7•dap4UserManual
DISPLAY PANEL
Conditions and Data Displayed
TEMPERATURE: Current return air temperature (°F or °C) UNIT TYPE: Data Aire model type
DISCHARGE AIR: Current Discharge Air Temp (°F or °C)* DATE: Current date (month/day/year)
UNIT ID/ZONE ID: Assigned unit ID and Zone Number* TIME: Current time (hour/minute)
TEMPERATURE SETPOINT: Current temp setpoint (°F or °C) UNIT STATUS: ON or OFF
HUMIDITY SETPOINT: Current humidity setpoint (%) HUMIDITY: Current return air humidity (%)
CHILLED WATER TEMPERATURE: Current Chilled Water Temperature (°F or °C)*
* This optional feature or data display may require additional components and/or sensors
FUNCTIONS DISPLAYED
COOLING: 1st stage, 2nd stage, 3rd stage*, 4th stage* HUMIDIFICATION: Appears when operating
DEHUMIDIFICATION: Appears when operating REHEAT: 1st stage, 2nd stage, 3rd stage
CHILLED WATER FLOW: 10-100% (based on VDC output) ENERGY SAVER: Appears when operating
FAN SPEED: 0-100% (based on VDC output – plug fan units
* This optional feature or data display may require additional components and/or sensors
WARNINGS AND ALARMS DISPLAYED
HIGH TEMPERATURE WARNING LOW TEMPERATURE WARNING
HIGH HUMIDITY WARNING LOW HUMIDITY WARNING
POWER FAILURE RESTART NO AIRFLOW
UNDER FLOOR WATER DETECTION DIRTY FILTER
LOW PRESSURE COMPRESSOR 1 LOW PRESSURE COMPRESSOR 2
MANUAL OVERRIDE FIRESTAT TRIPPED
HUMIDIFIER PROBLEM* MAINTENANCE REQUIRED
TEMPERATURE SENSOR FAILURE HUMIDITY SENSOR FAILURE
COMPRESSOR SHORT CYCLE NO WATER FLOW*
LOCAL ALARM* SMOKE DETECTOR*
CUSTOM MESSAGE* FAN MOTOR OVERLOAD*
DISCHARGE AIR SENSOR ERROR* HIGH CONDENSATE WATER LEVEL*
STANDBY PUMP ON* PERSON TO CONTACT ON ALARM
HIGH PRESSURE/INTERNAL OVERLOAD COMP 1 HIGH PRESSURE/INTERNAL OVERLOAD COMP 2
* This optional feature or data display may require additional components and/or sensors
HISTORICAL DATA DISPLAYED
EQUIPMENTRUNTIMES:Blower,compressor1,compressor2,reheatstrip1,2,and3,dehumidication,Energy
Saver*,humidier,condenserandchilledwater
ALARM HISTORY: Alarm list with time and date of occurrence
LAST 24 HOURS: High and low temperature, high and low humidity
AVERAGEPERCENTOFCAPACITYLASTHOUR:Compressor(s),humidier,reheatstripsandwatervalve