Application sheet
SpeedUp
Carpet / tiles / parquet / laminate / synthetics
Liquid screed
1
2
3
4
5
1 Carpet / tiles / parquet
2 Liquid screed (≥ CAF F5) 35 mm
3 System foil
4 SpeedUp heat panel + FH composite pipe 30 mm
5 Support batten (30mm)*
6 Additional insulation EPS 035 DEO 20 mm
7 Basic perimeter insulation
8 If necessary moisture barrier
Floor nish NA mm Carpet / tiles / parquet / laminate / synthetics
Construction height 85 mm Height excluding oor nish
Weight ~ 74 kg / m² Weight excluding oor nish
Thermal resistance R 1,43 m²K / W The minimum thermal resistance requirement of DIN EN 1264 is
fullled.
Thermal transmission coecient U 0,63 W / m²K If the architectural design species better thermal insulation, this
must be taken into account.
Design load ≤ 2,0 kN / m²
Point load (≥ 20 cm²) ≤ 1,0 kN
Impact subsonic noise reduction NA dB
Application area
Residential spaces, hallways and attic spaces in residential buildings and hotel rooms.
Corresponds to categories A1, A2 and A3 of DIN 1055-3.
Requirements & special features
Structural sealing according to DIN 18195 must be placed beneath the oor panel in case
of structures facing the ground, and otherwise on the unnished oor. The R value must
be increased if the groundwater level is less than or equal to 5 m. A U value not exceed-
ing 0.5 W/m²K must be maintained in existing buildings and additions with areas up to
50 m². * Construction without a stabilising support batten is also possible. For CAF-F4
self-levelling screeds a screed thickness of 40 mm must be maintained. The screed thick-
nesses must be adjusted in case of higher design load or point load values. Observe all
installation instructions and manufacturer’s instructions.
Additional insulation
20 mm EPS 035 DEO; existing buildings: 40 mm
Construction
According to EnEV, EN 1264, DIN 1055, 18195, 18202 and 18560
Construction number 77
Technical Data Floors/ceilings facing unheated rooms or the ground
6
7
8
© Danfoss 11/2008
VA.CR.K1.02