The Danfoss M-Bus module allows the ECL Comfort to read measured values of flow or energy consumption from connected heat meters. The ECL Comfort can use the measured data to perform outdoor temperature dependent flow limiting or energy limiting. The heat meters supported by the ECL Comfort are listed in the following table. The module enables the ECL Comfort to communicate with one or two heat meters on the bus at 300 b/s. It can take data input via two channels named I and II. These can be configured as M-bus, pulse, or not used.
The Danfoss M-Bus module allows the ECL Comfort to read measured values of flow or energy consumption from connected heat meters. The ECL Comfort can use the measured data to perform outdoor temperature dependent flow limiting or energy limiting. The heat meters supported by the ECL Comfort are listed in the following table. The module enables the ECL Comfort to communicate with one or two heat meters on the bus at 300 b/s. It can take data input via two channels named I and II. These can be configured as M-bus, pulse, or not used.
The Danfoss M-Bus module allows the ECL Comfort to read measured values of flow or energy consumption from connected heat meters. The ECL Comfort can use the measured data to perform outdoor temperature dependent flow limiting or energy limiting. The heat meters supported by the ECL Comfort are listed in the following table. The module enables the ECL Comfort to communicate with one or two heat meters on the bus at 300 b/s. It can take data input via two channels named I and II. These can be configured as M-bus, pulse, or not used.
Ask a question and I''ll find the answer in the document
Finding information in a document is now easier with AI