FläktGroup DENCO® C5-12 Controller Owner's manual

Category
Thermostats
Type
Owner's manual
C5-12
OPERATION MANUAL
C5-12 Controls
2FläktGroup DC-2016-0110-GB 2021-05/R2 • Subject to modifications
1 Overview ...................................................................................... 3
1.1 Introduction ................................................................................................ 3
1.2 Model numbers explained .......................................................................... 3
1.3 Product series overview ............................................................................. 4
1.4 Hardware – Controller ................................................................................ 4
1.5 Controller Inputs and Outputs .................................................................... 5
2 Safety and User Information ...................................................... 8
2.1 Availability of the operation manual ........................................................... 8
2.2 Scope of the operation manual .................................................................. 8
2.3 Document format ....................................................................................... 8
2.4 Safety-conscious working .......................................................................... 9
2.5 Modifications and changes ........................................................................ 9
2.6 Personnel selection and qualification ....................................................... 10
2.7 Closing down procedure .......................................................................... 10
3 Home Page and Status Screens .............................................. 11
3.1 Home Page .............................................................................................. 11
3.2 Unit Status Icons ...................................................................................... 12
3.3 Screen saver ............................................................................................ 12
3.4 Unit Status ............................................................................................... 13
3.5 Active Alarms and Alarm History ............................................................. 13
3.6 Alarms and Interlocks .............................................................................. 14
3.7 Sensor Graph Plots .................................................................................. 18
3.8 Status Information Pages ......................................................................... 19
4 Navigation .................................................................................. 21
4.1 Accessing settings ................................................................................... 21
4.2 Menu Navigation ...................................................................................... 21
4.3 Page Identification ................................................................................... 21
4.4 Additional Information .............................................................................. 21
5 User Settings ............................................................................. 22
5.1 Set-points (Level 1.1) ............................................................................... 22
5.2 Software Version (Level 1.2) .................................................................... 22
5.3 Time Control (Level 1.3) .......................................................................... 23
5.4 Language (Level 1.4) ............................................................................... 23
5.5 Time & Date (Level 1.5) ........................................................................... 23
5.6 Humidifier (CPY) control (Level 1.6) ........................................................ 24
5.7 BMS Communication setup (Level 1.7) ................................................... 24
5.8 pLAN Address (Level 1.8) ........................................................................ 25
5.9 Fan Speed (Level 1.9) ............................................................................. 25
PROTECTION NOTICES
The reproduction, distribution and utilization of this document as well as the communication of its contents to others without
express authorization is prohibited. Offenders will be held liable for the payment of damages. All rights reserved in the
event of the grant of a patent, utility model or design.
C5-12 Controls Overview
FläktGroup DC-2016-0110-GB 2021-05/R2 • Subject to modifications 3
1 Overview
1.1 Introduction
We would like to thank you for purchasing our products.
C5-12 Controls are intended and designed for use with DENCO Products® in applica-
tions of Precision Air Conditioning (PAC and DENCO-OfficeCool® products). The con-
trols are designed for refrigeration systems and/or chilled water systems and it is
prohibited to use our controls and software for any other purposes. The equipment has
been designed and manufactured with a 'Quality Assurance System' within a strict
quality controlled environment to ensure that it reaches you in perfect condition.
For help, assistance, spares or your local office, please visit the following website for
contact details in your region:
https://www.flaktgroup.com/en/contact-us/
When contacting please provide details of (if known):
Equipment model number
Serial Number
Date of supply
Any order reference numbers
Software version of equipment
1.2 Model numbers explained
Each product carries an 'Identification Plate' (sometimes referred to as 'serial plate')
inside the equipment for indoor units. For outdoor units, this maybe be on the external
casing. This identification plate carries information that is important and unique to the
unit.
Below shows an example serial plate for a Multi-DENCO A-Version unit.
For quick reference on the display, the "Model Type Code" is also shown in the top right
corner of the home screen. The text field is entered at the factory and does not need
to change.
