Installation guide
INSTALLATION AND COMMISSIONING
Monitoring system
FICO-MINI
FläktGroup FG_DC_10295GB_FICO-MINI_IN-CM_20220118_R2 Specifications are subject to alteration without notice.
2
FICO-MINI - Installation and Commissioning
CONTENTS
Connection instructions for the system FICO-MINI.......................................................................................................................................................................3
General......................................................................................................................................... .......................................................................................................3
Inputs FICO-MINI.......................................................................................................................... ....................................................................................................3
Outputs FICO-MINI....................................................................................................................... ....................................................................................................3
Damper actuators......................................................................................................................... ..................................................................................................3
Smoke detectors........................................................................................................................... ..................................................................................................3
Operating of fans.......................................................................................................................... ...................................................................................................3
Connection of communication between FICO-MINI and the multiboxes FCBB-2/FCBB-4 ..................................................................................3
Connection of communication to the central control and monitoring system .............................. .........................................................................3
External inputs.............................................................................................................................. ....................................................................................................3
Topology FICO-MINI................................................................................................................... ..............................................................................................................4
Combination options for FICO-MINI and FCBB-2/FCBB-4 ........................................................... ....................................................................................4
Central unit FICO-MINI with four dampers and two smoke detectors........................................... ..............................................................................5
Central unit FICO-MINI with one multibox FCBB-4, eight dampers and four smoke detectors ... ......................................................................6
Connections diagrams............................................................................................................... ............................................................................................................7
Control unit FICO-MINI................................................................................................................. ...................................................................................................7
Multibox FCBB-2........................................................................................................................... ..................................................................................................8
Multibox FCBB-4........................................................................................................................... ...................................................................................................9
Installation................................................................................................................................... ...............................................................................................................10
Control unit FICO-MINI................................................................................................................. ...................................................................................................10
Multibox FCBB-2.......................................................................................................................... ...................................................................................................11
Multibox FCBB-4.......................................................................................................................... ....................................................................................................12
Commissioning.......................................................................................................................... ...............................................................................................................13
Control unit FICO-MINI (first commissioning).............................................................................. ..........................................................................................13
Operation.......................................................................................................................... ...........................................................................................................................18
Alarms.............................................................................. ...................................................................................................................................................................18
Reset alarms.............................................................................. .......................................................................................................................................................18
Index .............................................................................................................................................................................................................................................................19
FläktGroup FG_DC_10295GB_FICO-MINI_IN-CM_20220118_R2 Specifications are subject to alteration without notice.
3
FICO-MINI - Installation and Commissioning
CONNECTION INSTRUCTIONS FOR THE SYSTEM FICO-MINI
GENERAL
Installation must be carried out by authorized personnel.
The FICO-MINI monitoring system consists of the control unit FICO-MINI,
the multiboxes FCBB-2 and FCBB-4, these components contain elec-
tronic components that can be damaged if handled incorrectly.
The system FICO-MINI is performed with auto-addressing, when the
system starts, it detects how many damper motors and smoke detec-
tors are connected.
Before the device is powered up, all external installations shall be com-
pleted.
The control unit FICO-MINI, the multiboxes FCBB-2 and FCBB-4 should
be mounted with 4 screws into the holes located under the housing
cover to ensure protection class IP54.
The control unit FICO-MINI is capable to handle 1-4 air dampers and 1-2
smoke detectors with individual indicator. The system can be extend-
ed up to max. 12 damper actuator and 6 smoke detectors by using the
multiboxes FCBB-2 and FCBB-4. The multiboxes are supplied with 230V
AC and communicate with the control unit FICO-MINI via a communi-
cation cable. Up to two multiboxes can be connected to a control unit
FICO-MINI.
INPUTS FICO-MINI
Supply voltage 230V AC, 6 A, terminal L, N and PE.
Example of electric cable type: EQQ3G1.5.
OUTPUTS FICO-MINI
All relay outputs are potential-free contacts, shown in a dead state.
Summation alarm for Fire alarm (marked FIRE) in the FICO-MINI. Max
load 230V AC, 6 A resistive load.
Summation alarm contacts for Service alarm (marked SERVICE) in the
FICO-MINI. Max. load 230V AC, 6A resistive load.
Relay contacts for interlocking of fans (marked FAN A) in the FICO-MINI.
Max load 230V AC, 6 A resistive load.
Example of electric cable type: EQQ3x1.5.
DAMPER ACTUATORS
The damper actuators are connected to the central unit FICO-MINI or/
and the multiboxes FCBB-2/FCBB-4. Up to max.12 actuators with in-
dividual indication can be connected to the system. In the control unit
FICO-MINI and in the multibox FCBB-4, four damper actuators can be
connected. In the multibox FCBB-2 two damper actuators can be con-
nected.
The supply voltage to the damper actuators is connected to FICO-MINI
and the multiboxes FCBB-2/FCBB-4 on terminals G and G0 (marked
DAMPER). Indication for closed damper is connected to terminal S2,
G0 is used as common conductor (marked DAMPER) and indication for
open damper is connected to terminal S6, G0 is used as common con-
ductor (marked DAMPER). See section Installation on pages 10-12.
S3 and S5 are not used and shall be insulated.
SMOKE DETECTORS
The Smoke detectors are connected to the control unit FICO-MINI, the
multiboxes FCBB2 / FCBB-4 and up to 6 smoke detectors with individu-
al indication. In to the FICO-MINI, FCBB-4 and FCBB-2 two smoke detec-
tors can be connected.
With FICO-MINI and FCBB-4 you can choose between two alternative
smoke detectors Calectro UG-3-O (duct) or EVC-PY-DA (room). With
FCBB-2 you can choose between three alternative smoke detectors Ca-
lectro UG-3-O (duct), EVC-PY-DA (room) or SOS2.xx (duct).
The supplied 2.2 kOhm resistor must be connected to the UG-3-O and
EVC-PY-DA.
OPERATING OF FANS
The control unit FICO-MINI has one relay output (one group) for inter-
locking fans marked FAN A. In de-energized state and in case of alarm,
the contact is open (NO).
CONNECTION OF COMMUNICATION BETWEEN FICO-MINI AND
THE MULTIBOXES FCBB-2/FCBB-4
The control unit FICO-MINI has two terminals for connecting communi-
cation wires between control unit FICO-MINI and the multiboxes FCBB-
2/FCBB-4 (marked LINK). Max. two multiboxes can be connected.
The FICO-MINI can be used in conjunction with two FCBB-4, one FCBB-2
and one FCBB-4 or two FCBB-2.
Type of electric cable:
FQAR-PG 2x2x0.5 or equivalent
CONNECTION OF COMMUNICATION TO THE CENTRAL
CONTROL AND MONITORING SYSTEM
In the control unit FICO-MINI there are terminals for connecting commu-
nication wiring (marked BMS) to a higher-level control and monitoring
system (Modbus RTU485).
EXTERNAL INPUTS
In the control unit FICO-MINI there are two inputs for external interlock-
ing.
Input for external fire alarm (EXT):
In case of the external fire alarm is triggered, the dampers are closed
and fan interlocking is activated, possibility to acknowledge the external
fire alarm only after it has been reset.
These terminals are normally factory jumpered.
Input for external interlocking (INT):
Dampers are closed and fan interlocking is activated. Normal status re-
turns when the interlocking is removed.
These terminals are normally factory jumpered.
Input for external test (TST):
An external pushbutton can be connected to perform damper actuator
test.
FläktGroup FG_DC_10295GB_FICO-MINI_IN-CM_20220118_R2 Specifications are subject to alteration without notice.
4
FICO-MINI - Installation and Commissioning
TOPOLOGY FICO-MINI
FICO-MINI FCBB-2 FCBB-2
FICO-MINI FCBB-4 FCBB-4
FICO-MINI FCBB-4 FCBB-2
230V
230V230V
230V
230V
230V
230V
230V
230V
FICO-MINI FCBB-2 FCBB-4
230V230V
230V
COMBINATION OPTIONS FOR FICO-MINI AND FCBB-2/FCBB-4
FläktGroup FG_DC_10295GB_FICO-MINI_IN-CM_20220118_R2 Specifications are subject to alteration without notice.
5
FICO-MINI - Installation and Commissioning
TOPOLOGY FICO-MINI
CENTRAL UNIT FICO-MINI WITH FOUR DAMPERS AND TWO SMOKE DETECTORS
FICO-MINI
Power supply 230 V Output fire alarm
Output service alarm
Interlockning of FAN A
Communication to higher-level system
Interlocking
FAN A
Interlocking
ST ST
STST
RD
RD
FläktGroup FG_DC_10295GB_FICO-MINI_IN-CM_20220118_R2 Specifications are subject to alteration without notice.
6
FICO-MINI - Installation and Commissioning
TOPOLOGY FICO-MINI
CENTRAL UNIT FICO-MINI WITH ONE MULTIBOX FCBB-4, EIGHT DAMPERS AND FOUR SMOKE DETECTORS
FICO-MINI
Power supply 230 V Output fire alarm
Output service alarm
Communication to higher-level system
Interlocking of FAN A
Interlocking
FAN A
Interlocking
FCBB-4
Supply 230 V
ST
ST
ST
STST
ST
ST
ST
RD
RD
RD
RD
FläktGroup FG_DC_10295GB_FICO-MINI_IN-CM_20220118_R2 Specifications are subject to alteration without notice.
7
FICO-MINI - Installation and Commissioning
CONNECTIONS DIAGRAMS
CONTROL UNIT FICO-MINI
1, 2, 3 Supply connection 230V AC
4, 5 Connection of fan interlocking FAN A, NO.
6, 7 Connection of output summation alarm for FIRE, NC.
8, 9 Connection of output summation alarm for SERVICE, NC.
10, 11 Input for external fire alarm. The alarm must be acknowledged at the control unit.
12, 13 Input for external interlocking. Needs no acknowledging at the control unit.
14, 15 External test (activates with a pulse), NO
16, 17,
18, 19
Connection of damper actuator 1. AC 24V, limit position for closed and open damper.
G0 (terminal 17) is used as common terminal for limit switches S2 and S4.
20, 21,
22, 23
Connection of damper actuator 2, AC 24V, limit position for closed or open damper.
G0 (terminal 21) is used as common terminal for limit switches S2 and S4.
24, 25,
26, 27
Connection of damper actuator 3, AC 24V, limit position for closed or open damper.
G0 (terminal 25) is used as common terminal for limit switches S2 and S4.
28, 29,
30, 31
Connection of damper actuator 4, AC 24V, limit position for closed or open damper.
G0 (terminal 29) is used as common terminal for limit switches S2 and S4.
32, 33 Connection of smoke detector 1, UG-3-O or EVC-PY-DA.
34, 35 Connection of smoke detector 2, UG-3-O or EVC-PY-DA.
36, 37,
38
Connection of communication to a higher-level BMS-system
Modbus RTU
39, 40,
41
Connection of the multiboxes FCBB-2 and FCBB-4.
101
L
230VAC
2
N
3
PE
11
T
T
12 13
T
14
X3
15
T
TT
16 17
T
G0 S2 GS6 G0
22 23
TT
28
G
29
G0 S2 G1S6 M1
34
G2
35
T
T
18 19 20 21 24 25 26 27 30 31 32 33 36 37 38 39
X1 X2 G S6 G S2G0 S6S2
T
T
M2 D0 D1
FICO-MINI
EXT INT TST DAMPER 1 DAMPER 2 DETECTOR BMS Link
MODBUS RTU
DAMPER 3
T
DAMPER 4
40 41
D0 D1
4 5 67 8 9
REL 1 REL 2 REL 3
FAN A ALARM SERVICE
FläktGroup FG_DC_10295GB_FICO-MINI_IN-CM_20220118_R2 Specifications are subject to alteration without notice.
