the basic functions to control room climate.
Figure 12: ISYteq LCD FSE50
3.5.2.1 Space requirements
Figure 13: Space requirements
LCD FSE50 display
Length / width (mm) 135 / 78
Power supply 24 VAC, 24 (+/- 10%) VDC
Backlight LCD
Operating temperature 0 °C to +40 °C
Storage temperature -20 °C to +50 °C
Integrated temperature sensor Yes
Protection class IP30
Table 8: LCD FSE50 display
20
FläktGroup DC-10650-GB 2022-08_R0 • Subject to modifications
ISYteq 3030
4. ASSEMBLY AND INSTALLATION
Electrocution through hazardous voltage will lead to death or serious injury!
The electrical installation and (dis)assembly of the ISYteq control panel should only be carried out by
qualified electricians in compliance with this operating manual and current EU standards.
Before drilling, ensure that the drilling area is free from electrical cables and pipes.
Only indoor mounting of the ISYteq 3030 control panel is allowed.
4.1 PLANNING OF MOUNTING
Note!
The installation site of the ISYteq 3030 control panel or room temperature sensor is crucial for the
precise measurement of room temperature. Therefore, the ISYteq 3030 control panels or sensors must
not:
be fitted next to doors, windows, passages etc., since intense movement of air can cause incorrect
measurements,
be mounted to hot or cold walls (e.g. chimney, outside wall), since the wall temperature can cause
incorrect measurements,
be fitted behind curtains or net curtains, since the insulating layers of air can cause incorrect
measurements,
be mounted adjacent to the unit’s discharge grilles, since the discharge temperature can cause
incorrect measurements,
be fitted below cold surfaces like windows, since descending cold air flow can cause incorrect
measurements.
Figure 14: Mounting of the ISYteq 3030 control panels/room temperature sensor
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72

FläktGroup ISYteq 3030 OM / GB Installation guide

Category
Thermostats
Type
Installation guide