PRODUCT RANGE / PROJECT TYPE Multi-DENCO® STANDARD
MODEL TYPE CODE / PED DMA030DPSIN4PN1 CAT. 1
SERIAL NUMBER
CONTRACT NO. / DATE OF BUILD 110196 02 / 2017
OPERATION MAN. / WIRING DIAGRAM PR-2013-0101 110196-101
VOLTAGE / PROTECTION RATING
400V-3PH-50HZ/60HZ+N
IP20
MAX. PRE-FUSE 32 TYPE D
FULL LOAD INPUT 11,4 kW
FULL LOAD CURRENT 29,9 A
COOLING MEDIUM
SOFTWARE VERSION
MWP HIGH PRESSURE SIDE 4,32 MPa
MWP LOW PRESSURE SIDE 4,32 MPa
CHILLED WATER 0,70 MPa
EMPTY WEIGHT 330,00 Kg
NOTE
6WC955
CV3.04.009B/DV4.06.009B
R410A (GWP 2088) & WATER
FIELD CHARGE (kg) CO2e
1015
FläktGroup Czech Republic a.s.
Slovanská 781, 463 12 Liberec XXV - Vesec, Czech Republic
ANY MODIFICATION MAY NOT BE REFLECTED ABOVE
=
( Field Charge (R410A) / 1000 ) x 2088 = CO
2
e
CONTAINS
GREENHOUSE
FLUORINATED
GASES
Overview C5-12 Controls
4FläktGroup DC-2016-0110-GB 2021-05/R2 • Subject to modifications
1.3 Product series overview
C5-12 controls are designed to work across several DENCO® products including the
different versions within those product range. Some features and settings are not
applicable to all products, however with correct setting of the unit type within the con-
trols, only the applicable features are enabled.
C5-12 controls are only designed to work in a network with other C5-12 controls prod-
ucts. The controls can provide information and some control features to a Building
Management System (BMS).
For any support regarding C5-12 controls, please contact your local sales department.
1.4 Hardware – Controller
Refer to unit specific wiring diagram for more information on controller connections.
1: Connection to pGDX or pGD1 display
2: Connection to pGDT display and
DencoNet
3 - 9: Digital outputs 1 to 13
10: Inbuilt BMS port (RS485/Modbus or
Energy Monitoring if LECUs are fitted)
11: Inbuilt fieldbus port (CPY humidifier
and expansion modules)
12: Electronic expansion valve number 1
13: Electronic expansion valve number 2
14: RS485 fieldbus interface port (inverter
and energy monitoring or LECUs)
15: Optional serial data interface port (e.g.
pCOWeb / pCONet / LonWorks)
16: Not used
17: Suction pressure and temperature
analogue inputs
18: 24V AV power supply
19: 5V DC supply for discharge pressure
transducers
20: Analogue inputs 1 to 3
21: Analogue inputs 4 to 5
22: Controller address button
23: Controller address display
24: Power and overload LEDs
25: Analogue outputs 1 to 4
26: Digital inputs 1 to 8
27: Analogue inputs 6 to 8
28: Digital inputs 9 to 12
29: Digital inputs 13 to 14
30: EEV Ultracap
C5-12 Controls Overview
FläktGroup DC-2016-0110-GB 2021-05/R2 • Subject to modifications 5
1.5 Controller Inputs and Outputs
INPUTS
Digital
ID1 Unit Remote On/Off 24V AC (Open circuit = unit off)
ID2 Airflow Fail 24V AC (Open circuit = alarm condition)
ID3 Filter Blocked 24V AC
ID4 Heater Over-Temperature Thermostat 24V AC (Open circuit = alarm condition)
ID5 Water Detection 24V AC
ID6 Sump Pump Failure 24V AC
ID7 CombiCool Change-over 24V AC
ID8 Generator Run 24V AC
ID9 Refrigerant Leak Detection 24V AC
ID10 Auxiliary 1 Alarm 24V AC
ID11 Auxiliary 2 Alarm 24V AC
ID12 Oil Level Switch (092 & 130 models only) 24V AC
ID13 Compressor Run Signal (X-Type only) 24V AC
Analogue
U1 Return Air Humidity Sensor type: 4-20mA
U2 Return Air Temperature Sensor type: NTC
U3 Supply Air Temperature Sensor type: NTC
U4 Water Inlet / Ambient Temperature Sensor type: NTC
U5 Water Outlet / Liquid Pipe Temperature Sensor type: NTC
U6 Discharge Pressure / CW Feedback Sensor type: 0-5V / 0-10V
U7 Discharge Temperature Sensor type: NTC
U8 Supply Air Humidity / Airflow Volume Monitoring Sensor type: 4-20mA
NOTES!
