Installation Instructions
NeoSwitch Passive Infrared (PIR)
Dual Relay Occupancy Sensing Wall Switch
(Ground Required)
• Readallinstructionsonbothsidesofthis
sheetfirst
• InstallinaccordancewithALLlocalcodes
• Forindooruseonly
Technology:PassiveInfrared(PIR)
Electrical Ratings:
120VAC:
• Incandescent/Tungsten–
Max.load:6.7amps,800W,50/60Hz
• Fuorescent/Ballast–
Max.load:10amps,1200W,50/60Hz
MotorLoad:¼HP@125VAC
277VAC:
• Fluorescent/Ballast–
Max.load:9.8amps,2700W,50/60Hz
Ballast Compatibility:Compatiblewithmagneticand
electronicballasts
No Minimum Load Requirement
Time Delays:Self-Adjusting,15seconds/test(10min
Auto),Selectable5,15,30minutes
Coverage:Majormotion–1000sq.ft.
Minormotion–300sq.ft.
Light Level Sensing:0to200foot-candles
Operating Environment:
• Temperature:32°F–104°F(0°C–40°C)
• RelativeHumidity:20%to90%Non-condensing
Housing:Durable,injectionmoldedhousing.Polycarbonate
resincomplieswithUL94VO.
Size:
• MountingPlate/StrapDimensions:
4.195"Hx1.732"W(106.553mmx44mm)
• ProductHousingDimensions:
2.618"Hx1.752"Wx1.9"D
(66.5mmx44.5mmx48.26mm)
LED Indicators:RedLEDindicatesPIRdetection;Green
LEDactsasEcoMeterornightlightlocator.
TheONW-P-1001-DMVOccupancySensingWallSwitchisaPassiveInfrared(PIR)motionsensinglightingcontroland
conventionalwallswitchall-in-one,used
forenergysavingsandconvenience.
PIR Technology
Thesensor’ssegmentedlensdividesthefieldofviewintosensorzones,anddetectsthechangesintemperaturethat
arecreatedwhenaperson,orpartofapersonassmallasahand,passesintooroutofasensorzone.
TheONW-P-1001-DMVallowsthecontroloftwoseparateloadswithoneoccupancysensorswitch.
EnergySaverMode–EitherorbothloadsmaybeconfiguredtoturnONmanually.Thedefaultsettingforthesecond
loadisManualON.Thisensuresthewallswitchonlyactivatesoneload.Ifbothloadsareonwhenthesensortimes-out,
onlytheprimaryloadwillbeactivated.IfthelightswereshutOFFmanually,theunitwillactivatetheprimaryloadonly.
InAutomaticONMode,thelightsturnONautomaticallywhenapersonenterstheroom.InManualONMode,thelights
areturnedONbypressingtheuniversallyrecognizedlighticonpushbutton.Ineithermode,thelightsstayONaslongas
thesensordetectsmotionintheroom.Whentheroomisvacated,thelightsturnOFFautomaticallyafterapresettime
delayinterval.
Thesensorincludesself-adaptivetechnologythatcontinuallyadjuststoconditionsby
adjustingsensitivityandtime
delayinreal-time.Byadjustingsensitivityandtimedelayautomatically,thesensorismaximizingthepotentialenergy
savingsthatareavailableintheparticularapplication.
TheEcoMeterprovidesavisualindicatorofenergyusage,increasingenduserawarenessandremindingindividualsto
takecontroloftheirlightingtomaximizeenergysavings.
TheDaylightingfeaturepreventslightsfromturningON,whentheroomisadequatelyilluminatedbynaturallight.
Walk-ThroughfeaturemaximizesenergysavingsbynotleavingthelightsONafteramomentaryoccupancy.Thesensor
willswitchthelightsONwhenitdetectsapersonenteringthearea.Ifthesensordoesnotcontinuetodetectmotion20
secondsfollowingtheinitialactivation,itwillautomaticallygotoashorter2minutetimedelay.
BathroomMode–Whenselected,bathroommodekeepsthesecondrelayONforanadditional8minutes,afterthe
firstrelayhasbeenturnedO FF.Combinethiswithchangingthepushbuttontothelight/fangraphicandyounowhavethe
universallyrecognizedandeasytousebathroomsolution.
RelaySwapOption–Acommonprobleminelectricwiringiswiringthewrongswitchtothewrongload.Thiscanmake
controlofloadsconfusingto
anenduser.TheRelaySwapoptionsolvestheproblembyallowingtheswitchbuttonsonthe
faceoftheunittobeswapped,aftertheunitiswiredandinstalled.
TheONW-P-1001-DMVisdesignedforofficesupto300squarefeet.
WheninstallingtheONW-P-1001-DMVinanewjunctionbox,choosetheswitchlocationcarefullytoprovideoptimum
coverageoftheoccupiedarea.Whenreplacinganexistingwallswitch,bearinmindthattheremustbeaclearline-of-sight
betweenthesensorandtheareatobecovered.AvoidpointingtheONW-P-1001-DMVdirectlyintothehallwaywhereitmay
detectpassers-by.
EcoMeter Operation
Load 1 Load 2 EcoMeter LED
OFF OFF 100%
ON OFF 50%
OFF ON 50%
ON ON OFF
Action EcoMeter Benefit
Apersonentersthespaceand
oneoftheloadsisactivated
50% Increasedawarenessofenergysavings
BothloadsareON OFF
Theareaisvacatedandthe
lightsturnOFFautomatically
100%
Increasedawarenessofenergysavings;
Actsasanightlightlocator
ApersonturnsthelightsOFF
manuallyuponexitinganarea
100%
Increasedawarenessofenergy
savingsandremindsindividualstotake
controloftheirlightingforadditional
savings;Actsasanightlightlocator
IftheDaylightingfunctionis
activatedforoneofthetwoloads
andthereissufficientdaylightinthe
space,theunitwillholdthatloadOFF
50%
Increasedawarenessofenergy
savings;Letspersonsknowthatthe
daylightsensorisholdingthelightsOFF;
Actsasanightlightlocator
IftheDaylightingfunctionis
activatedforbothloadsandthereis
sufficientdaylightinthespace,the
unitwillholdthatloadsOFF
100%
Increasedawarenessofenergy
savings;Letspersonsknowthatthe
daylightsensorisholdingthelightsOFF;
Actsasanightlightlocator
CAUTION: Before installing or performing any service on a Greengate system, the power MUST be turned OFF at
the branch circuit breaker. According to NEC 240-83(d), if the branch circuit breaker is used as the main switch
for a fluorescent lighting circuit, the circuit breaker should be marked “SWD.” All installations should be in
compliance with the National Electric Code and all state and local codes.
NOTE REGARDING COMPACT FLUORESCENT LAMPS: The life of some compact fluorescent lamps (CFLs) is shortened
by frequent automatic or manual switching. Check with CFL and ballast manufacturer to determine the effects of cycling.
1. MakesurepoweristurnedOFFatthebranchcircuitbreaker.
2.Wireunitsasshown
inwiringdiagramsperapplicablevoltagerequirements.
3.Mountunittowallbox.
4. TurnpowerbackONatthebranchcircuitbreakerandwait2minutesfortheunittostabilize.
5.Makenecessaryadjustments.(SeeCheckoutandAdjustmentssection)
6.Installwallswitchplate.
LOAD 2
LOAD 1
120/277 VAC
BLACK
RED
BLUE
RED
NEUTRAL
GROUND
GREEN
Wiring Diagram 1: 120/277 VAC dual level single circuit wiring diagram
TheONW-P-1001-DMVcanbeinstalledinanystandardsinglegangbox.Itmaybe
installedinthesamemannerasanordinarywallswitch.
• WiretheONW-P-1001-DMVasdescribedinthewiringsection
• MounttheONW-P-1001-DMVinthejunctionbox
,
36
20
,
Maximum coverage area may
vary somewhat according to room
shape and the presence of obstacles.
8
,
Minor Motion, IR
Major Motion, IR
Coverage Description
Specifications
General Information
Location
Installation
Wiring
Model # ONW-P-1001-DMV-W
Model # ONW-P-1001-DMV-V
Model # ONW-P-1001-DMV-LA
Model # ONW-P-1001-DMV-G
Model # ONW-P-1001-DMV-B
P/N 9850-000341-01