Cooper Lighting NeoSwitch - 120/277/347V PIR/Dual Relay Wall Switch Sensor (Ground Required) Installation guide

Type
Installation guide
Eaton’s Cooper Controls Business
203 Cooper Circle
Peachtree City, Georgia 30269
www.coopercontrol.com
Installation Instructions
NeoSwitch Passive Infrared (PIR)
Dual Relay Occupancy Sensing Wall Switch
(Ground Required)
• Readallinstructionsonbothsidesofthis
sheetfirst
• InstallinaccordancewithALLlocalcodes
• Forindooruseonly
Technology:PassiveInfrared(PIR)
Electrical Ratings:
120VAC:
• Incandescent/Tungsten–
Max.load:6.7amps,800W,50/60Hz
• Fuorescent/Ballast–
Max.load:10amps,1200W,50/60Hz
MotorLoad:¼HP@125VAC
277VAC:
• Fluorescent/Ballast–
Max.load:9.8amps,2700W,50/60Hz
Ballast Compatibility:Compatiblewithmagneticand
electronicballasts
No Minimum Load Requirement
Time Delays:Self-Adjusting,15seconds/test(10min
Auto),Selectable5,15,30minutes
Coverage:Majormotion–1000sq.ft.
Minormotion–300sq.ft.
Light Level Sensing:0to200foot-candles
Operating Environment:
• Temperature:32°F–10F(0°C–40°C)
• RelativeHumidity:20%to90%Non-condensing
Housing:Durable,injectionmoldedhousing.Polycarbonate
resincomplieswithUL94VO.
Size:
• MountingPlate/StrapDimensions:
4.195"Hx1.732"W(106.553mmx44mm)
• ProductHousingDimensions:
2.618"Hx1.752"Wx1.9"D
(66.5mmx44.5mmx48.26mm)
LED Indicators:RedLEDindicatesPIRdetection;Green
LEDactsasEcoMeterornightlightlocator.
TheONW-P-1001-DMVOccupancySensingWallSwitchisaPassiveInfrared(PIR)motionsensinglightingcontroland
conventionalwallswitchall-in-one,used
forenergysavingsandconvenience.
PIR Technology
Thesensorssegmentedlensdividesthefieldofviewintosensorzones,anddetectsthechangesintemperaturethat
arecreatedwhenaperson,orpartofapersonassmallasahand,passesintooroutofasensorzone.
TheONW-P-1001-DMVallowsthecontroloftwoseparateloadswithoneoccupancysensorswitch.
EnergySaverMode–EitherorbothloadsmaybeconfiguredtoturnONmanually.Thedefaultsettingforthesecond
loadisManualON.Thisensuresthewallswitchonlyactivatesoneload.Ifbothloadsareonwhenthesensortimes-out,
onlytheprimaryloadwillbeactivated.IfthelightswereshutOFFmanually,theunitwillactivatetheprimaryloadonly.
InAutomaticONMode,thelightsturnONautomaticallywhenapersonenterstheroom.InManualONMode,thelights
areturnedONbypressingtheuniversallyrecognizedlighticonpushbutton.Ineithermode,thelightsstayONaslongas
thesensordetectsmotionintheroom.Whentheroomisvacated,thelightsturnOFFautomaticallyafterapresettime
delayinterval.
Thesensorincludesself-adaptivetechnologythatcontinuallyadjuststoconditionsby
adjustingsensitivityandtime
delayinreal-time.Byadjustingsensitivityandtimedelayautomatically,thesensorismaximizingthepotentialenergy
savingsthatareavailableintheparticularapplication.
TheEcoMeterprovidesavisualindicatorofenergyusage,increasingenduserawarenessandremindingindividualsto
takecontroloftheirlightingtomaximizeenergysavings.
TheDaylightingfeaturepreventslightsfromturningON,whentheroomisadequatelyilluminatedbynaturallight.
Walk-ThroughfeaturemaximizesenergysavingsbynotleavingthelightsONafteramomentaryoccupancy.Thesensor
willswitchthelightsONwhenitdetectsapersonenteringthearea.Ifthesensordoesnotcontinuetodetectmotion20
secondsfollowingtheinitialactivation,itwillautomaticallygotoashorter2minutetimedelay.
BathroomMode–Whenselected,bathroommodekeepsthesecondrelayONforanadditional8minutes,afterthe
firstrelayhasbeenturnedO FF.Combinethiswithchangingthepushbuttontothelight/fangraphicandyounowhavethe
universallyrecognizedandeasytousebathroomsolution.
RelaySwapOption–Acommonprobleminelectricwiringiswiringthewrongswitchtothewrongload.Thiscanmake
controlofloadsconfusingto
anenduser.TheRelaySwapoptionsolvestheproblembyallowingtheswitchbuttonsonthe
faceoftheunittobeswapped,aftertheunitiswiredandinstalled.
TheONW-P-1001-DMVisdesignedforofficesupto300squarefeet.
WheninstallingtheONW-P-1001-DMVinanewjunctionbox,choosetheswitchlocationcarefullytoprovideoptimum
coverageoftheoccupiedarea.Whenreplacinganexistingwallswitch,bearinmindthattheremustbeaclearline-of-sight
betweenthesensorandtheareatobecovered.AvoidpointingtheONW-P-1001-DMVdirectlyintothehallwaywhereitmay
detectpassers-by.
EcoMeter Operation
Load 1 Load 2 EcoMeter LED
OFF OFF 100%
ON OFF 50%
OFF ON 50%
ON ON OFF
Action EcoMeter Benefit
Apersonentersthespaceand
oneoftheloadsisactivated
50% Increasedawarenessofenergysavings
BothloadsareON OFF
Theareaisvacatedandthe
lightsturnOFFautomatically
100%
Increasedawarenessofenergysavings;
Actsasanightlightlocator
ApersonturnsthelightsOFF
manuallyuponexitinganarea
100%
Increasedawarenessofenergy
savingsandremindsindividualstotake
controloftheirlightingforadditional
savings;Actsasanightlightlocator
IftheDaylightingfunctionis
activatedforoneofthetwoloads
andthereissufficientdaylightinthe
space,theunitwillholdthatloadOFF
50%
Increasedawarenessofenergy
savings;Letspersonsknowthatthe
daylightsensorisholdingthelightsOFF;
Actsasanightlightlocator
IftheDaylightingfunctionis
activatedforbothloadsandthereis
sufficientdaylightinthespace,the
unitwillholdthatloadsOFF
100%
Increasedawarenessofenergy
savings;Letspersonsknowthatthe
daylightsensorisholdingthelightsOFF;
Actsasanightlightlocator
CAUTION: Before installing or performing any service on a Greengate system, the power MUST be turned OFF at
the branch circuit breaker. According to NEC 240-83(d), if the branch circuit breaker is used as the main switch
for a fluorescent lighting circuit, the circuit breaker should be marked “SWD.” All installations should be in
compliance with the National Electric Code and all state and local codes.
NOTE REGARDING COMPACT FLUORESCENT LAMPS: The life of some compact fluorescent lamps (CFLs) is shortened
by frequent automatic or manual switching. Check with CFL and ballast manufacturer to determine the effects of cycling.
1. MakesurepoweristurnedOFFatthebranchcircuitbreaker.
2.Wireunitsasshown
inwiringdiagramsperapplicablevoltagerequirements.
3.Mountunittowallbox.
4. TurnpowerbackONatthebranchcircuitbreakerandwait2minutesfortheunittostabilize.
5.Makenecessaryadjustments.(SeeCheckoutandAdjustmentssection)
6.Installwallswitchplate.
LOAD 2
LOAD 1
120/277 VAC
BLACK
RED
BLUE
RED
NEUTRAL
GROUND
GREEN
Wiring Diagram 1: 120/277 VAC dual level single circuit wiring diagram
TheONW-P-1001-DMVcanbeinstalledinanystandardsinglegangbox.Itmaybe
installedinthesamemannerasanordinarywallswitch.
• WiretheONW-P-1001-DMVasdescribedinthewiringsection
• MounttheONW-P-1001-DMVinthejunctionbox
,
36
20
,
Maximum coverage area may
vary somewhat according to room
shape and the presence of obstacles.
8
,
Minor Motion, IR
Major Motion, IR
Coverage Description
Specifications
General Information
Location
Installation
Wiring
Model # ONW-P-1001-DMV-W
Model # ONW-P-1001-DMV-V
Model # ONW-P-1001-DMV-LA
Model # ONW-P-1001-DMV-G
Model # ONW-P-1001-DMV-B
P/N 9850-000341-01
Eaton’s Cooper Controls Business
203 Cooper Circle
Peachtree City, Georgia 30269
www.coopercontrol.com
Printed in Malaysia
PIR Sensitivity
1. Standindifferentareasoftheroomandwaveyourhands.
2.IftheRedLEDdoesnotturnON,checkforanyobstructions.
3.Standstillthreetofourfeetawayfromsensorforveseconds.LEDshouldnotturnON.
4. IfRedLEDturnsONwithoutmotionorisconstantlyonadjustPIRsensitivityto50%bymovingDIPSwitch5up.
Field-of-view outside the space
1. AdjustPIRsensitivityto50%bymovingDIPSwitch5up.
2.Usenon-reectivetapestripstocovertheportionsofthesensorlensthatviewoutsidethespace.