(i) The digital inputs will operate within a voltage range of -15% to +10%
(20.4 V to 26.4 V), 50 or 60 Hz.
(ii) All digital inputs are functionally isolated from the rest of the controller.
(iii) For C5-12 Small; ONLY the following inputs are available:
Digital: ID1 ID8
Analogue: U1 U5
Overview C5-12 Controls
6FläktGroup DC-2016-0110-GB 2021-05/R2 • Subject to modifications
OUTPUTS
Digital
NO1 Unit Status Relay Output Normally Open Contact
NO2 Heater 1 / DODC Heat Open / Thyristor Enable Relay Output Normally Open Contact
NO3 Heater 2 / DODC Heat Close Relay Output Normally Open Contact
NO4 Compressor 1 / DODC Cool Open / CombiCool
Secondary CW Open
Relay Output Normally Open Contact
NO5 Compressor 2 / DODC Cool Close / CombiCool
Secondary CW Close
Relay Output Normally Open Contact
NO6 Dehumidification Output Relay Output Normally Open Contact
NO7 Critical Alarm Relay Output Normally Closed Contact
NO8 Maintenance Alarm Relay Output Normally Closed Contact
NO9 CombiCool Primary CW DODC Open Relay Output Normally Open Contact
NO10 CombiCool Primary CW DODC Close Relay Output Normally Open Contact
NO11 FreeCooling Enable Relay Output Normally Open Contact
NO12 Shut-Off Damper Enable Relay Output Normally Open Contact
NO13 Heat Pump Enable Relay Output Normally Open Contact
Analogue
Y1 Evaporating Fan 0 – 10 V DC
Y2 Cooling Demand / FreeCool Demand / CombiCool
Secondary Valve / Heat Pump Demand
0 – 10 V DC
Y3 Condensing Pressure Control / Drycooler Fan 0 – 10 V DC
Y4 CombiCool Primary Valve 0 – 10 V DC
NOTES!
(i) All digital outputs are relay contacts rated at 24 V DC - 240 V AC 10 A
fitted with surge suppressor network.
(ii) All PCB tracks rated to withstand let through energy of a 24 V AC
control fuse (10 A).
(iii) All output relay contacts common to 24V AC.
(iv) DODC refers to Drive Open/Drive Close valve actuator.
(v) The evaporating fan output is to operate alongside the highest demand
of either the cooling, heating or humidification.
(vi) For C5-12 Small; ONLY the following inputs are available:
Digital: NO1 NO8
Analogue: Y1 Y5
C5-12 Controls Overview
FläktGroup DC-2016-0110-GB 2021-05/R2 • Subject to modifications 7
Expansion Modules
The following additional inputs and outputs are available, with an expansion module,
when specific options are selected.
NOTE!
The DIP switches on the expansion modules must be configured as shown below
to ensure correct operation.
pCOe Expansion I/O Module (address 1)
Analogue Input
B1 APS (Under Floor Pressure Control) Sensor type: 4-20 mA
Analogue Output
Y1 Thyristor / Remote Heating Demand 0 – 10 V DC
pCOe Expansion I/O Module (address 2)
Analogue Output
Y1 Remote Humidifier Demand 0 – 10 V DC
c.pCOe Expansion I/O Module (address 7)
Universal Output
U1 Thyristor / Remote Heating Demand 0 – 10 V DC
U2 Dehumidification Demand 0 – 10 V DC
NOTE!
The default software address is configured as 7.
The address is configured in software level 2.6.
Safety and User Information C5-12 Controls
8FläktGroup DC-2016-0110-GB 2021-05/R2 • Subject to modifications
2 Safety and User Information
The C5-12 controller and control strategy has been designed in accordance with state-
of-the-art technological and engineering standards as well as in conformity with the
recognized safety regulations.
It must be used in an appropriate manner for suitable purposes, following the details
contained within this manual and taking account of safety aspects and potential haz-
ards.
Failure to follow the instructions in this manual may result in danger to health and
safety, damage to materials and incorrect unit operation. Information within this
document advises on, but is not limited to, potential threats or concerns related to
health and safety. All users must be, or employ, a trained professional to, assess
issues relating to health and safety, before any use.
2.1 Availability of the operation manual
This manual must always be available at the site where unit is operating. Every person
working on the equipment must read this manual fully before commencing the work
and take note of all relevant information while performing a task.
The manual is intended for end users along with service and commissioning engineers.
2.2 Scope of the operation manual
THIS IS AN ORIGINAL OPERATION MANUAL VERIFIED BY THE MANUFACTURER.
This document has been developed by the manufacturer specifically for details relating
to the C5-12 controller and associated control strategy. Information within this docu-
ment is non-transferable. The information should not be used as a basis for any other
products.
Every effort is made to ensure that information contained within this manual is fair and
accurate, but FläktGroup endeavours to continuously update and improve all of our
products for our customers. Due to this continuous development, some information
contained within this manual may become outdated or no longer relevant. If you are in
any doubt regarding any information contained within this document, please contact
your local sales or support representative who will be happy to assist and enquire fur-
ther for you.
2.3 Document format
Significant information for each chapter will be highlighted in the following format:
This symbol is used to indicate normal lists.
This symbol indicates instructions to follow.
The result of an action is indicated with this symbol.
NOTE!
Here you will find additional details on using the Multi-DENCO unit.
C5-12 Controls Safety and User Information
FläktGroup DC-2016-0110-GB 2021-05/R2 • Subject to modifications 9
2.4 Safety-conscious working
The following is initial general advice to consider during various stages of a project.
More information can be found in the relevant Operation Manual for the product design.
2.4.1 At all times
2.4.2 Whenever opening/removing any panel/grille/door
You must wear suitable Personal Protective Equipment (PPE) at any point working
with a unit from the DENCO Products range. As a minimum we recommend:
Wear safety footwear
Wear eye protection
Wear protective gloves
Wear protective clothing
If operating for a prolonged period of time, noise reducing ear protection may be
required.
Always conduct your own personal risk assessment to evaluate any further
requirements.
2.4.3 When unit is operational
2.5 Modifications and changes
Modification to the C5-12 control or display software, language, programming or
design is not permitted and will invalidate warranty.
Any requests for modifications, after the unit has been installed must be made through
your local or regional office.
Filters (especially used or dirty filters) are easily flammable. Leaking refrigerant can
catch fire and emit noxious substances.
No smoking is allowed in direct proximity of any aspect of the
Multi-DENCO system.
No open flames near the system.
At any time the unit is operational, rotating machinery and electrically charged com-
ponents are present. When the unit is not electrically isolated:
Ensure all guards and doors are closed.
Only remove guards or open doors:
When the unit has been electrically isolated.
Sufficient time has been allowed for the rotating fan momentum to cease.
Sufficient time has been allowed for inverter circuits to discharge.
Safety and User Information C5-12 Controls
10 FläktGroup DC-2016-0110-GB 2021-05/R2 • Subject to modifications
2.6 Personnel selection and qualification
Any individual working on the unit must read and understand all of this manual
before starting any works.
Any individual working on this system shall be suitably qualified and licensed for the
region that the system in installed within.
All personnel involved with the system must understand and observe any local
legislation regarding safe working practice.
2.7 Closing down procedure
It is essential for starting, closing down, emergency operation and fault finding to know
the location of the following components:
Location of isolator for power distribution to the unit
Main Isolator (integral to unit or local position)
ON/OFF icon on the display of the unit
All valves likely to affect water supply to humidifier (if fitted)
Short periods Should you require the equipment to be closed down for the weekend or Bank Holi-
days, no special precautions are required.
Each unit may simply be turned off by pressing the On/Off icon.
Alternatively, the "On/Off Times" can be configured in the controller software.
Long periods If the plant is to be shut down for longer periods (up to a month) this can be done by
switching off at the on/off icon, then opening the Main Isolator, and closing the local
mains water supply to the humidifier. When re-starting the plant, follow the same
instructions but in the reverse order.
Indefinitely When the equipment is to be taken out of service for an indefinite period we recom-
mend a qualified air conditioning engineer. An engineer will also be required for the
restarting of the equipment.
For units fitted with chilled water cooling and/or hot water heating, the mains power
should remain "ON" for at least the stroke time of the valve actuator to ensure that the
valve closes fully.
NOTE!
The units are designed for continuous operation and it is recommended that the sys-
tem is kept running overnight and at weekends to maintain stable room conditions.
C5-12 Controls Home Page and Status Screens
FläktGroup DC-2016-0110-GB 2021-05/R2 • Subject to modifications 11
3 Home Page and Status Screens
3.1 Home Page
The 'Home Page' is the controller's default display. You can return to this page by
pressing the 'Home button' on any screen.
Fig. 3-1
NOTICE
When starting the unit, during the start-up procedure:
Do not touch the screen during start-up
It will take approximately 40 seconds for the home page to display
When the 'Home Page' is shown, you can use the interface
1: Unit ON/OFF – Use this button to turn the
unit ON or OFF, without removing the
power supply (Units Status = OFF by
keyboard).
2: Unit Status – This display what state the
unit is in (see chapter 3.4).
3: Alarm Page – Use this to see any active
alarms and alarm history (see chapter 3.5).
4: Unit Graphs – Use this to see the history
of the sensor values.
5: Login Use this to gain access to settings
menu
6: Logout
7: Logged to Level
8: Status InformationUse this to view the
unit's status (see chapter 3.8).
9: Current Humidity– Depending on the
options fitted, this value could be return or
supply air and could be internal to the unit
or remotely positioned.
10: Model Reference The model short code
of the unit design.
11: Help/additional information - On some
pages, additional information can be
displayed by pressing this button.
12: Time – The time configured in the unit.
13: Network Status This shows whether the
network connection is healthy or
disconnected.
14: Unit Number – This is the same number
as number 18.
15: Unit Function Icons This symbols show
what operations the unit is currently
performing: fans operating, heating,
cooling, humidification control (both
humidification and dehumidification).
16: Date – The date configured in the unit.
17: Active Alarm – This symbol will flash if
there is an active alarm.
18: Unit Number – This is used for
networking.
19: Current Temperature Depending on the
options fitted, this value could be return or
supply air and could be internal to the unit
or remotely positioned.
Home Page and Status Screens C5-12 Controls
12 FläktGroup DC-2016-0110-GB 2021-05/R2 • Subject to modifications
3.2 Unit Status Icons
3.3 Screen saver
The screen saver is activated when the screen has not been pressed for 15 minutes.
Screen saver when unit has no active alarms.
Fig. 3-2
Screen saver when unit has active alarms.
Fig. 3-3
UNIT RUNNING – shown when the unit's fan(s) are running.
COOLING – shown when cooling demand is greater than 0%.
HEATING – shown when heating demand is greater than 0%.
HUMIDIFYING – shown when humidification demand is greater than 0%.
DEHUMIDIFYING – shown when dehumidification demand is greater than 0%.
Network Status (Healthy) – shown when there is a healthy connection between the Controller
and Display.
Network Status (Fault) – shown when there is an un-healthy connection between the Controller
and Display.
C5-12 Controls Home Page and Status Screens
FläktGroup DC-2016-0110-GB 2021-05/R2 • Subject to modifications 13
3.4 Unit Status
The unit status on the Home page (see balloon 2 on Fig. 3-1) can be any of the follow-
ing;
Unit On The unit is operating.
Off by Alarms Disabled due to an alarms that requires a unit to be stopped for protection of equipment
or environment.
Off by BMS Disabled by a BMS signal to stop the unit.
Off by Time Zone Disabled due to the time control settings in Level 1.3.
Off by DI Disabled due to a break in the remote stop/start connection.
Off by Keyboard The unit has been switched off by the on/off icon on the display.
On HOA Mod Any of the units’ outputs has been configured for ‘Hand’ operation.
Stand-by Unit is configured for a DencoNet auto change-over and is currently in stand-by.
On Generator Mode There is a 24 Vac signal on ID8 and the unit is operating in 'cooling only' mode.
3.5 Active Alarms and Alarm History
Where this button is shown, you can press it to see the active alarms page (shown in
Fig. 3-4). If there is no active alarms, this button will be black instead of red.
Fig. 3-4
1: Use these checkboxes to select specific
alarms.
2: Use this to reset any selected alarms.
3: Use this to select all alarms.
4: Use this to see the Alarm History (see
Fig. 3-5).
5: Use this to see the Graph Plots (see
chapter 3.8).
6: Use this to return to the Home Page.
7: Use this scroll through the alarm list.
Home Page and Status Screens C5-12 Controls
14 FläktGroup DC-2016-0110-GB 2021-05/R2 • Subject to modifications
After selecting 'Alarm History', Fig. 3-5 is shown. The software can display 28 days of
alarms. On the 29th day, these alarms will over-write the 1st day's alarms.
Fig. 3-5
3.6 Alarms and Interlocks
1: Alarm event and description - the date is in
the format MM/DD/YYY.
2: Use this drop down menu to change the
view to show more or less history. The
range is from 5 minutes to 4 weeks.
3: After changing the history duration, this
'refresh' button will update the list to show
the correct alarms.
4: Use this to scroll through the alarm list.
5: This allows you to export the alarm history
to a USB memory device (SD card not
available). The USB port is on the under-
side of the touch display. The information is
exported into a Comma Separated Values
(CSV) file.
Alarm Description Relay Activated Reset Function Comments
Airflow Failure Critical Manual Switches unit off.
Filter Blocked Maintenance Manual Relay operation selectable in software.
Heater Over-Tem-
perature Alarm
Critical Manual Electric heater over-temperature thermostat activated
and disables heater outputs.
Water Detection Critical Manual Disable humidifier operation.
Note: there is an option to select the whole unit to be dis-
abled in the event of a water alarm.
Auxiliary Alarms
1 & 2
Maintenance Manual Custom text and relay operation selectable in software.
Sump Pump Failure Critical Manual Disables humidifier operation.
Refrigerant Leak
Detection
Critical Manual Monitoring only.
Return Air
Temperature
Sensor Failure
Critical Auto Disables temperature control outputs.
Return Air Humidity
Sensor Failure
Critical Auto Disables humidity control outputs.
C5-12 Controls Home Page and Status Screens
FläktGroup DC-2016-0110-GB 2021-05/R2 • Subject to modifications 15
Discharge Pressure
Sensor Failure
Critical Auto Disables cooling operation.
Water Inlet
Temperature
Sensor Failure
Critical Auto Activates CombiCool secondary circuit
Water Outlet
Temperature
Sensor Failure
Critical Auto Monitoring only.
Supply Air
Temperature
Sensor Failure
Critical Auto Disables temperature control outputs (if selected as sup-
ply air temperature control).
Supply Air Humidity
Sensor Failure
Critical Auto Disables humidity control outputs (if selected as supply
air humidity control).
Air Volume Pres-
sure Sensor Failure
Critical Auto Unit fans revert to ‘Normal’ operation when selected as
Air Volume Control.
APS Pressure
Sensor Failure
Critical Auto Unit fans revert to ‘Normal’ operation when selected as
APS Control.
Ambient Tempera-
ture Sensor Fail
Critical Auto Disables FreeCooling.
Discharge
Temperature
Sensor Failure
Critical Auto Disables cooling operation.
High Control Air
Temperature Alarm
Critical Auto Monitoring only.
Low Control Air
Temperature Alarm
Critical Auto Monitoring only (only activated if heating function select-
ed).
High Control Air
Humidity Alarm
Critical Auto Monitoring only (only activated if dehumidification func-
tion selected).
Low Control Air
Humidity Alarm
Critical Auto Monitoring only (only activated if humidification function
selected).
Low Supply Air
Temperature Alarm
Critical Auto Monitoring only (only activated if supply air temperature
control and heating function selected).
High Supply Air
Humidity Alarm
Critical Auto Monitoring only (only activated if supply air humidity con-
trol and dehumidification function selected).
CPY Offline Critical Auto No communication between the CPY humidifier module
and the C5-12 controller.
Parameters Not
Downloaded (CPY)
Critical Manual Humidifier configuration incorrect. Disables humidifier
operation.
High Current Alarm
(CPY)
Maintenance Manual Excessive current drawn by humidifier. Disables humidi-
fier operation.
Lack of Water Alarm
(CPY)
Maintenance Manual No water supply to humidifier or the bottle has reached
the end of its operational life. Disables humidifier opera-
tion.
High Conductivity
Alarm (CPY)
Maintenance Manual Excessive conductivity measured by conductivity probes.
Disables humidifier operation.
Alarm Description Relay Activated Reset Function Comments
Home Page and Status Screens C5-12 Controls
16 FläktGroup DC-2016-0110-GB 2021-05/R2 • Subject to modifications
Low Production
Alarm (CPY)
Maintenance Manual Humidifier not achieving target current. Disables humidi-
fier operation.
Humidifier Cylinder
Full Alarm (CPY)
Maintenance Manual Water reaches high level probes in humidifier bottle. Dis-
ables humidifier operation.
pCOe Offline Critical Auto No communication between the C5-12 controller and the
expansion module used for thyristor heating and/or APS.
pCOe 2 Offline Critical Auto No communication between the C5-12 controller and the
expansion module used for remote humidifier.
C,pCOe Offline Critical Auto No communication between the C5-12 controller and the
expansion module used for remote dehumidifier.
BMS Offline None Manual No communication between the C5-12 controller and the
BMS when ‘BMS Comms Alarm’ enabled.
Denconet Commu-
nication Alarm
None Manual No communication with other units on a Denconet net-
work.
Energy Meter
Device Off Line
None Auto No communication to the power meter.
Clock Alarm None Manual Fault on C5-12 controller. No effect to unit functionality.
LECU Offline None Auto No communication between LECU and C5-12 controller.
Circuit LP Threshold
Alarm
Critical Manual LP alarm threshold reached (default 2.5 bar) and dis-
ables cooling operation.
Circuit HP Thresh-
old Alarm
Critical Manual HP alarm threshold reached (default 41 bar) and disables
cooling operation.
Low Pressure
Switch Alarm
Critical Manual LP switch activated and disables cooling.
Note: DMA092 &130 only.
High Discharge Gas
Temperature
Critical Manual Discharge pipe temperature exceeds 120°C and disables
cooling operation.
Low Pressure
Differential Alarm
Critical Manual After five attempts to re-start, the differential between the
suction and discharge pressures is less than 1.3bar and
disables the cooling operation.
Envelope Alarm Critical Manual Compressor operating outside of the envelope limits for
4 hours and disables the cooling operation.
Low Superheat Critical Manual Superheat below alarm threshold (default 2K) for longer
than 60 seconds. Disables cooling operation.
Low Evaporating
Temperature
Critical Manual Evaporating temperature envelope low limit reached.
Disables cooling operation.
High Evaporating
Temperature
Critical Manual Evaporating temperature envelope high limit reached.
Disables cooling operation.
High Condensing
Temperature
Critical Manual Condensing temperature envelope high limit reached.
Disables cooling operation.
Low Suction
Temperature
Critical Manual Evaporating temperature envelope low limit reached.
Disables cooling operation.
Low Discharge
Superheat Alarm
Critical Manual Discharge Superheat below 12K for longer than 10 min-
utes. Disables cooling operation.
Alarm Description Relay Activated Reset Function Comments
C5-12 Controls Home Page and Status Screens
FläktGroup DC-2016-0110-GB 2021-05/R2 • Subject to modifications 17
High Discharge
Superheat Alarm
Critical Manual Discharge Superheat above 50K for longer than 10 min-
utes. Disables cooling operation.
EEV Motor Error Critical Manual Electronic expansion valve not communicating to C5-12.
Disables cooling operation.
Power+ Device Off
Line
Critical Auto No communication with Power+ Inverter, normally occurs
when there is no mains power supply to inverter.
Cooling will not operate.
Inverter Model Not
Compatible
None Manual Incorrect configuration.
Cooling will not operate
Danfoss Inverter Off
Line
Critical Auto No communication with Danfoss inverter (models 092 &
130 only). Cooling will not operate.
Danfoss Inverter
Alarm
Critical Manual Inverter compressor fault (models 092 & 130 only).
Disables cooling operation.
Danfoss Oil
Protection Mode
Alarm
Critical Manual Optical oil sensor detects low oil level following oil recov-
ery cycle (models 092 & 130 only).
Disables cooling operation.
Power+
Drive Disabled
Critical Auto HP safety switch activated.
Disables cooling operation.
Power+
Drive Over Temp
Critical Auto Inverter electronics temperature limit reached.
Disables cooling operation.
Power+
Motor Phase Failure
Critical Auto Power supply to inverter disrupted.
Disables cooling operation.
Power+
Over Voltage
Critical Auto Inverter detects a high voltage supplied to compressor.
Also a symptom of an over condensing condition.
Disables cooling operation.
Power+ Under Volt-
age
Critical Auto Inverter detects a low voltage supplied to the compres-
sor. Disables cooling operation.
Power+
Speed Failure
Critical Auto Inverter unable to manage the correct rotor speed. This
normally occurs during start-up and is caused by the
presence of liquid in the compressor.
Disables cooling operation.
Power+ Over
Current Failure
Critical Manual Excess compressor current measured. Also a symptom
of the system operating with a high discharge tempera-
ture. Disables cooling operation.
Alarm Description Relay Activated Reset Function Comments
NOTE!
There is an option in the software to disable the whole unit in the event of a com-
pressor alarm, i.e. cooling disabled.
Home Page and Status Screens C5-12 Controls
18 FläktGroup DC-2016-0110-GB 2021-05/R2 • Subject to modifications
3.7 Sensor Graph Plots
Fig. 3-6
1: Values on graph - the colour of the text
represents the colour of the line on the
graph. Values that can be shown are:
– Supply Air Temperature °C
– Return Air Temperature °C
– Chilled Water Outlet Temperature °C
– Return Air Relative Humidity %
– Supply Air Relative Humidity %
2: Scroll forward in time
3: Scroll backwards in time
4: Refresh the graph
5: Change the scale of the X-axis (time)
6: Change the scale of the Y-axis (sensor
values)
NOTE!
The graph will only show sensors that are installed and are set to 'Fitted' in the set-
tings (Level 3.3A).
C5-12 Controls Home Page and Status Screens
FläktGroup DC-2016-0110-GB 2021-05/R2 • Subject to modifications 19
3.8 Status Information Pages
Press this icon on the Home page to show a series of pages that show status and sen-
sor values. Use the left and right arrows to navigate to different pages. Once you have
navigated past the last page, it will go back to the first page.
As standard the following pages are shown:
Setpoint & Demand Status
Sensor Status
Sensor Status - Expansion
Only if the equipment is installed and enabled in the settings are these pages shown:
LECU(s) Status
Airflow Status (requires Air Volume Monitoring)
Humidifier Status
Energy Meter
Home Page and Status Screens C5-12 Controls
20 FläktGroup DC-2016-0110-GB 2021-05/R2 • Subject to modifications
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26

FläktGroup DENCO® C5-12 Controller Owner's manual

Category
Thermostats
Type
Owner's manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI