Application sheet
SpeedUp
Massive wooden planks on battens
Direct load
1
2
3
4
5
1 Wooden planks ≤ 22 mm
2 SpeedUp heat panel + FH composite pipe 30 mm
3 Support batten (30mm)
4 Additional insulation EPS 035 DEO 20 mm
5 SpeedUp perimeter insulation
6 If necessary moisture barrier
Floor nish ≤ 22 mm Massive wooden planks or parquet
Construction height ≤ 72 mm Height including oor nish
Weight ~ 19 kg / m² Weight including oor nish
Thermal resistance R 1,43 m²K / W The minimum thermal resistance requirement of DIN EN 1264 is
fullled.
Thermal transmission coecient U 0,63 W / m²K If the architectural design species better thermal insulation, this
must be taken into account.
Design load ≤ 2,0 kN / m²
Point load (≥ 20 cm²) ≤ 2,0 kN Sum point load ≤ design load; please notice special heavy ob-
jects (aquaria etc.)
Impact subsonic noise reduction NA dB
Application area
Residential spaces, hallways and attic spaces in residential buildings and hotel rooms.
Corresponds to categories A1, A2 and A3 of DIN 1055-3. Oce spaces, hallways in oce
buildings, medical oces, stations and spaces with human occupancy, and commercial
spaces with oor areas up to 50 m² in residential or oce buildings. Corresponds to
categories B1, D1 and D2 of DIN 1055-3.
Requirements & special features
A level, smooth and structurally sound surface is necessary for full surface contact with
the heating elements (elevated requirements according to DIN 18202 Table 3, row 4).
Structural sealing according to DIN 18195 must be placed beneath the oor panel in case
of structures facing the ground, and otherwise on the unnished oor. The R value must
be increased if the groundwater level is less than or equal to 5 m. A U value not exceed-
ing 0.5 W/m²K must be maintained in existing buildings and additions with areas up
to 50 m². If necessary, protect oorboards and prefabricated parquet against moisture
penetration from below according to the manufacturer’s instructions (vapour barrier).
Observe all installation instructions and manufacturer’s instructions.
Additional insulation
20 mm EPS 035 DEO 200 kPa; existing buildings: 40 mm XPS 035 500 kPa
Construction
According to EnEV, EN 1264, DIN 1055, 18195 and 18202
Construction number 82
Technical Data Floors/ceilings facing unheated rooms or the ground
6
© Danfoss 11/2008
VA.CR.Q1.02