Daylight Adjustments
TheDaylightingfeaturepreventsthelightsfromturningONwhen
theroomisadequatelyilluminatedbynaturallight.Ifthereisenough
lightintheroomregardlessofoccupancy,thesensorwillholdthe
lightsOFF.Ifthereisnotenoughlightintheroom,thesensorwill
allowthelightstoturnONwhenoccupied.TheDaylightingfeature
allowstheselectionofwhichrelaytocontrolviadaylighting(dualload
modelsonly).ThesensorwillnotallowtheDaylightingfeaturetoturn
theloadOFFuntilthespaceisvacantifthelightlevelrisesabovethe
setpointandthetimedelayexpires.WhileinManualActivationMode,
ifsomeoneattemptstoturntheloadONandthereissufcientdaylightavailabletheDaylightingfeaturewillholdthelightsOF F.
1. Setthelightlevelwhentheambientlightisatthelevelwherenoartificiallightisneeded.Ifthisfeatureisnotneeded,
leavethelightlevelatmaximum(fullyCW).
2.SetDIPSwitches11(Relay1)and/or12(Relay2)fordaylightcontrol.
3.Withtheload(s)ON,putthesensorintoTestMode.ToplaceintoTestMode,toggleDIPSwitch12outofitscurrent
position,wait3secondsandthenbackintoitsoriginalposition.
4. Setthelightleveltominimum(fullyCCW).
5.Letthesensortime-outsolightsareOF F.EnterthespaceandlightsshouldremainOF F.
6.MakesurenottoblockthesensorfromthedaylightsourceandadjustthelightlevelpotentiometerCWinsmall
increments.(Pause5secondsbetweeneachadjustment)
7. LightswillnotturnONuponoccupancyactivation,whentheambientlightlevelexceedsthedaylightthresholdsetting.
Time Delay Adjustments
Peoplewhoremainverystillforlongperiodsoftimemayneed
alongertimedelaythanthedefaultsettingof10minutes.Aslong
astheself-adjustingfeatureisenabled,theswitchwillrespond
toeachpairoffalse-OFFswithnonormalOFFinbetween,by
alternatelymakingslightadjustmentstoeithertimedelay(by2minute
increments)orsensitivity,sothereshouldbenoneedformanual
adjustment.Ifmanualadjustmentisdesired,refertoTimeDelay
settingsinDIPSwitchlegend.
ResetsensortimedelaytofactorysettingsbymovingDIPSwitches
1and2down.(IfDIPSwitches1and2arealreadydown,toggleDIP
Switch1outofitscurrentposition,wait3seconds,andthenbackto
itsoriginalposition)
Pleaserefertowww.coopercontrol.comundertheLegalsectionforourtermsandconditions.
1. WalkaroundtheroomandmonitorLEDs.
2. Standindifferentpartsoftheroomandwaveyourhands.
LEDshouldonlyturnONforonesecondwitheachmotion.
(IfLEDdoesnotturnON,gotoInstallerAdjustments–
SensitivityAdjustmentSection)
3. Standstillthreetofourfeetawayfromsensorforve
seconds.LEDshouldnotturnON.(IfLEDturnsON,goto
InstallerAdjustments–SensitivityAdjustmentssection)
4. Walkoutsidetheroomandwait15secondsforthe
lightstoturnOFF.(IflightsdonotturnOFFgotoInstaller
Adjustments
Section)
5. Re-entertheroomtoactivatesensor.(Iflightsdonotturn
ONgotoTroubleshootingSection)
6. Atthispointyoucanexittheroomandletthesensortime-
out.Whenthesensortimes-outandisinactiveforve
minutes,theunitwillgotoa10minutetimedelayuser
modesetting.
Note:ToplaceintoTestMode,toggleDIPSwitch12outofitscurrent
position,wait3seconds,andthenbackintoitsoriginalposition.
LOAD 2
LOAD 1
BLACK
RED
BLUE
RED
NEUTRAL (CIRCUIT 1)
NEUTRAL (CIRCUIT 2)
GROUND
CIRCUIT 1
GREEN
CIRCUIT 1
120/277 VAC
CIRCUIT 2
120/277 VAC
LOAD 2
LOAD 1
BLACK
RED
BLUE
RED
NEUTRAL
THREE-WAY WIRING DIAGRAM:
LIGHTS WILL TURN OFF, WHEN UNIT THAT WAS TURNED ON LAST AND/OR DETECTED MOTION LAST TIMES-OUT
GROUND
GREEN
120/277 VAC
BLACK
RED
BLUE
RED
GROUND
GREEN
TRAVELER
WIRES
Wiring Diagram 3: 120/277 VAC dual level single circuit three-way wiring diagram
Wiring Diagram 2: 120/277 VAC dual level dual circuit wiring diagram
CAUTION: If a room is wired for two circuits using two separate hot leads, it is very important to connect only one circuit
per relay. Both circuits must be fed from the same phase.
Issue Possible Causes Suggestions
Lights
Will Not
Turn ON
automatically
SensorisinManualONmode
Presspushbutton.IfAutoMode
isdesiredchangeActivationModetoAuto.
SensorwasturnedOFFmanually.Ifthe
SensorwasturnedOFFmanuallybefore
thetimedelayexpired,lightswillremain
OFFfortheremainderofthetimedelay.
CheckEcoMeterLED.IfLEDisONthisisan
indicationthatthelightswereturnedOFFmanually.
PressthepushbuttontoturnthelightsbackON.
DaylightingFeatureEnabled
IfalllightsarerequiredtoturnONadjust
DIPSwitches11and12and/ordaylightpotentiometer.
Powerinterruption Checkincomingvoltageand/orwiring.
Lights
Will Not
Turn ON
manually
DaylightingFeatureEnabled
IfalllightsarerequiredadjustDIPSwitches
11and12and/ordaylightpotentiometer.
Powerinterruption Checkincomingvoltageand/orwiring.
If lights will still not turn ON, set sensor to override mode and call Technical Services at 1-800-553-3879
Lights
Will Not
Turn OFF
automatically
Override MakesuresensorisnotinOverrideMode(DIPSwitch8up).
Self-Adjust
IfsensorisinSelf-AdjustMode,itmaybepossibleforthe
unittohaveincreasedthetimedelaytoa30minutedelay.
IfthelightsdonotturnOFFafter30minutesfollownextstep.
30MinuteDelay
Maximumtimedelayis30Minutes.CheckDIP
SwitchestoverifyDIPSwitchsettings.Iflightsdo
not
turnOFFatthesettimedelay,checknextstep.
PIRactivatedbyheatsourceotherthanoccupant MoveDIPSwitch5up.
Lights
Will Not
Turn OFF
manually
CallTechnicalServices
If lights will still not turn OFF, call Technical Services at 1-800-553-3879
5 Minutes
Auto*
*Self-Adjusts to
10 min. user
mode
Time Delay
DIP Switch
Activation PIR Sensitivity EcoMeterBathroom Relay SwapDaylighting
Relay 1Relay 2Relay 1 Relay 2
OverrideWalk-Through Mode
Default =
30 Minutes
15 Minutes
12
DIP Switch Legend
12
Disable
Enable
11
Disable
Enable
9
Disable
Enable
6
Disable
Enable
4
Auto
Manual
3
Auto
Manual
5
Full
50%
8
Disable
Enable
7
Enable
Disable
10
Normal
Swap
12345678910
11 12
EcoMeter
ON/OFF Buttons
1 & 2
PIR Lens
DIP Switches
Daylight
Sensor Level
Adjustment
Red (PIR)
Detection LED
11 and 12
12345678910
11 12
12
34567891011
1 and
2
12
AdjustmentsshouldbemadewiththeHVACsystemONsothattheinstallerwillbeabletodetecttheeffectofairowon
theoperationoftheONW-P-1001-DMV.Useonlyinsulatedtoolstomakeadjustments.
Immediatelyafterapplyingpowertothelightingcircuit,waitapproximatelytwominutesfortheswitchtopower-up
andstabilize.
Self-Adjust
Sensorisshippedinself-adjustmode.ThisappliestotimedelayandPIRsensitivity.InpreparationfortheInstallerTest,
thetimedelayissetto15seconds,afterthesensorisinstalled,poweredONandhasstabilized,theunitwilltime-out15
secondsafterthelastmotiondetected.CoverageandsensitivitycanbeconrmedbywatchingtheRed(PIR)indicatorLED
onthefrontofthesensor,whilemovingaroundtheroom.
Override
TheOverridesettingallowsthesensortooperateasaserviceswitchintheunlikelyeventoffailure.
1. MoveDIPSwitch8up.
2.ThepushbuttoncanbeusedtomanuallyturnlightsONorOFF.
Checkout and Adjustment
DIP Switch Settings
Installer Adjustments
Troubleshooting
Warranties and Limitation of Liability
  • Page 1 1
  • Page 2 2

Cooper Lighting NeoSwitch - 120/277/347V PIR/Dual Relay Wall Switch Sensor (Ground Required) Installation guide

Type
Installation guide

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI