HK Instruments DPI series Installation guide

Type
Installation guide

This manual is also suitable for

HK Instruments DPI series is a versatile electronic differential pressure switch with built-in transmitter functionalities. It offers accurate and reliable pressure measurement with a wide range of applications in HVAC/R systems, including fan, blower, and filter monitoring, staircase pressure monitoring, pressure monitoring in cleanrooms, and boiler pressure monitoring. Its key features include adjustable switching points, relay activation on increasing or decreasing pressure, and autozero calibration for enhanced stability.

HK Instruments DPI series is a versatile electronic differential pressure switch with built-in transmitter functionalities. It offers accurate and reliable pressure measurement with a wide range of applications in HVAC/R systems, including fan, blower, and filter monitoring, staircase pressure monitoring, pressure monitoring in cleanrooms, and boiler pressure monitoring. Its key features include adjustable switching points, relay activation on increasing or decreasing pressure, and autozero calibration for enhanced stability.

Copyright HK Instruments 2022 www.hkinstruments. Installaon version 8.0 2022
INSTALLATION
INSTRUCTIONS
DIFFERENTIAL PRESSURE SWITCHES
DPI Series
READ THESE INSTRUCTIONS CAREFULLY BEFORE ATTEMPTING
TO INSTALL, OPERATE OR SERVICE THIS DEVICE.
• Failuretoobservesafetyinformaonandcomplywithinstrucons
canresultinPERSONALINJURY,DEATHAND/ORPROPERTY
DAMAGE.
• Toavoidelectricalshockordamagetoequipment,disconnect
powerbeforeinstallingorservicinganduseonlywiringwith
insulaonratedforfulldeviceoperangvoltage.
• Toavoidpotenalreand/orexplosiondonotuseinpotenally
ammableorexplosiveatmospheres.
• Retaintheseinstruconsforfuturereference.
• Thisproduct,wheninstalled,willbepartofanengineeredsystem
whosespecicaonsandperformancecharacteriscsarenot
designedorcontrolledbyHKInstruments.Reviewapplicaons
andnaonalandlocalcodestoassurethattheinstallaonwill
befunconalandsafe.Useonlyexperiencedandknowledgeable
technicianstoinstallthisdevice.
• Fuseatloadsupply(normally6A,10A,16A)doesnotalwayslimit
therelayoutputloadcurrentto6A.RelayMaximumLoad(250Vx
6Ares.)
• Addanexternalfusetorelaycommonconnector.Useame-lag
fuse(max6A)thatisinaccordancewiththestandardIEC60127-2.
Theproductdoesn’thaveaninternalfusefortherelay.
 CAUTION:Theproductmayonlybeconnectedtoovervoltage
categoryIIelectricitynetworkaccordingtoIEC60664-1.
SPECIFICATIONS
ThankyouforchoosinganHKInstrumentsDPIserieselectronicdif-
ferenalpressureswitch.TheDPIseriesisintendedforuseincom-
mercialenvironments.Itcombinestheadvantagesofanelectronic
dierenal pressure switch (on-o relay) and a mul-funconal
dierenal pressure transmier to meet your applicaon require-
ments.
The DPI series is comprised of the DPI±500 with bi-direconal
measurementrangesfrom±100to±500PaandtheDPI2500with
measurementrangesfrom100to2500Pa.
AllDPIseriesdevicesincludeonerelay,display,manualpushbuon
zeropointcalibraonandspanpointcalibraon.Oponalfeatures
includeasecondrelayandautozerocalibraon.
DPIseriesdevicesarecommonlyusedinHVAC/Rsystemsfor:
•fan,blowerandltermonitoring
•staircasepressuremonitoringandalarm
•pressuremonitoringincleanrooms
•boilerpressuremonitoringandalarm
SPECIFICATIONS
Performance
Accuracy:
±1.5%(±0.7%*)
%FSfromhighestpressurerange(including:
generalaccuracy,temperaturedri,linearity,hysteresis,
andrepeonerror)
*Canbeachievedwithspanpointcalibraon
Long term stability:
Typical1year
Withautozero:±1Pa
Withoutautozero:±8Pa
Thermal eects:
Temperaturecompensatedacrossthefullspectrumof
capability
Overpressure:
Proofpressure:25kPa
Burstpressure:30kPa
Zero point calibraon:
Automacwithautozero(-AZ)circuitor
Manual via menu
Response me:
0.5–10s,selectableviamenu
Technical Specicaons
Media compability:
Dryairornon-aggressivegases
Measuring units:
Pa,kPa,mmWC,inWC,mbarselectableviamenu
Measuring element:
Piezoresisve
Environment:
OperangTemperature:
 Withoutautozero:-10...50°C
 Withautozero:-5...50°C
Storagetemperature:-20...70°C
Humidity:0to95%rH,noncondensing
Physical
Dimensions:
Case:89x86.5x37.1mm
Weight:
150g
Mounng:
Case:2each4.3mmholes
Lid:2each4.3mmholes
Materials:
Case: ABS
Lid:PC
Ductconnectors:ABS
Tubing:PVC
Protecon standard:
IP54
Touchsensivebuonsonthelid:
Menu,Back,OK,downarrow,uparrow
Display:
31/2digitLCDbacklitdisplay
Size:46.0Wx14.5Hmm
Electrical connecons:
n/out:
 Terminalblock(24V,GND,0–10V)
 Wire:0.2–1.5mm2(16–24AWG)
Relay1:
 Terminalblock(NC,COM,NO)
 Wire:0.2–1.5mm2(16–24AWG)
Relay2:
 Terminalblock(NC,COM,NO)
 Wire:0.2–1.5mm2(16–24AWG)
Cable entries:
Strainrelief:M16&M20
Knockout:16mm
Knockout:20mm
Pressure ngs:
5.2mmbarbedbrass
 +Highpressure
 −Lowpressure
Electrical
Circuit:3-wire(24V,GND,010V)
Input:
 Withoutautozero:21–35VDC/24VAC,±10%
 Withautozero:24VACorVDC,±10%
Output:
 Analog:0–10V
 Relay1:250VAC/30VDC/6A
 Relay2:250VAC/30VDC/6A
 Adjustableswitchingpointandhysteresis
Zero/Spanoutputcalibratedwithin±0.025V
Resistanceminimum:1kΩ
Currentconsumpon:
 35mA+relays(7mAeach)+AZcircuit(20mA)
 +0–10Voutput(10mA)
Conformance
Meetsrequirementsfor:
CE:  UKCA:
EMC:  2014/30/EU S.I.2016/1091
RoHS:  2011/65/EU S.I.2012/3032
LVD/EESR: 2014/35/EU S.I.2016/1101
WEEE:  2012/19/EU S.I.2013/3113
INTRODUCTION
APPLICATIONS
WARNING
RoHS
COMPLIANT
Copyright HK Instruments 2022 www.hkinstruments. Installaon version 8.0 2022
SCHEMATICS
DIMENSIONAL DRAWINGS
INSTALLATION
Figure 1a - Surface mounng
STEP 1: MOUNTING THE DEVICE
1)Mountthedeviceinthedesiredlocaon(seestep1).
2)Openthelidandroutethecable(s)throughthestrainrelief(s)and
connectthewirestotheterminalblock(s)(seestep2).
3)Thedeviceisnowreadyforconguraon.
WARNING!Applypoweronlyaerthedeviceisproperlywired.
1)Selectthemounnglocaon(duct,wall,panel).
2)Usethedeviceasatemplateandmarkthescrewholes.
3)Mountwithappropriatescrews.
Figure 1b - Mounng orientaon
Figure 1c - Applicaon connecons
24 V GND 0–10 V
Terminal block Terminal block for relays
NC COM NO NC COM NO
37.1
89.0
86.5
74.5
64.5
52.5
4.2
YES NO NO
Stac pressure Filter/Damper
monitoring
Fan/Blower
monitoring
Not
connected
Copyright HK Instruments 2022 www.hkinstruments. Installaon version 8.0 2022
STEP 2: WIRING DIAGRAMS CONFIGURATION CONTINUED
ForCEcompliance,aproperlygroundedshieldingcableisrequired.
1)Unscrewthestrainreliefandroutethecable(s).Useseparatestrain
reliefforthe010Voutputcableandtherelaycable(s).
2)Connectthewiresasshowningure2aand2b.
3)Tightenthestrainrelief.
Figure 2a - Wiring diagram 010 V output
Figure 2b - Wiring diagram relay(s)
STEP 3: CONFIGURATION
1)Selectthedesiredmeasurementunit.
2)Selectthedesiredmeasurementrange.
3)Selectthedesiredresponseme.
4)Conguretherelay(s).
5)Zerothedevice.
6)Calibratethespanpoint.
7)Connectthepressuretubes.Connectposivepressuretoport
labeled"+"andnegavepressuretoport"-".
Thedeviceisnowreadytobeused.
24 V
GND
P out
Power supply
24 VDC / 24 VAC
+
Output 0...10 V
V
+
SPAn
ZEro
rEL1/2
rESP
PSEL
UnIt
Pa, kPa, mmH2O, inchWC, mbar
Pressure range selecon
Response me
Relay menu(s)
Zero point calibraon
High point calibraon menu
rES
AdJ
High point calibraon
Reset high point calibraon
HYS
SP
dir
Relay acvaon menu
Relay setpoint
Relay hysteresis 050 % of range
FALL
rISE
Relay acvaon on increasing pressure
Relay acvaon on decreasing pressure
NC
COM
NO
Relay 1
NC
COM
NO
Relay 2
With the MENU buon you can enter the menu by pressing the buon for
3 seconds. You can exit the menu without making any
changes.
With the BACK buon you can return without making changes.
With the OK buon you can open new opons or confirm changes and return
to previous display.
With the buons you can scroll the menus.
Copyright HK Instruments 2022 www.hkinstruments. Installaon version 8.0 2022
NOTE! Always zero the device before use.
Tozerothedevicetwooponsareavailable:
1)Manualzeropointcalibraon
2)Autozerocalibraon
Does my transmier have an autozero calibraon? See the product
label.Ifitshows-AZinthemodelnumber,thenyouhavetheautozero
calibraon.
1)Manualzeropointcalibraon
NOTE:Supplyvoltagemustbeconnectedatleastonehour priorto
zeropointadjustment.
a)Disconnectbothpressuretubesfromthepressureportslabeled+
and–.
b)Pushbotharrowbuonsontopofthelidshortlyorgoto
conguraonmenuandselect“Zero”.
c)Thezeroingofthedevicewillproceedautomacallywhenthe
greenledontopofthelidturnsoand“Zero”textfollowedby
 acounterfrom3to0secondsappearsonthedisplay.Thezeroing
iscompletewhenthegreenledturnsonagain.
d)ReinstallthepressuretubesensuringthattheHighpressuretube
isconnectedtotheportlabeled+,andtheLowpressuretubeis
connectedtotheportlabeled−.
NOTE:Thezeropointshouldbecalibratedviamanualzeropoint
calibraononehouraerinstallaonandatleastevery12months
duringnormaloperaons.
2)Autozerocalibraon
If the device includes the oponal autozero circuit, no acon is re-
quired.
Autozerocalibraon(-AZ)isanautozerofunconintheformofanauto-
maczeroingcircuitbuiltintothePCBboard.Theautozerocalibraon
electronicallyadjuststhetransmierzeroatpredeterminedmeinter-
vals(every 10minutes).Thefunconeliminatesalloutputsignal dri
due to thermal, electronic or mechanical eects, as well as the need
fortechnicianstoremovehighandlowpressuretubeswhenperform-
ing inial or periodic transmier zero point calibraon. The autozero
adjustmenttakes4secondsaerwhichthedevicereturnstoitsnormal
measuring mode. Duringthe 4 secondadjustmentperiod, theoutput
anddisplayvalueswillfreezetothelatestmeasuredvalue.
Transmiers equipped with the autozero calibraon are virtually
maintenancefree.
Thesellerisobligatedtoprovideawarrantyofveyearsforthedeliv-
eredgoodsregardingmaterialandmanufacturing.Thewarrantyperiod
isconsidered tostart on thedeliverydate ofthe product. If adefect
in raw materials ora produconaw isfound, the sellerisobligated,
whentheproductissenttothesellerwithoutdelayorbeforeexpira-
onofthewarranty,toamendthemistakeathis/herdiscreoneither
by repairing the defecve product or by delivering free of charge to
thebuyeranewawlessproductandsendingittothebuyer.Delivery
costsfor therepair underwarrantywillbepaidbythebuyerandthe
return costs by the seller. The warranty does not comprise damages
causedbyaccident,lightning,oodorothernaturalphenomenon,nor-
malwearandtear,improperorcarelesshandling,abnormaluse,over-
loading,improperstorage,incorrectcareorreconstrucon,orchanges
andinstallaonworknotdonebytheseller.Theseleconofmaterials
fordevicespronetocorrosionisthebuyer’sresponsibility,unlessother-
wiseislegallyagreedupon.Shouldthemanufactureralterthestructure
ofthedevice, thesellerisnotobligatedto makecomparablechanges
todevicesalreadypurchased.Appealingforwarrantyrequiresthatthe
buyerhascorrectlyfullledhis/herduesarisenfromthedeliveryand
stated in the contract. The seller will give a new warranty for goods
thathavebeenreplacedorrepairedwithinthewarranty,howeveronly
totheexpiraonoftheoriginalproduct’swarrantyme.Thewarranty
includestherepairofadefecvepartordevice,orifneeded,anewpart
ordevice,butnotinstallaonorexchangecosts.Undernocircumstance
isthesellerliablefordamagescompensaonforindirectdamage.
RECYCLING/DISPOSAL
The parts le over from installaon should be
recycled according to your local instrucons.
Decommissioned devices should be taken to a
recyclingsitethatspecializesinelectronicwaste.
STEP 4: ZEROING THE DEVICE WARRANTY POLICY
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4

HK Instruments DPI series Installation guide

Type
Installation guide
This manual is also suitable for

HK Instruments DPI series is a versatile electronic differential pressure switch with built-in transmitter functionalities. It offers accurate and reliable pressure measurement with a wide range of applications in HVAC/R systems, including fan, blower, and filter monitoring, staircase pressure monitoring, pressure monitoring in cleanrooms, and boiler pressure monitoring. Its key features include adjustable switching points, relay activation on increasing or decreasing pressure, and autozero calibration for enhanced stability.