  • Hello! I am an AI chatbot trained to assist you with the Danfoss SpeedUp - Direct load User guide. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
Application sheet
SpeedUp
Parquet
Direct load
1
2
3
4
5
1 Parquet ≥ 14 mm
2 Sound insulation 2 mm
3 SpeedUp heat panel + FH composite pipe 30 mm
4 Support batten (30mm)
5 Additional insulation EPS 035 DEO 20 mm
6 SpeedUp perimeter insulation
7 If necessary moisture barrier
Floor nish ≥ 14 mm Parquet
Construction height ≥ 66 mm Height including parquet
Weight ~ 14 kg / m² Weight including parquet
Thermal resistance R 1,43 m²K / W The minimum thermal resistance requirement of DIN EN 1264 is
fullled.
Thermal transmission coecient U 0,63 W / m²K If the architectural design species better thermal insulation, this
must be taken into account.
Design load ≤ 2,0 kN / m²
Point load (≥ 20 cm²) ≤ 2,0 kN Sum point load ≤ design load; please notice special heavy ob-
jects (aquaria etc.)
Impact subsonic noise reduction NA dB
Application area
Residential spaces, hallways and attic spaces in residential buildings and hotel rooms.
Corresponds to categories A1, A2 and A3 of DIN 1055-3.
Oce spaces, hallways in oce buildings, medical oces, stations and spaces with
human occupancy, and commercial spaces with oor areas up to 50 m² in residential or
oce buildings. Corresponds to categories B1, D1 and D2 of DIN 1055-3.
Requirements & special features
A level, smooth and structurally sound surface is necessary for full surface contact with
the heating elements (elevated requirements according to DIN 18202 Table 3, row 4).
Structural sealing according to DIN 18195 must be placed beneath the oor panel in case
of structures facing the ground, and otherwise on the unnished oor. The R value must
be increased if the groundwater level is less than or equal to 5 m. A U value not exceed-
ing 0.5 W/m²K must be maintained in existing buildings and additions with areas up to
50 m². Supply / return panels and cut panels (insulation panels or SpeedUp panels) must
be glued to the substrate and to each other. If necessary, protect oorboards and prefab-
ricated parquet against moisture penetration from below (vapour barrier). Observe all
installation instructions and manufacturer’s instructions.
Additional insulation
20 mm EPS 035 DEO 200 kPa; existing buildings: 40 mm XPS 035 500 kPa
Construction
According to EnEV, EN 1264, DIN 1055, 18195 and 18202
Construction number 81
Technical Data Floors/ceilings facing unheated rooms or the ground
6
7
© Danfoss 11/2008
VA.CR.O1.02
Danfoss HES
/