Troubleshooting
BC-HM VI.BA.P1.02 © Danfoss A/S 11
Swapping Addresses
Now, if – by a mistake during the procedure outlined above – the heat meter that
should be assigned to circuit I has been assigned to circuit II and vice versa, the
following service parameter solves the problem:
Param.
No.
Range
Default
value
Description
196 0, 1 0
When parameter 196 is set to 1, the M-bus addresses of two
connected heat meters are swapped. After addresses have
been swapped, parameter 196 is automatically reset to 0
4.2 Reading Measured Data
You display the data read by the ECL Comfort from the attached heat meter(s) by
reading parameter 110 for circuit I and II. When reading the parameter, you change
between circuit I and II by pressing
.
Param.
No.
Range
Default
value
Description
110 * 0
The actual flow or energy measurement. The unit depends on
the setting of parameter 115 (see page 8)
* Depends on the setting of parameter 115
5. Troubleshooting
5.1 What to Expect
After the ECA 84 M-bus module has been installed as described in chapter 3 and
set up as described in chapter 4, the measured flow or energy data should become
available in parameter 110 (circuit I and/or II), as described above. However, you
must take into consideration that:
• The ECA 84 M-bus module exchanges data with the ECL Comfort’s CPU once
every 30 seconds
• The process of detecting addresses on the M-bus (see page 10) may take up to
10 minutes if both communication channels are set up to M-bus.
When pulse communication is used, you may experience discrepancies between the
data displayed by the heat meter and the data displayed in parameter 110 by the
ECL Comfort when the flow or energy consumption is low, that is, is much lower
than the reference value. This phenomenon is due to the method used by the ECL
Comfort to calculate the measurement time for pulse communication.
Bear in mind, therefore, that if the data measured by ECL Comfort deviates from
the values reported by the heat meter at low flow/energy values, this will not influ-
ence the function of the flow/energy limiting. The ECL Comfort measures cor-
rectly in the interval surrounding the reference value.