  • Hello! I've reviewed the mounting instructions for retrofitting the SNV valve on FRICK units, replacing the SVA valve . The document specifies the components in the kit and the steps for installation, including cutting the old nozzle , welding a new one, and mounting the new valve. I'm ready to answer any questions you have about this process.
  • What should I do before performing the retrofit?
    What does the retrofit kit, part no. 3084.875, contain?
    How far from the shell should I cut the old nozzle?
Page 1 of 2
Johnson Controls Denmark ApS
Christian X's Vej 201 ∙ 8270 Højbjerg ∙ Denmark
Phone +45 87 36 70 00 ∙ www.sabroe.com
CVR No 19 05 61 71
Mounting instruction
0015061
11 March 2022
Retrofit SNV valve on FRICK units
Note: Before performing the retrofit, you must contact local authorities to make sure that current rules and regula-
tions about execution and non-destructive testing (NDT) are followed.
The retrofit solution fits old FRICK OHU with SVA valve.
The retrofit kit, part no. 3084.875, contains:
1 x 2321.1055 (Threaded nozzle)
1 x 2313.027 (Plug)
1 x 2356.123 (Gasket ring)
1 x 2356.283 (Gasket ring)
1 x 1361.118 (SNV-ST needle valve)
1. Cut away the old nozzle, min. 21 mm from the shell to keep the strength
Page 2 of 2
Johnson Controls Denmark ApS
Christian X's Vej 201 ∙ 8270 Højbjerg ∙ Denmark
Phone +45 87 36 70 00 ∙ www.sabroe.com
CVR No 19 05 61 71
2. Weld on the threaded nozzle (2321.1055)
3. Mount the SNV valve (1361.118) with gasket rings (2356.123 and 2356.283) and plug (2312.027).