8
FICO-MINI - Installation and Commissioning
CONNECTIONS DIAGRAMS
MULTIBOX FCBB-2
101
L
230VAC
2
N
3
PE
11
T
T
12 13
T
14
X3
15
T
TT
16 17
T
G0 S1
T
S4S2 S6
22 23
TT
28
G1
29
M1 B1 M2G2 B2
34
D0
35
T
T
18 19 20 21 24 25 26 27 30 31 32 33 36 37 38 39
X1 X2
T
G G0 S1 S4S2 S6G
TT
T
D1 D0 D1
FCBB-2
EXT INT TST DAMPER 1 DAMPER 2 DETECTOR IN OUT
MODBUS RTU
TEST RESET
ALARM
STATUS
OPEN
CLOSE
FIRE
SERVICE
SERVICE
LINK
OPEN
CLOSE
FIRE
SERVICE
1, 2, 3 Supply connection 230V AC.
10, 11 Input for external fire alarm (only available with FICO-PRO). The alarm must be acknowledged
at the control unit.
12, 13 Input for external interlocking (only available with FICO-PRO). Needs no acknowledging at the
control unit.
14, 15 External test (only available with FICO-PRO).
16, 17
18, 19
20, 21
Connection of damper actuator 1, AC 24 V, limit position for closed and open damper.
Optionally, if the connection is made with 7-wire or 4-wire. If four-wire coupling is used,
G0 (terminal 17) is used as common terminal for the limit switches S1 and S4.
22, 23
24, 25
26, 27
Connection of damper actuator 2, AC 24 V, limit position for closed and open damper.
Optionally, if the connection is made with 7-wire or 4-wire. If four-wire coupling is used,
G0 (terminal 23) is used as common terminal for the limit switches S1 and S4.
28, 29,
30
Connection of smoke detector of manufacturer Calectro (UG-3-O or EVC-PY-DA) or Siemens
(Rököga SOS2.xx).
31, 32,
33
Connection of smoke detector of manufacturer Calectro (UG-3-O or EVC-PY-DA) or Siemens
(Rököga SOS2.xx).
34, 35,
36
Connection of communication between the control unit FICO-MINI, multiboxes FCBB-2 and
FCBB-4.
37, 38,
39
Connection of communication between the control unit FICO-MINI, multiboxes FCBB-2 and
FCBB-4.
ALARM
STATUS
OPEN
CLOSE
FIRE
SERVICE
SERVICE
LINK
OPEN
CLOSE
FIRE
SERVICE
STATUS Power SERVICE
ALARM LINK Communication
OPEN Damper 1, Open OPEN Damper 2, Open
CLOSE Damper 1, Closed CLOSE Damper 2, Closed
FIRE Detector 1, Alarm FIRE Detector 2, Alarm
SERVICE Detector 1, Service alarm SERVICE Detector 2, Service alarm
Indication on the circuit board for FCBB-2
FläktGroup FG_DC_10295GB_FICO-MINI_IN-CM_20220118_R2 Specifications are subject to alteration without notice.
9
FICO-MINI - Installation and Commissioning
CONNECTIONS DIAGRAMS
MULTIBOX FCBB-4
10
1
L
230VAC
2
N
3
PE
11
T
T
12 13
T
14
X3
15
T
TT
16 17
T
G0 S2 GS6 G0
22 23
T
T
28
G
29
G0 S2 G1S6 M1
34
G2
35
T
T
18 19 20 21 24 25 26 27 30 31 32 33 36 37 38 39
X1 X2 G S6 G S2G0 S6S2
T
T
M2 D0 D1
FCBB-4
EXT INT TST DAMPER 1 DAMPER 2 DETECTOR IN OUT
MODBUS RTU
DAMPER 3
T
DAMPER 4
40 41
D0 D1
TEST RESET
ALARM
STATUS
OPEN
CLOSE
FIRE
SERVICE
SERVICE
LINK
OPEN
CLOSE
FIRE
SERVICE
OPEN
CLOSE
OPEN
CLOSE
1, 2, 3 Supply connection 230V AC
10, 11, Input for external fire alarm (only available with FICO-PRO). The alarm must be acknowledged
at the control unit.
12, 13 Input for external interlocking (only available with FICO-PRO). Needs no acknowledging at the
control unit.
14, 15 External test (only available with FICO-PRO).
16, 17,
18, 19
Connection of damper actuator 1, AC 24 V, limit position for closed(S2) and open dam per(S6).
G0 (terminal 17) is used as common terminal for the limit switches S1 and S4.
20, 21,
22, 23
Connection of damper actuator 2, AC 24 V, limit position for closed(S2) and open dam per(S6).
G0 (terminal 17) is used as common terminal for the limit switches S1 and S4.
24, 25,
26, 27
Connection of damper actuator 3, AC 24 V, limit position for closed(S2) and open dam per(S6).
G0 (terminal 17) is used as common terminal for the limit switches S1 and S4.
28, 29,
30, 31
Connection of damper actuator 4, AC 24 V, limit position for closed(S2) and open dam per(S6).
G0 (terminal 17) is used as common terminal for the limit switches S1 and S4.
32, 33 Connection of smoke detector 1, UG-3-O or EVC-PY-DA.
34, 35 Connection of smoke detector 2, UG-3-O or EVC-PY-DA.
36, 37,
38
Connection of communication between control unit FICO-MINI, multiboxes FCBB-2 and FCBB-4.
39, 40,
41
Connection of communication between control unit FICO-MINI, multiboxes FCBB-2 and FCBB-4.
ALARM
STATUS
OPEN
CLOSE
OPEN
CLOSE
SERVICE
LINK
OPEN
CLOSE
OPEN
CLOSE
FIRE
SERVICE
FIRE
SERVICE
STATUS Power SERVICE
ALARM LINK Communication
OPEN Damper 1, Open OPEN Damper 2, Open
CLOSE Damper 1, Closed CLOSE Damper 2, Closed
OPEN Damper 3, Open OPEN Damper 4, Open
CLOSE Damper 3 Closed CLOSE Damper 4, Closed
FIRE Detector 1, Alarm FIRE Detector 2, Alarm
SERVICE Detector 1, Service alarm SERVICE Detector 2, Service alarm
Indication on the circuit board for FCBB-4
FläktGroup FG_DC_10295GB_FICO-MINI_IN-CM_20220118_R2 Specifications are subject to alteration without notice.
10
FICO-MINI - Installation and Commissioning
INSTALLATION
CONTROL UNIT FICO-MINI
DAMPER 1
1
FICO-MINI
2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41
230VAC FAN A ALARM SERVICE EXT EXT TST DAMPER 2 DAMPER 3 DAMPER 4 DETECTOR BMS LINK
L N PE
REL 1 REL 2 REL 3 X1 X2 X3 G G0 S2 S6 G G0 S2 S6 G G0 S2 S6 G G0 S2 S6 G1 M1 G2 M2 D0 D1 D0 D1
12 S1 S2 S4 S6
1 2 S1 S2 S4 S6
1 2 S1 S2 S4 S6
12 S1 S2 S4 S6
Supply
voltage
230VAC
FAN
control
Fire
alarm
Service
alarm
External
re alarm
*
External
interlock
*
External
test
Fire damper
Fire damper
Fire damper
Fire damper
21 5
2.2KOhm
2 1 5
2.2KOhm
MODBUS RTU
Ventilation duct detector
UG-3-O
* Connection short circuit by cable jumper at delivery.
Need to be removed for function to be used.
32 33 34 35
DETECTOR
G1 M1 G2 M2
6 3 1
2.2KOhm
16 3
2.2KOhm
Room detector
EVC-PY-DA
FläktGroup FG_DC_10295GB_FICO-MINI_IN-CM_20220118_R2 Specifications are subject to alteration without notice.
11
FICO-MINI - Installation and Commissioning
INSTALLATION
MULTIBOX FCBB-2
DAMPER 1
1
FCBB-2
2 3 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39
230VAC EXT EXT TST DAMPER 2 DETECTOR LINK - IN LINK - OUT
L N PE
X1 X2 X3 S4 S6 D0 D1 D0 D1
12 S1 S2 S4 S6
Supply
voltage
230VAC
External
re alarm
*
External
interlock
*
External
test
Fire damper
21 5
2.2KOhm
MODBUS RTU
Ventilation duct detector
UG-3-O
* Connection short circuit by cable jumper at delivery.
Need to be removed for function to be used.
(Only necessary with FICO-PRO.)
Room detector
EVC-PY-DA
S2S1
G G0
S4 S6
S2S1
G G0 G1 M1 G2 M2
B1 B2
2 1 5
2.2KOhm
1 2 S1 S2 S4 S6
Fire damper
28 29 30 31 32 33
DETECTOR
G1 M1 G2 M2
B1 B2
G M B G M B
28 29 30 31 32 33
DETECTOR
G1 M1 G2 M2
B1 B2
6 3 1
2.2KOhm
6 3 1
2.2KOhm
Ventilation duct detector
SOS2.30 / SOS2.60
FläktGroup FG_DC_10295GB_FICO-MINI_IN-CM_20220118_R2 Specifications are subject to alteration without notice.
12
FICO-MINI - Installation and Commissioning
INSTALLATION
MULTIBOX FCBB-4
DAMPER 1
1
FCBB-4
2 3 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41
230VAC EXT EXT TST DAMPER 2 DAMPER 3 DAMPER 4 DETECTOR LINK - IN LINK - OUT
L N PE
X1 X2 X3 G G0 S2 S6 G G0 S2 S6 G G0 S2 S6 G G0 S2 S6 G1 M1 G2 M2 D0 D1 D0 D1
12 S1 S2 S4 S6
1 2 S1 S2 S4 S6
12 S1 S2 S4 S6
12 S1 S2 S4 S6
Supply
voltage
230VAC
External
re alarm
*
External
interlock
*
External
test
Fire damper
Fire damper
Fire damper
Fire damper
21 5
2.2KOhm
2 1 5
2.2KOhm
MODBUS RTU
Ventilation duct detector
UG-3-O
* Connection short circuit by cable jumper at delivery.
Need to be removed for function to be used.
(Only necessary with FICO-PRO.)
32 33 34 35
DETECTOR
G1 M1 G2 M2
6 3 1
2.2KOhm
16 3
2.2KOhm
Room detector
EVC-PY-DA
FläktGroup FG_DC_10295GB_FICO-MINI_IN-CM_20220118_R2 Specifications are subject to alteration without notice.
13
FICO-MINI - Installation and Commissioning
COMMISSIONING
CONTROL UNIT FICO-MINI (FIRST COMMISSIONING)
Symbols shown in FICO-MINI:
Use the ENTER key to activate the row (value) that you want to
change.
Use the esc key to go back one step.
esc
Use the arrow keys to move up and down in menus and to
change the values.
The communication between the control unit FICO-MINI and
multiboxes FCBB-2 or FCBB-4 is working.
Indicates which unit of those shown on the display has functioning
communication.
The communication between the control unit FICO-MINI and
multiboxes FCBB-2 or FCBB-4 is NOT working (interrupted).
No damper is connected to the FICO-MINI, FCBB-2 or FCBB-4.
A damper is connected to the FICO-MINI, FCBB-2 or FCBB-4 and it
indicates CLOSED position.
A damper is connected to the FICO-MINI, FCBB-2 or FCBB-4 and it
is moving.
A damper is connected to the FICO-MINI, FCBB-2 or FCBB-4 and it
indicates OPEN position.
There is NO smoke detector connected to FICO-MINI, FCBB-2 or
FCBB-4.
There is a smoke detector connected to FICO-MINI, FCBB-2 or
FCBB-4.
If the smoke detector is triggered, these symbols are displayed
alternately on the control unit FICO-MINI.
Normal view menu.
Press the ENTER key once.
The picture shows that there is a control unit FICO-MINI, a
multibox FCBB-4 and a multibox FCBB2 in the plant.
FläktGroup FG_DC_10295GB_FICO-MINI_IN-CM_20220118_R2 Specifications are subject to alteration without notice.
14
FICO-MINI - Installation and Commissioning
COMMISSIONING
CONTROL UNIT FICO-MINI (FIRST COMMISSIONING)
Here you can see the status of the control unit FICO-MINI.
A damper is connected to the control unit.
No smoke detectors are connected.
Here you can see the status of the multibox FCBB-4.
A damper is connected and it indicates open position. A smoke
detector is connected and it is not in alarm mode.
Commissioning
1Before starting with the control unit FICO-MINI settings, all
installations of peripheral components shall be completed. See
Chapter 4.
2FICO-MINI has automatic reading of connected damper actuators
and smoke detectors.
3Switch on the control unit FICO-MINI.
4Press the ARROW UP and ARROW DOWN keys simultaneously to
access the QUICK INSTALL startup menu.
5Available languages: English, Swedish,Suomi,Dansk,German.
6First press ENTER to select the language.
7Use the ARROW UP key to switch to desired language. Then press
ENTER.
8Press the ARROW DOWN key and then press ENTER to set the
year using the ARROW keys. Change to the correct year and then
press ENTER.
9Press the ARROW DOWN key and then press ENTER.
10 Press the ARROW UP / ARROW DOWN keys to set the correct
month and then press ENTER.
11 Press the ARROW DOWN key and thereafter press ENTER to set
the day.
12 Press the ARROW UP / ARROW DOWN keys to set the correct day
and then press ENTER.
FläktGroup FG_DC_10295GB_FICO-MINI_IN-CM_20220118_R2 Specifications are subject to alteration without notice.
15
FICO-MINI - Installation and Commissioning
COMMISSIONING
CONTROL UNIT FICO-MINI (FIRST COMMISSIONING)
13 Press the ARROW DOWN key to set the hour.
14 Press ENTER and then press the ARROW UP / ARROW DOWN keys
to set the correct hour and then press ENTER.
15 Press the ARROW DOWN to set the minutes.
16 Press ENTER and then press the ARROW UP / ARROW DOWN keys
to set the correct minutes and then press ENTER.
17 Press the ARROW DOWN key to set the damper test interval. 1-180
days.
18 Press ENTER and then press the ARROW UP / ARROW DOWN keys
to select the desired damper test interval. Then press ENTER.
19 Press the ARROW DOWN key to select the first day for the damper
test.
It is only possible to choose test day if the test interval is 7, 14, 21,
28 days, etc. This means whole weeks.
20 Press ENTER and then press the ARROW UP / ARROW DOWN
keys to select the first day for your damper test cycle. Then press
ENTER.
21 Press the ARROW DOWN key to set the time that the damper test
will take place in hours.
22 Press ENTER and then press the ARROW UP / ARROW DOWN keys
to set the hour for the damper test. Then press ENTER.
23 Press the ARROW DOWN key to set the minutes.
24 Press ENTER and then press the ARROW UP / ARROW DOWN keys
to select the minutes. Then press ENTER.
FläktGroup FG_DC_10295GB_FICO-MINI_IN-CM_20220118_R2 Specifications are subject to alteration without notice.
16
FICO-MINI - Installation and Commissioning
COMMISSIONING
CONTROL UNIT FICO-MINI (FIRST COMMISSIONING)
25 Press the ARROW DOWN key and then ENTER.
26 Press the ARROW UP key.
27 Exit the Quick Start by pressing ENTER.
The plant starts and is now running.
28 Now the Quick Start is complete.
Press ESC twice to access the main menu.
29 In the main menu you will see the clock and how long time is left
to the next damper test.
In this case, it is five days, 20 hours and 23 minutes.
30 Press ENTER.
Here you can see the control unit FICO-MINI and how many
multiboxes FCBB-2/4 that are connected to the system.
31 Press ENTER to check each unit separately.
32 Press ESC and then ENTER to access the control unit FICO-MINI.
33 Press ESC, ARROW DOWN and then ENTER to access the device
2 (FCBB-4).
34 Press ESC, ARROW DOWN and then ENTER to access the device
3 (FCBB-2).
FläktGroup FG_DC_10295GB_FICO-MINI_IN-CM_20220118_R2 Specifications are subject to alteration without notice.
17
FICO-MINI - Installation and Commissioning
COMMISSIONING
CONTROL UNIT FICO-MINI (FIRST COMMISSIONING)
Display
Damper Smoke detector
LED Status Service Alarm Open Close Fire Service
De-energized --- --- --- --- --- --- ---
Normal ventilation
Damper open
Steady
green
--- --- Steady
green
--- --- ---
Normal ventilation
Damper closed
--- --- --- --- Steady
yellow
--- ---
Alarm/close
Damper
Steady
green
--- Flashes
red
--- --- --- ---
Service alarm
Smoke detector
--- --- --- --- --- --- Flashes
yellow
Damper error
Open damper
--- --- Flashes
red
Flashes
green
--- --- ---
Damper error
Closed damper
--- --- Flashes
red
XFlashes
green
--- ---
External fire alarm No display
External interlocking No display
FläktGroup FG_DC_10295GB_FICO-MINI_IN-CM_20220118_R2 Specifications are subject to alteration without notice.
18
FICO-MINI - Installation and Commissioning
OPERATION
ALARMS
The FICO mini include an event system. Every unexpected event like fire
alarm, damper failure or extrernal alarm add an event to the built in log.
1Press the ARROW DOWN and select the alarm icon
2Press ENTER to open alarms menu.
3Press ENTER again to reset the alarm. The system will ask if you
want to reset the alarm or not. Press ENTER to continue.
Alarm types Acknownledge required
Fire alarm Fire alarm from smoke detector or generated from
damper actuator
YES
Service alarm On ore more of the smoke detectors are in service
state.
NO
Damper failure A damper has got stuck during either open or closed
operation
YES
External alarm System is closed due to an external alarm. Need to
be acknowledged from the FICO-MINI display
YES
Interlock System is closedby and external request, system will
return to operatoin mode as soon a input signal are
closed
NO
RESET ALARMS
An alarm can be acknowledged and rested from the alarm view.
The alarm view is accessable from the main screen my pressening
FläktGroup FG_DC_10295GB_FICO-MINI_IN-CM_20220118_R2 Specifications are subject to alteration without notice.
19
FICO-MINI - Installation and Commissioning
INDEX
A
Alarms .....................................................................................................................18
C
Commissioning, Control unit FICO-MINI ......................................................14
Connection diagram, Multibox FCBB-2 ........................................................7
Connection diagram, Multibox FCBB-4 ........................................................8
Connections diagram, Control unit FICO-MINI ...........................................9
D
Damper actuators ...............................................................................................3
DIP switch ..............................................................................................................10
Display .....................................................................................................................17
E
External inputs ......................................................................................................3
F
FAN A .......................................................................................................................3
FAN B .......................................................................................................................3
I
Input for external fire alarm .............................................................................3
Input for external interlocking .........................................................................3
Inputs FICO-MINI ..................................................................................................3
Installation, Control unit FICO-MINI ................................................................10
Installation, Multibox FCBB-2 ..........................................................................11
Installation, Multibox FCBB-4 ...........................................................................12
Interlocking fans ..................................................................................................3
O
Outputs FICO-MINI ...............................................................................................3
P
Protection class ...................................................................................................3
S
Select language....................................................................................................14
Setting the damper test interval .....................................................................16
Setting the day......................................................................................................14
Setting the hour ....................................................................................................15
Setting the minutes .............................................................................................15
Setting the month ................................................................................................14
Setting the year ....................................................................................................14
Smoke detectors .................................................................................................3
Summation alarm contacts for Service alarm ..........................................3
Summation alarm for Fire alarm ...................................................................3
Symbols ..................................................................................................................13
T
Topology FCBB2/4 ..............................................................................................4
Topology FICO-MINI .............................................................................................4
WWW.FLAKTGROUP.COM FICO-MINI 10295
» Learn more on www.flaktgroup.com
or contact one of our offices
FG_DC_10295GB_FICO-MINI_IN-CM_20190404_R1 © Copyright 2019 FläktGroup
FläktGroup is the European market leader for smart and energy efficient Indoor Air
and Critical Air solutions to support every application area. We offer our customers
innovative technologies, high quality and outstanding performance supported by more
than a century of accumulated industry experience. The widest product range in
the market, and strong market presence in 65 countries worldwide, guarantee
that we are always by your side, ready to deliver Excellence in Solutions.
PRODUCT FUNCTIONS BY FLÄKTGROUP
Air Treatment | Air Movement | Air Diffusion | Air Distribution | Air Filtration
Air Management & ATD’s | Air Conditioning & Heating | Controls | Service
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20

FläktGroup FICO-MINI (FCMB-4) Installation guide

Type
Installation guide

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI