Danfoss SpeedUp - Direct load User guide

Type
User guide

Danfoss SpeedUp - Direct Load

With Danfoss SpeedUp - Direct load, you have purchased a high-quality heating system that is suitable for residential and commercial use. It consists of massive wooden planks on battens and is designed for direct load. The system is easy to install and can be used in a variety of applications, including:

  • Residential spaces, hallways, and attic spaces in residential buildings and hotel rooms
  • Office spaces, hallways in office buildings, medical offices, stations, and spaces with human occupancy
  • Commercial spaces with floor areas up to 50 m² in residential or office buildings

Danfoss SpeedUp - Direct Load

With Danfoss SpeedUp - Direct load, you have purchased a high-quality heating system that is suitable for residential and commercial use. It consists of massive wooden planks on battens and is designed for direct load. The system is easy to install and can be used in a variety of applications, including:

  • Residential spaces, hallways, and attic spaces in residential buildings and hotel rooms
  • Office spaces, hallways in office buildings, medical offices, stations, and spaces with human occupancy
  • Commercial spaces with floor areas up to 50 m² in residential or office buildings
Application sheet
SpeedUp
Massive wooden planks on battens
Direct load
1
2
3
4
5
1 Wooden planks ≤ 22 mm
2 SpeedUp heat panel + FH composite pipe 30 mm
3 Support batten (30mm)
4 Additional insulation EPS 035 DEO 20 mm
5 SpeedUp perimeter insulation
6 If necessary moisture barrier
Floor nish ≤ 22 mm Massive wooden planks or parquet
Construction height ≤ 72 mm Height including oor nish
Weight ~ 19 kg / m² Weight including oor nish
Thermal resistance R 1,43 m²K / W The minimum thermal resistance requirement of DIN EN 1264 is
fullled.
Thermal transmission coecient U 0,63 W / m²K If the architectural design species better thermal insulation, this
must be taken into account.
Design load ≤ 2,0 kN / m²
Point load (≥ 20 cm²) ≤ 2,0 kN Sum point load ≤ design load; please notice special heavy ob-
jects (aquaria etc.)
Impact subsonic noise reduction NA dB
Application area
Residential spaces, hallways and attic spaces in residential buildings and hotel rooms.
Corresponds to categories A1, A2 and A3 of DIN 1055-3. Oce spaces, hallways in oce
buildings, medical oces, stations and spaces with human occupancy, and commercial
spaces with oor areas up to 50 m² in residential or oce buildings. Corresponds to
categories B1, D1 and D2 of DIN 1055-3.
Requirements & special features
A level, smooth and structurally sound surface is necessary for full surface contact with
the heating elements (elevated requirements according to DIN 18202 Table 3, row 4).
Structural sealing according to DIN 18195 must be placed beneath the oor panel in case
of structures facing the ground, and otherwise on the unnished oor. The R value must
be increased if the groundwater level is less than or equal to 5 m. A U value not exceed-
ing 0.5 W/m²K must be maintained in existing buildings and additions with areas up
to 50 m². If necessary, protect oorboards and prefabricated parquet against moisture
penetration from below according to the manufacturer’s instructions (vapour barrier).
Observe all installation instructions and manufacturer’s instructions.
Additional insulation
20 mm EPS 035 DEO 200 kPa; existing buildings: 40 mm XPS 035 500 kPa
Construction
According to EnEV, EN 1264, DIN 1055, 18195 and 18202
Construction number 82
Technical Data Floors/ceilings facing unheated rooms or the ground
6
© Danfoss 11/2008
VA.CR.Q1.02
Danfoss HES
  • Page 1 1

Danfoss SpeedUp - Direct load User guide

Type
User guide

Danfoss SpeedUp - Direct Load

With Danfoss SpeedUp - Direct load, you have purchased a high-quality heating system that is suitable for residential and commercial use. It consists of massive wooden planks on battens and is designed for direct load. The system is easy to install and can be used in a variety of applications, including:

  • Residential spaces, hallways, and attic spaces in residential buildings and hotel rooms
  • Office spaces, hallways in office buildings, medical offices, stations, and spaces with human occupancy
  • Commercial spaces with floor areas up to 50 m² in residential or office buildings

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI