PIR Sensitivity
1.Standindifferentareasoftheroomandwaveyourhands.
2.IftheRedLEDdoesnotturnON,checkforanyobstructions.
3.Standstillthreetofourfeetawayfromsensorforfiveseconds.LEDshouldnotturnON.
4.IfRedLEDturnsONwithoutmotionorisconstantlyonadjustPIRsensitivityto50%bymovingDIPSwitch5up.
Field-of-view outside the space
1.AdjustPIRsensitivityto50%bymovingDIPSwitch5up.
2.Usenon-reflectivetapestripstocovertheportionsofthesensorlensthatviewoutsidethespace.
Daylight Adjustments
ThedaylightingfeaturepreventsthelightsfromturningONwhentheroom
isadequatelyilluminatedbynaturallight.Ifthereisenoughlightintheroom
regardlessofoccupancy,thesensorwillholdthelightsOFF.Ifthereisnotenough
lightintheroom,thesensorwillallowthelightstoturnONwhenoccupied.The
sensorwillnotallowthedaylightingfeaturetoturntheloadOFFuntilthespaceis
vacantorthelightlevelrisesabovethesetpointandtheTimeDelayexpires.While
inManualActivationMode,ifsomeoneattemptstoturntheloadONandthereis
sufficientdaylightavailablethe
daylightingfeaturewillholdthelightsOFF.
1. Setthelightlevelwhentheambientlightisatthelevelwherenoartificial
lightisneeded.Ifthisfeatureisnotneeded,leavethelightlevelat
maximum.(fullyCW)
2. Withtheload(s)ON,putthesensorintoTestMode.ToplaceintoTestMode,
toggleDIPSwitch8outofitscurrentposition,wait3secondsandthenback
intoitsoriginalposition.
3. SettheLightleveltominimum.(fullyCCW)
4. LetthesensortimeoutsolightsareOFF.EnterthespaceandlightsshouldremainOFF.
5. MakesurenottoblockthesensorfromthedaylightsourceandadjustthelightlevelpotentiometerCWinsmall
increments.Pause5secondsbetweeneachadjustment)
6. LightswillnotturnONuponoccupancyactivation,whentheambientlightlevelexceedsthedaylightthresholdsetting.
Time Delay Adjustments
PeoplewhoremainverystillforlongperiodsoftimemayneedalongerTimeDelaythanthedefaultsettingof10
minutes.Aslongastheself-adjustingfeatureisenabled,theswitchwillrespondtoeachpairofFalse-offswithno
normaloffinbetween,byalternatelymakingslightadjustmentsto
eitherTimeDelay(by2minuteincrements)orsensitivity,sothere
should
benoneedformanualadjustment.Ifmanualadjustmentis
desired,refertoTimeDelaysettingsinDIPSwitchlegend.
ResetsensorTimeDelaytofactorysettingsbymovingDIP
Switches1and2down.(IfDIPSwitches1and2arealready
down,toggleDIPSwitch1outofitscurrentposition,wait3
seconds,andthenbacktoitsoriginalposition)
Warranties and Limitation of Liability
DIP Switch Settings
Troubleshooting
Pleaserefertowww.coopercontrol.comundertheLegalsectionforourtermsandconditions.
Checkout and Adjustment
347 VAC
BLACK
BLUE
NEUTRAL
GROUND
GREEN
LOAD 1
LOAD 2
LOAD 1
BLACK
BLUE
NEUTRAL
THREE-WAY WIRING DIAGRAM:
LIGHTS WILL TURN OFF, WHEN UNIT THAT WAS TURNED ON LAST AND/OR DETECTED MOTION LAST TIMES-OUT.
GROUND
GREEN
347 VAC
BLACK
BLUE
GROUND
GREEN
TRAVELER
WIRES
Wiring Diagram 3: 347 VAC single level single circuit three-way wiring diagram
Wiring Diagram 2: 347 VAC single level switch dual level wiring using a toggle switch wiring diagram
5 Minutes
Auto*
*Self-Adjusts to
10 min. user mode
Time Delay
DIP Switch
Activation
PIR Sensitivity Override
Relay 1
Not Used
EcoMeter
Walk-Through Mode
Default =
30 Minutes
15 Minutes
12
DIP Switch Legend
6
Disable
Enable
43
Auto
Manual
5
Full
50%
8
7
Enable
Disable
Disable
Enable
12345678
AdjustmentsshouldbemadewiththeHVACsystemonsothattheinstallerwillbeabletodetecttheeffectof
airflowontheoperationoftheONW-P-1001-347.Useonlyinsulatedtoolstomakeadjustments.
Immediatelyafterapplyingpowertothelightingcircuit,waitapproximatelytwominutesfortheswitchtopowerup
andstabilize.
Self-Adjust
Sensorisshippedinself-adjustmode.ThisappliestoTimeDelay,USandPIRsensitivity.Inpreparationforthe
InstallerTest,theTimeDelayissetto15seconds,afterthesensorisinstalled,poweredONandhasstabilized,the
unitwillTime-out15secondsafterthelastmotiondetected.Coverageandsensitivitycanbeconfirmedbywatching
theRed(PIR)indicatorLEDonthefrontofthesensor,whilemovingaroundtheroom.
1.WalkaroundtheroomandmonitorLEDs.
2.Standindifferentpartsoftheroomandwaveyour
hands.LEDshouldonlyturnONforonesecondwith
eachmotion.(IfLEDdoesnotturnON,gotoInstaller
AdjustmentsSection)
3.Standstillthreetofourfeetawayfromsensorforfive
seconds.LEDshouldnotturnON.(IfLEDturnson,go
toInstallerAdjustmentssection)
4.Walkoutsidetheroomandwait15secondsforthe
lights
toturnOFF.(IflightsdonotturnoffgotoInstaller
AdjustmentsSection)
5.Re-entertheroomtoactivatesensor.(Iflightsdonot
turnONgotoTroubleshootingSection)
6.Atthispointyoucanexittheroomandletthesensor
Time-outandisOFFwithpoweronforfiveminutes,the
unitwillgotoa10minuteTimeDelayuser
modeseting.
Note:
ToplaceintoTestMode,toggleDIPSwitch8outofitscurrentposition,wait3seconds,andthenbackintoitsoriginalposition.
ON/OFF Button
PIR Lens
DIP Switches
Daylight
Sensor Level
Adjustment
Red (PIR)
12345678
DIP Switches
1 & 2
Issue Possible Causes Suggestions
Lights
Will Not
Turn ON
automatically
SensorisinManualONmode
PressPushbutton.IfAutoMode
isdesiredchangeActivationModetoAuto.
SensorwasturnedOFFmanually.IftheSensor
wasturnedOFFmanuallybeforetheTimeDelay
expired,lightswillremainOFFfortheremainder
oftheTimeDelay.
CheckEcoMeterLED,ifLEDisONthisis
anindicationthatthelightswereturnedOFFmanually.
PressthePushbuttontoturnthelightsbackON.
DaylightFeatureEnabled
IfalllightsarerequiredtoturnON
adjustdaylightpotentiometer.
Powerinterruption Checkincomingvoltageand/orwiring.
Lights
Will Not
Turn ON
manually
DaylightFeatureEnabled
IfalllightsarerequiredtoturnON
adjustdaylightpotentiometer.
Powerinterruption Checkincomingvoltageand/orwiring.
If lights will still not turn ON, set sensor to override mode and call Technical Services at 1-800-553-3879
Lights
Will Not
Turn OFF
automatically
Override MakesuresensorisnotinOverrideMode(DIPSwitch8up).
Self-Adjust
IfsensorisinSelf-AdjustMode,itmaybepossibleforthe
unittohaveincreasedtheTimeDelaytoa30minutedelay.
IfthelightsdonotturnOFFafter30minutesfollownextstep.
30MinuteDelay
MaximumTimeDelayis30Minutes.CheckDIPSwitches
toverifyDIPSwitchsettings.IflightsdonotturnOFFatthe
setTimeDelay,checknextstep.
PIR
activatedbyheatsourceotherthanoccupant MoveDIPSwitch5up.
Lights
Will Not
Turn OFF
automatically
CallTechnicalServices
If lights will still not turn OFF, call Technical Services at 1-800-553-3879
Installer Adjustments
CAUTION: If a room is wired for two circuits using two separate hot leads, it is very important to connect only
one circuit per relay. Both circuits must be fed from the same phase.
Override
TheOverridesettingallowsthesensortooperateasaserviceswitchintheunlikelyeventoffailure.
1.MoveDIPSwitch8up.