Copyright HK Instruments 2021 www.hkinstruments. Installaon version 2.0 2021
Thesellerisobligatedtoprovideawarrantyofveyearsforthedeliv-
eredgoodsregardingmaterialandmanufacturing.Thewarrantyperiod
isconsidered tostart on thedelivery dateof theproduct.If a defect
in raw materials or a produconawisfound, theseller is obligated,
whentheproductissenttothesellerwithoutdelayorbeforeexpira-
onofthewarranty,toamendthemistakeathis/herdiscreoneither
by repairing the defecve product or by delivering free of charge to
thebuyeranewawlessproductandsendingittothebuyer.Delivery
costsfor therepairunderwarrantywillbepaidbythebuyer and the
return costs by the seller. The warranty does not comprise damages
causedbyaccident,lightning,oodorothernaturalphenomenon,nor-
malwearandtear,improperorcarelesshandling,abnormaluse,over-
loading,improperstorage,incorrectcareorreconstrucon,orchanges
andinstallaonworknotdonebytheseller.Theseleconofmaterials
fordevicespronetocorrosionisthebuyer’sresponsibility,unlessother-
wiseislegallyagreedupon.Shouldthemanufactureralterthestructure
ofthedevice, thesellerisnotobligatedtomakecomparablechanges
todevicesalreadypurchased.Appealingforwarrantyrequiresthatthe
buyerhascorrectlyfullledhis/herduesarisenfromthedeliveryand
stated in the contract. The seller will give a new warranty for goods
thathavebeenreplacedorrepairedwithinthewarranty,howeveronly
totheexpiraonoftheoriginalproduct’swarrantyme.Thewarranty
includestherepairofadefecvepartordevice,orifneeded,anewpart
ordevice,butnotinstallaonorexchangecosts.Undernocircumstance
isthesellerliablefordamagescompensaonforindirectdamage.
STEP 8: ZEROING THE DEVICE
WARRANTY POLICY
RECYCLING/DISPOSAL
The parts le over from installaon should be
recycled according to your local instrucons.
Decommissioned devices should be taken to a
recyclingsitethatspecializesinelectronicwaste.
Span point calibration
1)Autozerocalibraon
Autozero calibraon (-AZ) is an autozero funcon in the form of an
automaczeroingcircuitbuiltintothePCBboard.Theautozerocali-
braon electronically adjusts the transmier zero at predetermined
me intervals(every10minutes).Thefuncon eliminatesalloutput
signaldriduetothermal,electronicormechanicaleects,aswellas
theneedfortechnicianstoremovehighandlowpressuretubeswhen
performing inial or periodic transmier zero point calibraon. The
autozeroadjustmenttakes4secondsaerwhichthedevicereturnsto
itsnormalmeasuringmode.Duringthe4secondadjustmentperiod,
theoutputanddisplayvalueswillfreezetothelatestmeasuredvalue.
Transmiersequippedwiththeautozerocalibraonarevirtuallymain-
tenancefreeandmanualzeroingisnotrequired.
NOTE! Always zero the device before use.
Tozerothedevicetwooponsareavailable:
1)Autozerocalibraon(manualzeroingnotrequired)
2)ManualPushbuonzeropointcalibraon
2)ManualPushbuonzeropointcalibraon
NOTE:Supplyvoltagemustbeconnectedatleastonehourpriortozero
pointadjustment.
a)Disconnectbothpressuretubesfromthepressureportslabeled+
and–.
b)PushdownthezerobuonunltheLEDlight(red)turnsonandthe
displayreads“zeroing”(displayopononly).(seeFigure4)
c)Thezeroingofthedevicewillproceedautomacallyin4seconds.
Zeroingledlightsonlyforamoment.Zeroiningiscompletewhen
thedisplayreads0(displayopononly).
d)ReinstallthepressuretubesensuringthattheHighpressuretube
isconnectedtotheportlabeled+,andtheLowpressuretubeis
connectedtotheportlabeled−.
a) Disconnect both pressure tubes from the pressure ports labeled +
and –.
b) Push down the zero buon (joysck) unl the LED light (red)
turns on and the display reads “zeroing” (display opon only). (see
Figure 6)
c) The zeroing of the device will proceed automacally. Zeroing is
complete when the LED turns off, and the display reads 0 (display
opon only).
d) Reinstall the pressure tubes, ensuring the High pressure tube is
connected to the port labeled +, and the Low pressure tube is
connected to the port labeled −.
Press down buon
LED turns ON
Display reads “Zeroing”
LED
Figure 4
Oponalspanpointcalibraon(-S)isusedforadjusngtheupperrange
value of the measurement range. The span point calibraon has been
performedbythemanufactureranditisusuallynotnecessarytoadjust
thespansengonsite.Insomecases,spanpointeldcalibraonmay
benecessary,e.g.incaseofannualcalibraonincleanroomapplicaons.
Thespanpointcalibraonrequiresaceredhighaccuracypressurecali-
bratorforreferencepressure.
Toperformaspanpointcalibraon:
1) Connect pressure tubes between the transmier and the pressure
calibratorconnectors.Connectposivepressuretoport“+”andnega-
vepressuretoport“-”.
2)Setthecalibratorsupplypressuretomatchtheupperrangevalueof
themeasurementrangeusedinthetransmier(e.g.whenused-50…
+50Pameasurementrange,setthecalibratorpressureto+50Pa).
3)Openthelidofthetransmier.
4)Performamanualpushbuonzeropointcalibraon(seestep8).
5)Adjusttheupperrangevaluebyturningthetrimmer(seeschemacs)
witha screwdriverunlthe value shown onthe transmier display
correspondstothesetupvalueofthecalibrator.