Application Sheet
SpeedUp Wall Heating
Fibre reinforced plasterboard
1
2
3
4
1 Dry walling screws
2 SpeedUp panel, 30 mm
3 Danfoss composite pipe 16 x 2 mm
4 Fibre reinforced plasterboard, 12.5 mm
Technical Data SpeedUp wall heating dry construction
Wall covering 12.5 mm Fibre reinforced plasterboard or similar
Constructional thickness 42.5 mm Dimensions without unfinished wall
Thermal resistance R 0.86 m²K / W Thermal resistance value for SpeedUp panel
Pipe spacing 125-250 mm EZ = 125; CZ = 250;
Requirements and specialities Surface smoothness +/- 3 mm per 1 m. Observe building regulation requirements con-
cerning thermal insulation. Moisture condensation can occur and should be taken into
consideration when planning wall heating on outer walls and walls between heated and
unheated rooms.
Wall coverings Fermacel/fibre reinforced plasterboard: Thermal conductivity: 0.32 W/m²K; maximum
flow temperature 55°C; form board butt joint as a glued joint. Form wall attachment
with an elastic acrylic joint or joint filler on divider.
Construction Refering to EN 1264
Construction number 601