Digital Monitoring Products XTLN-WiFi Installation guide

Category
Serial switch boxes
Type
Installation guide

This manual is also suitable for

InstallatIon GuIde
Xtln/Xtln-WIFI Panel
MODEL XTLN/XTLN-WiFi
INSTALLATION GUIDE
FCC NOTICE
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant
to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful
interference in a residential installation. This equipment generates, uses and can radiate radio frequency
energy and, if not installed and used in accordance with the instructions, may cause harmful interference
to radio communications. However, there is no guarantee that interference will not occur in a particular
installation. If this equipment does cause harmful interference to radio or television reception, which can be
determined by turning the equipment off and on, the user is encouraged to try to correct the interference
by one or more of the following measures:
• Reorient or relocate the receiving antenna.
• Increase the separation between the equipment and receiver.
• Connect the equipment into an outlet on a circuit different from that to which the receiver is
connected.
• Consult the dealer or an experienced radio/TV technician for help.
Changesormodicationsnotexpresslyapprovedbythepartyresponsibleforcompliancecouldvoidthe
user’s authority to operate the equipment.
This device has been designed to operate with the integrated 1100 Series PCB antenna having a maximum
gain of 1.8 dB. Antennas having a gain greater than 1.8 dB are strictly prohibited for use with this device.
The required antenna impedance is 50 ohms.
If necessary, the installer should consult the dealer or an experienced radio/television technician
foradditionalsuggestions.Theinstallermayndthefollowingbooklet,preparedbytheFederal
Communications Commission, helpful:
“How to identify and Resolve Radio-TV Interference Problems.”
ThisbookletisavailablefromtheU.S.GovernmentPrintingOfce,WashingtonD.C.20402
StockNo.004-000-00345-4
©2015DigitalMonitoringProducts,Inc.
InformationfurnishedbyDMPisbelievedtobeaccurateandreliable.
This information is subject to change without notice.
XTLN/XTLN-WiFi Installation Guide Digital Monitoring Products
i
Table of ConTenTs
Panel Specications
1.1 .............................................................................Power Supply 1
1.2 ..........................................................................Communication 1
1.3 .................................................................................... Keypads 1
1.4 ....................................................................... Number of Zones 1
1.5 ..............................................................Enclosure Specications 1
Introduction
2.1 ................................................................System Congurations 1
2.2 ............................................................................Caution Notes 1
2.3 ............................................................. Compliance Instructions 1
System Components
3.1 ......................................................................Accessory Devices 2
Installation
4.1 ................................................... Mounting Location Information 3
4.2 .............................................................. Mounting the Enclosure 3
Primary Power Supply
5.1 ................................................................................... DC Input 3
Secondary Power Supply
6.1 ......................................................................... Standby Battery 4
6.2 ..............................................................................Replacement 4
6.3 .................................................................... Battery Supervision 4
LED Operation
7.1 ...............................................................................Backlit Logo 5
On-Board Network (XTLN only)
8.1 ................................................................................ Description 5
8.2 ............................................................................Ethernet LEDs 5
On-Board WiFi Network (XTLN-WiFi only)
9.1 ................................................................................ Description 5
9.2 ..................................................................................WiFi LEDs 5
RESET Button
10.1 .............................................................................. Description 5
Programming Connection
11.1 ..........................................................Programming Connection 5
On-Board 1100 Series Wireless
12.1 ..................................................................... Wireless Antenna 6
12.2 ............................................................ Wireless LED Operation 6
Wireless Keypads
13.1 ....................................................................Mounting Keypads 6
13.2 ..................................................... Wireless Keypad Association 6
Wireless Zones
14.1 .............................................................................. Description 6
Wireless Key Fobs and Outputs
15.1 .............................................................................. Description 6
Flash LOAD Button
16.1 .............................................................................. Description 7
Listed Compliance Specications
17.1 ..............................................................................Introduction 8
17.2 ............................................................................. Use Marking 8
17.3 ................................................................................... NFPA 72 8
17.4 ....................................................................... Types Of Service 8
17.5 ......................................................................... Bypass Reports 8
17.6 ........................................................................ Battery Standby 8
Household Burglar-Alarm System Units
ANSI/UL 1023
18.1 .............................................................................. Bell Cutoff 8
18.2 ..............................................................................Entry Delay 8
18.3 ................................................................................Exit Delay 8
18.4 ......................................................... Wireless External Contact 8
18.5 ........................................................ Wireless Supervision Time 8
18.6 ...................................................Wireless Audible Annunciation 8
18.7 .......................................................................... Panel location 8
18.8 ........................................................................ Test Frequency 8
Central Station Burglar Alarm Units
ANSI/UL 1610
19.1 ..............................................................................Supervision 9
19.2 ........................................................................Remote Disarm 9
19.3 .........................................................................Central Station 9
Household Fire Warning System
ANSI/UL 985 NFPA 72 Specications
20.1 ............................................................... Bell Output Denition 9
20.2 ................................................................... Household System 9
20.3 ........................................................ Wireless Supervision Time 9
20.4 ........................................................................ Test Frequency 9
20.5 .........................................................................Wired Modules 9
False Alarm Reduction Programmable Options ANSI/SIA CP-01-2010
19.1 ................... Shipping Defaults and Recommended Programming 10
Revisions to This Document
Certications ...............................................................................12
XTLN/XTLN-WiFi Installation Guide Digital Monitoring Products
1
Panel sPecifications
Panel Specications
1.1 Power Supply
Input: 12VDC
StandbyBattery: 3.7VDCLithium
All circuits inherent power limited
1.2 Communication
Built-innetworkcommunicationtoDMPModelSCS-1RorSCS-VRReceivers.
1.3 Keypads
Youcanconnectupto4alphanumeric9000SeriesWirelessKeypads.
1.4 Number of Zones
• XTLN/XTLN-WiFihas28wirelessinitiatingzonesnumbered1-28
• ZoneandOutputnumbers31to34and41to44cansupport1100SeriesKeyFobs,OutputModules,
or sirens
1.5 Enclosure Specications
TheXTLN/XTLN-WiFipanelshipsinaplasticenclosurewithauser’sguideandprogrammingsheet.
Size Color
5.5”Wx3.75”Hx1”D White(W)
Introduction
2.1 System Congurations
The panel can be programmed to operate as any of the following system types:
• All/Perimetersystemthatprovidesoneperimeterareaandoneinteriorarea
• Home/Sleep/Awaysystemthatprovidesoneperimeter,oneinterior,andonebedroomarea.The
bedroom area provides for any protection devices the user wants disarmed during their sleeping hours
and armed in the Away mode.
• Sixareasystemthatprovidesareasofprotectionthatcanbeindependentlyarmedordisarmed.
2.2 Caution Notes
Throughoutthisguideyouwillseecautionnotescontaininginformationyouneedtoknowwheninstalling
thepanel.Thesecautionsareindicatedwithayieldsign.Wheneveryouseeacautionnote,makesureyou
completely read and understand its information. Failing to follow the caution note can cause damage to the
equipment or improper operation of one or more components in the system.
2.3 Compliance Instructions
ForapplicationsthatmustconformtoalocalauthoritiesinstallationstandardoraNationalRecognized
TestingLaboratorycerticatedsystem,pleaseseetheListedComplianceSpecicationssectionneartheend
of this guide for additional instructions.
IntroductIon
Digital Monitoring Products XTLN/XTLN-WiFi Installation Guide
2
system components
System Components
3.1 Accessory Devices
DMP Two-Way Wireless Devices
1100R Repeater Provides additional range for wireless devices.
1101UniversalTransmitter Provides both internal and external contacts that may be used at the same time to yield two
individualreportingzonesfromonewirelesstransmitter.
1102UniversalTransmitter Provides one external contact.
1103UniversalTransmitter
Provides both internal and external contacts that may be used at the same time to yield two
individual reporting zones from one wireless transmitter. Requires EOL resistor for external
contact. ProvidesDisarm/Disablefunctionality.
1106UniversalTransmitter Provides both internal and external contacts that may be used at the same time to yield two
individualreportingzonesfromonewirelesstransmitter.
1107MicroWindowTransmitter* Provides a wireless window transmitter.
1114Four-ZoneExpander* ProvidesfourwirelesszoneswithEOLresisters.
1116RelayOutput* Provides one Form C relay.
1117LEDAnnunciator* Provides a visual system status indicator.
1119DoorSounder* Provides a wireless sounder with integrated door contact
1121PIRMotionDetector* Provides motion detection with pet immunity.
1126RPIRMotionDetector* CeilingmountmotiondetectorwithpanelprogrammablesensitivityandDisarm/Disable
functionality.
1127C/1127WPIRMotion
Detector
WallmountmotiondetectorwithpanelprogrammablesensitivityandDisarm/Disable
functionality.
1129GlassbreakDetector* Detectstheshatteringofframedglassmountedinanoutsidewallandprovidesfull-pattern
coverage and false-alarm immunity.
1131RecessedContact*
Provides concealed protection for doors, windows or other applications.
1135/1135DBSiren* Provides a wireless siren
1139BillTrap* Provides a silent alarm option for use in cash drawers.
1141WallButton* Onebuttonwallmountedwirelesstransmitter.
1142BCTwo-buttonPanicBelt
Clip Transmitter
Provides portable two-button panic operation.
1142Two-buttonPanic
Transmitter
Provides permanently mounted under-the-counter two-button panic operation.
1145-4(Four-Button)*
1145-2(Two-Button)*
1145-1(One-Button)*
KeyFobtransmittersdesignedtoclipontoakeyringorlanyard.
1161ResidentialSmokeDetector Residentialsmokedetectorwithsounder.
1162ResidentialSmokeDetector Residentialsmoke/heatdetectorwithsounderandxedrate-of-riseheatdetector.
1164WirelessSynchronized
SmokeDetector
Commercialorresidential,batterypowered,wireless,lowprole,photoelectricsmoke
detector,withsynchronizingsounder.
1183-135FHeatDetector Fixed temperature heat detector
1183-135RHeatDetector Fixed temperature and rate-of-rise heat detector
1184CarbonMonoxideDetector CarbonMonoxidedetector.
Interface Module
738ZZ-WaveInterfaceModule* ProvidesconnectionforZ-Wavemodules.
Keypads
9000SeriesLCDkeypads Allowsyoutocontrolthepanelfromvariousremotelocationsusing9000SeriesWireless
Keypads.Connectuptofour9060,9063WirelessKeypads.
9800SeriesWireless
Graphic
Touchscreenkeypads
Allowsyoutocontrolthepanelfromvariousremotelocations.Connectuptofourkeypads.
9862WirelessKeypads.
* These devices have not been investigated and shall not be used in listed installations
XTLN/XTLN-WiFi Installation Guide Digital Monitoring Products
3
InstallatIon
Installation
4.1 Mounting Location Information
A location should be selected that is centrally located between the 1100 Series transmitters used in the
installation.InstalltheXTLN/XTLN-WiFiawayfrommetalobjects.Mountingthepanelonornearmetal
surfacesimpairsperformance.Whenselectingthepropermountinglocationofatransmitter,refertothe
LEDSurveyOperationsectionofthespecicinstallationguideforthetransmitterbeinginstalled.
4.2 Mounting the Enclosure
The enclosure for the panel must be mounted using the provided #6 screws in the four mounting holes
showninFigure2.Mounttheenclosureinasecure,dryplaceawayfrommetalobjectstoprotectthepanel
fromdamageduetotamperingortheelements.Mountthepanelaminimumof4feetfromanywireless
transmitters or repeaters. It is not necessary to remove the PCB when installing the enclosure.
Mounting Hole Locations
Network
Connector
RESET
S1
LOAD
S2
BAT
J7
PROG
RED
PWR
MODEL XTLN
TX RF RX
SN
J1
Figure 1: Mounting Hole Locations
Primary Power Supply
5.1 DC Input
MountthepanelnearawalloutletfortheModel372-500plug-inDCtransformer.Inadditiontopoweringthe
panel,theDCplug-intransformeralsochargestheback-upbattery.The372-500mustbelocatedwithin100
feetofthepanelusing22AWGwire.Usethefollowingstepstoconnecttheplug-intransformer:
OBSERVE POLARITY
1.Using22AWGwire,connectthepanelPWRrstterminal(+)tothepositiveterminalonthepower
supply.
2.ConnectthepanelPWRsecondterminal(-)tothenegativeterminalonthepowersupply.
3.Plugthepowersupplyintoa120VoltAC,60Hzdedicatedoutletnotcontrolledbyaswitch.
Wire Exits for DC
Power Supply
+
Model 372-500
DC Plug-in
Power
Supply
Use 22 AWG for
Power Supply connection
_
RESET
S1
LOAD
S2
BAT
J7
PROG
RED
PWR
MODEL XTLN
TX RF RX
SN
J1
Figure 2: DC Power Supply Connection
Digital Monitoring Products XTLN/XTLN-WiFi Installation Guide
4
InstallatIon
Secondary Power Supply
6.1 Standby Battery
TheXTLN/XTLN-WiFirechargeablebatteryisusedtoprovidebackupbatterypowerwhenDCpowerisnot
available.Thebatteryisintendedforbackuppoweronlyandnottooperatethepanelonadailybasis.If
the battery is low, or not plugged into the BAT battery connector, a low battery condition is indicated by the
panel.
Note:Ifremovingthepanelfromservice,disconnectthebackupbatteryfromtheBATconnector.
6.2 Replacement
UsethefollowingstepstoreplacetheXTLN/XTLN-WiFistandbybattery.DMPrecommendsreplacingthe
batteryevery3yearsundernormaluse.
1.Unplugthebatteryconnector(BAT)fromtheXTLN/XTLN-WiFipanel.
2.Ifinstalled,removethescrewfromthePCB.
3.LoosenthetopPCBsnaps.
4.LeanthepanelPCBforwardandliftoutfromthebottomPCBsnaps.
5. Remove and properly dispose of the used battery.
Caution:Riskofre,explosion,andburns.Donotdisassemble,heatabove212°F(100°C),
or incinerate. Properly dispose of used batteries.
6.PlacethenewbatteryintotheXTLN/XTLN-WiFihousingbasewiththebatterywiresdirectedtoward
thebottomrightcorner.SeeFigure4.
7.SettheXTLN/XTLN-WiFiPCBintothebottomsnapsandpressintothetopsnapstosecureinplace.
8.Plugthebatteryintothepanelconnector(BAT).
6.3 Battery Supervision
ThepanelteststhebatteryonceeveryhourwhenDCpowerispresent.Thistestoccurs15minutespast
eachhourandlastsforveseconds.Aloadisplacedonthebatteryandifthebatteryvoltageislow,alow
batteryisdetected.IfDCpowerhasfailed,alowbatteryisdetectedanytimethebatteryvoltagefalls
below3.7V.
RESET
S1
LOAD
S2
BAT
J7
PROG
RED
PWR
MODEL XTLN
TX RF RX
SN
J1
PCB Screw Locations
Top PCB Snaps
Bottom PCB Snaps
Battery
connector
3.7V
Rechargeable
Battery
Figure 4: Standby Battery ReplacementFigure 3: PCB Screw Locations
XTLN/XTLN-WiFi Installation Guide Digital Monitoring Products
5
InstallatIon
LED Operation
7.1 Backlit Logo
ThebacklitlogoindicatesthePowerandArmedstatusofthepanel.Dependingontheoperation,theLED
displaysinRedorGreenaslistedinthetable.
Color and Activity Operation
GreenSteady PanelDisarmed,PrimaryPowerOK,BatteryOK
GreenBlinking PanelDisarmed,PrimaryPowerOK,BatteryFault
NoLight PanelDisarmed,PrimaryPowerFault,BatteryOK
Red Steady PanelArmed,PrimaryPowerOK,BatteryOK
Red/GreenAlternate PanelArmed,PrimaryPowerOK,BatteryFault
RedBlinking PanelArmed,PrimaryPowerFault,BatteryOK
On-Board Network (XTLN only)
8.1 Description
TheETHERNETConnectorconnectsdirectlytoanEthernetnetworkusingastandardCAT-5patchcable.
8.2 Ethernet LEDs
ThetwoLEDs,locatedontheleftsideoftheETHERNETConnector,indicatenetworkoperation.Thetop,
LinkLEDisablinkinggreenlightwhenmessagesarebeingreceivedortransmitted.Thebottom,ActivityLED
ashesyellowtoindicate100Mbits/second.
On-Board WiFi Network (XTLN-WiFi only)
9.1 Description
TheXTLN-WiFiconnectsdirectlytoaWiFinetworkforencryptedTCPcommunicationusingaWireless-B/G
connection.TheXTLN-WiFiuseswireless802.11b/gWiFitechnology,whichcantravel125ft.indoorsandcan
reachoutto460ft.outdoorswithaclearlineofsight.
Note:RangeforWiFicommunicationhasnotbeeninvestigatedbyUL.
9.2 WiFi LEDs
ThetwoWiFiLEDs,locatedinthecenterofthecircuitboard,indicatenetworkoperation.Theleft
WiFi-1LEDisagreenlightthatissolidwhenthenetworkisconnectedandblinksonandoffwhenthereisno
networkconnectivity.TherightWiFi-2LEDisayellowlightandblinkswhenmessagesarebeingreceivedor
transmitted.
RESET Button
10.1 Description
TheRESETbuttonislocatedontherightsideofthecircuitboardandisusedtoresettheXTLN/XTLN-WiFi
microprocessor.Toresetthepanelpriortoreprogramming,presstheRESETbuttonwithoutpoweringdown
thesystem.Afterresettingthepanel,beginprogrammingwithin30minutes.Ifyouwaitlongerthan30
minutes, you must reset the panel again.
Programming (PROG) Connection
11.1 Programming Connection
Alocking4-pinPROGheaderisprovidedtoconnectakeypadwhenusingaDMPModel330Programming
Cable.ThisprovidesaquickandeasyconnectionforprogrammingtheXTLN/XTLN-WiFipanel.After
programmingiscomplete,removethekeypad.
Installing the 738Z
Toconnectthewiringofthe738ZtothePROGheaderofthepanel,useaPC-0140ConnectorAssembly
(includedwiththe738Z)forconnectionofaModel300harness.WhenusedwiththeXTLN/XTLN-WiFi,the
738Zoperatesusingthebackupbatterywhenprimarypowerisnotpresent.
Note:ThePROGheaderisnotintendedtoprovideaKeypadDataBusconnection.Theprogrammingkeypad
is operational only when primary power is applied to the panel.
Digital Monitoring Products XTLN/XTLN-WiFi Installation Guide
6
InstallatIon
On-Board 1100 Series Wireless
12.1 Wireless Antenna
TheXTLN/XTLN-WiFiWirelessAntennaisintegratedintothecircuitboard.Thepanel’sbuilt-inwireless
receiveroperateswithDMP1100Seriestransmitters.Seesection3.1foralistofaccessorydevices.
12.2 Wireless LED Operation
Green (TX):ThegreenLEDasheseverytimethereceivertransmits(32timespersecond).Ifthepanel
isreset,orthepanelispoweredoff,thegreenLEDisoff.Undernormaloperation,thegreenLEDashes
constantly with no interruption or change.
Yellow (RX):TheyellowLEDasheseverytimethepanelreceivesamessagefromaprogrammedwireless
transmitter.Whenamessageissentbyatransmitter,typicallybypressingorreleasingthetamperswitch,
theyellowLEDshouldashindicatingthatthepanelreceivedamessagefromthetransmitter.IftheLED
neverashes,thetransmitterisnotgettingthroughtothepanel.Thiscouldbebecauseofamisprogrammed
serialnumberorthetransmitteristoofaraway.Undernormaloperation,theyellowLEDashesatevery
tripofeverywirelesstransmitterandwhenthetransmittersperformtheirperiodiccheck-in.Itisnot
unusualforthisLEDtostayoffformanyminutesatatimewhennotransmittersarecommunicating.
Wireless Keypads
13.1 Mounting Keypads
DMPkeypadshaveremovablecoversthatallowthebasetobemountedonawall,deskstandorotherat
surface using the screw holes provided on each corner.
13.2 Wireless Keypad Association
EnableWirelessKeypadAssociationoperationonboththekeypadandpanel.
Toenableassociationoperationinthekeypad,accesstheInstallerOptionsMenu(3577(INST)).Thekeypad
logoLEDsturnoffuntilassociationissuccessful.Referto9000SeriesWirelessKeypadInstallationGuide
LT-1107orthe9862SeriesWirelessGraphicsKeypadInstallationGuideLT-1367formoreinformation.
To enable association in the panel, reset the panel three times as described below and observe the operation
ofGreenLEDandRedBacklitLogoLED’s.SeeFigure5forBacklitLogoLEDlocation.
1. PressRESET.
2. TheGreenLEDturnsoff.
3. TheGreenLEDandRedLEDturnonsteadythenoff.
4. TheGreenLEDturnsonagain.
Repeatsteps1-4twomoretimesoruntilboththeGreenLEDand
RedLEDremainonsteady.
For60secondsthepanellistensforwirelesskeypadsthatareinthe
InstallerOptionsMenu(3577CMD)andhavenotbeenprogrammed,
orassociatedintoanotherpanel.Wirelesskeypadsareassignedto
therstopendevicepositionautomaticallybasedupontheorderin
whichtheyaredetected.ThekeypadlogoturnsGreentoindicateit
has been associated with the panel.
Wireless Zones
14.1 Description
XTLN/XTLN-WiFipanelsprovide28wirelesszonesnumbered1to28.Adefaultzonename,zonetype,and
areaassignmentaredescribedintheXTLN/XTLN-WiFiProgrammingGuide(LT-1221)andcanbechangedin
Zone Information programming as needed. The defaults are provided as a programming convenience to help
reduce installation time.
Wireless Key Fobs and Outputs
15.1 Description
XTLN/XTLN-WiFipanelsprovide8wirelesskeyfoboroutputaddressesnumbered31to34and41to44.
A default name is provided as a programming convenience to help reduce installation time. The default
namesaredescribedintheXTLN/XTLN-WiFiProgrammingGuide(LT-1221)andcanbechangedinOutput
Information or Zone Information programming as needed.
+
_
RESET
S1
LOAD
S2
BAT
J1
PROG
RED
PWR
MODEL XTL
TX RF RX
S
N
CR7
CR6
Red LED
Green LED
Figure 5: XTLN/XTLN-WiFi Backlit
Logo LED’s
XTLN/XTLN-WiFi Installation Guide Digital Monitoring Products
7
InstallatIon
Flash LOAD Button
16.1 Description
TheXTLN/XTLN-WiFipanelsoftwarecanbeupdatedviathepanel’sProgramming(PROG)header.Toupdate
the panel with a new software version, complete the following steps at the protected premise:
Model 399 Cable
1.ConnectaDMP399CablefromthePROGHeadertotheserialportofyourPCoperatingRemoteLinkand
containingtheXTLN/XTLN-WiFiRUle.
2.StartRemoteLinkandcreateoropenthecontrolpanelaccountthatmatchesthepaneltobeupdated.
3.SettheConnectionInformationTypetoDirectwithabaudrateof38400andchoosetheappropriate
COMport.
4.SelectPanel>RemoteUpdate,thenselectthecorrectRUleforthepanel.
5.PressandholdtheLOADbutton,thenpressandreleasetheRESETbutton.
6.ReleasetheLOADbuttonandclick<Update>inRemoteLink.
7.Afterthesoftwareupdateiscompleted,removethe399cableandpresstheRESETbuttontoresume
normal panel operation.
Model 400 USB Flash Module
1.PressandholdtheLOADswitch.WhileholdingtheLOADswitch,pressandreleasetheRESETswitch
2.ReleasetheLOADswitch.
3.ConnecttheUSBashdrivetotheModel400andconnecttheassemblytothepanelsPROGheader.The
LEDontheModel400willashanddisplaysteadygreen.
5.PressandreleasetheloadbuttonontheModel400toinitiatethermwareupdate.TheLEDonmodel
400willashslowly.IftheLEDdisplaysfastashesitmeansthermwareupdatewasunsuccessful.
6.Theupdatewilltakeapproximately4.5minutesandwhencompletetheLEDontheModel400will
display steady green.
7.PressandreleasetheRESETswitchthenremovetheUSBashdriveandModel400assembly.For
additionalinformationseeModel400USBFlashModuleInstallationGuide(LT-1402).
Digital Monitoring Products XTLN/XTLN-WiFi Installation Guide
8
COMPLIANCE
Listed Compliance Specications
17.1 Introduction
Theprogrammingandinstallationspecicationscontainedinthissectionmustbecompletedwhen
installingtheXTLN/XTLN-WiFiinaccordancewithanyoftheANSI/ULorSIAburglarystandards.Additional
specicationsmayberequiredbyaparticularstandard.
17.2 Use Marking
CommercialCentralStation,HouseholdBurglarandFireControlUnit.
17.3 NFPA 72
ThisequipmentshouldbeinstalledinaccordancewithChapter11oftheNationalFireAlarmCode,
ANSI/NFPA72-2002,(NationalFireProtectionAssociation,BatterymarchPark,Quincy,MA02269).Printed
information describing proper installation, operation, testing, maintenance, evacuation planning, and repair
serviceistobeprovidedwiththisequipment.Warning:Owner’sinstructionnotice,nottoberemovedby
anyone except occupant.
17.4 Types Of Service
SuitableforCentralStationBurglar.SuitableforHouseholdFireandHouseholdBurglar.Testweekly.
17.5 Bypass Reports
ThebypassreportsmustbeprogrammedasYESforalllistedburglaryapplications.
17.6 Battery Standby
TheXTLN/XTLN-WiFiisshippedwithabatteryfor24hourbatterystandbyoperation.
Household Burglar-Alarm System Units
ANSI/UL 1023
18.1 Bell Cutoff
Thebellcutofftimecannotbelessthan4minutes.
18.2 Entry Delay
Themaximumentrydelayusedmustnotbemorethan45seconds.
18.3 Exit Delay
The maximum exit delay used must not be more than 60 seconds.
18.4 Wireless External Contact
Whenused,theExternalContactof1101,1102,or1106transmittersmustbeprogrammedNormallyClosed.
18.5 Wireless Supervision Time
TheZoneInformationSupervisionTimecannotbesetto0(zero).
18.6 Wireless Audible Annunciation
TheWirelessAudibleoptionmustbeselectedasDAYforresidentialapplications.
18.7 Panel location
Mountpanelinsideprotectedarea.
18.8 Test Frequency
TheTestFrequencyoptionmustbeprogrammedtosendareportatleastonceevery30days.
XTLN/XTLN-WiFi Installation Guide Digital Monitoring Products
9
COMPLIANCE
Central Station Burglar Alarm Units
ANSI/UL 1610
19.1 Supervision
CommercialBurglaryisprovidedwhentheCheck-inandFailTimetimeissetto3minutes.
19.2 Remote Disarm
REMOTEDISARMmustbeprogrammedasNO.
19.3 Central Station
MESSAGETOTRANSMITprogrammingforzonesmustnotbesettoLOCAL(L).
Household Fire Warning System
ANSI/UL 985 NFPA 72 Specications
20.1 Bell Output Denition
The wireless siren of the panel must be programmed to operate steady on burglary alarms and temporal on
realarms.SeetheXTLN/XTLN-WiFiProgrammingGuide(LT-1221).
20.2 Household System
An alarm sounding device must be installed indoors so that it is clearly heard in all sleeping areas.
20.3 Wireless Supervision Time
TheZoneInformationSupervisionTimemustbe3minutesforredevices.SeetheXTLN/XTLN-WiFi
ProgrammingGuide.
20.4 Test Frequency
TheTestFrequencyoptionmustbeprogrammedtosendareportatleastonceevery30days.
20.5 Wired Modules
ModulesthatconnecttothePROGheader,suchasthe738Z,mustnotbeusedsincethebatterystandby
timewillbereducedbelowthe24hourminimum.
Digital Monitoring Products XTLN/XTLN-WiFi Installation Guide
10
COMPLIANCE
False Alarm Reduction Programmable Options ANSI/SIA CP-01-2010
19.1 Shipping Defaults and Recommended Programming
SIA CP-01 FEATURE
PARAGRAPH # AND
DESCRIPTION
DMP PROGRAMMING
GUIDE LT-1221
SECTION #
REQUIREMENT RANGE
SHIPPING
DEFAULT
RECOMMENDED
PROGRAMMING*
4.2.2.1ExitTime 8.6ExitDelay
Required
(Programmable)
45sec.-250sec.
60
Seconds
60 Seconds
4.2.2.2Progress
Annunciation
13.13Prewarn
Address
Allowed
Individualkeypadsmay
bedisabledperzone
All
keypads
enabled
Allkeypads
enabled
4.2.2.3ExitTimeRestart 8.6ExitDelay RequiredOption
For re-entry during exit
time
Enabled Enabled
4.2.2.5AutoStayArmon
UnvacatedPremises
8.15Occupied
Premise - See Install
Guide
RequiredOption
(exceptforremote
arming)
OccupiedPremiseNO/
YESoption
Enabled
EnabledYes
for Residential
Applications
4.2.4.4ExitTimeand
Progress Annunciation/
Disable-forRemoteArm
NotAvailableon
Remote Arming
AllowedOption
Progress Annunciation
Always disabled for
Remote Arming
Not
Available
Remote Arming not
allowed for CP-01
installations.
4.2.3.1EntryDelay(s) 8.5EntryDelay
Required
(Programmable)Only
useEntryDelay1.Do
notuseEntryDelay2.
30sec.–240Sec.**
30
Seconds
Atleast30
Seconds **
4.2.5.1AbortWindow–
forNon-FireZones
3.3TransmitDelay RequiredOption
Disablebyzoneorzone
type
Enabled
NTDYEX
Zone
Enabled
4.2.5.1AbortWindow
Time–forNon-FireZones
3.3TransmitDelay
Required
(Programmable)
20sec.,30sec.,or
40sec.**
30
Seconds
Atleast20
Seconds **
4.2.5.1.2Abort
Annunciation
3.3TransmitDelay RequiredOption
Annunciate that no
alarm was transmitted
Yes Yes
4.2.5.4.1Cancel
Annunciation
AlwaysEnabled-Not
Programmable
RequiredOption
Annunciate that a
Cancel was transmitted
(S49)
Always
Enabled
Yes
4.2.6.1&4.2.6.2Duress
Feature
UserCode+1=
AmbushCodeNot
Available
AllowedOption
No1+derivativeof
another user code/no
duplicates with other
user codes
Code+1
Always
Disabled
NotProgrammable
4.3.1CrossZoning 13.16CrossZone RequiredOption
Yes/NoZone
Programming
No
Enabledusing
two or more
programmedzones
4.3.1ProgrammableCross
Zoning Time
8.7CrossZoneTime Allowed 4sec.-250sec. 0 Seconds
Perwalkpath
in protected
premises
4.3.2SwingerShutdown
NotAvailable—
AlwaysOn
Required 1-6 trips 2trips 2trips
4.3.2SwingerShutdown
Disable
13.12SwingerBypass Allowed
For non-police
responsezones
Yes Enabled(allzones)
4.3.3FireAlarm
Verication
13.5ZoneType RequiredOption FV Type Zone No
Yes as required
(unlesssensorscan
selfverify)
4.6.3SystemTest 16.6WalkTest Allowed
Test all protection
devices
N/A N/A
4.6.5Communications 16.6WalkTest NotAllowed N/A N/A N/A
*Programmingatinstallationmaybesubordinatetootherlistedrequirementsfortheintendedapplication.
**ForlistedInstallations,combinedEntryDelayandTransmitDelayshouldnotexceed1minute.
LocalBell
Allnon-rezonessuchasNight,Day,Exit,Aux1andAux2mustbeprogrammedforlocalbellenabledwithabellcutofftimeset
toaminimumof6minutestoprovideacancelwindowof5minutesorgreater.Thisdoesnotapplytomanuallyoperatedzone
typessuchasPanicandEmergency.
TherequirementsaresupersededbyanyrequirementsforCommercialBurglar,HouseholdFireWarning,orHouseholdBurglar
applications.
MinimumInstallationRequirements:SIACP-01-2010minimumsysteminstallationrequirementsincludeanXTLN/XTLN-WiFi,an
1135WirelessSiren,a9000SeriesWirelesskeypad,andcommunicationtoanSCS-1Rreceiver.
XTLN/XTLN-WiFi Installation Guide Digital Monitoring Products
11
Revisions
Revisions to This Document
Thissectionexplainsthechangesmadetothisdocumentduringthisrevision.Itliststhedateandidenties
thechange(s)made,therelatedsectionnumberandsectionheading,andasummaryofthechange.
Ver. Section Number and Heading Quick Explanation of Changes
1.02 EntireDocument AddedreferencesandinformationforXTLN-WiFi
1.01 EntireDocument InitialRelease
800-641-4282
    
www.dmp.com 2500 North Partnership Boulevard



LT-1220 1.02 © 2014 Digital Monitoring Products, Inc.
15435
Certications
CaliforniaStateFireMarshal(CSFM)
FCCWirelessReceiverApprovals
FCCPart15ID:CCKPC0117
IndustryCanadaID:5251A-PC0117
FCCWiFiNetworkApprovals
FCCID:XM5-SM2144SMT
IndustryCanadaID:8516A-SM2144SMT
ANSI/UL1023 HouseholdBurglar
ANSI/UL985 HouseholdFireWarning
ANSI/UL1610 CentralStationBurglar
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16

Digital Monitoring Products XTLN-WiFi Installation guide

Category
Serial switch boxes
Type
Installation guide
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI