Danfoss ECA 82, LonWorks in the ECL Comfort Operating instructions

Type
Operating instructions
DH-SMT/DK VI.7F.C5.02 © Danfoss 12/2007 DH-SMT/DK VI.7F.C5.02 © Danfoss 12/2007
ECA 82
LONworks in the ECL Comfort 200/300/301
Instructions
VI.7F.C5.02 © Danfoss 12/2007 DH-SMT/DK
Instructions ECA 82 LONworks in the ECL Comfort 200/300/301
Table of Contents
1 Introduction 1
1.1 Scope ..............................................................................................................................................................................................................................................1
1.2 About the implementation in the LONworks protocol ...............................................................................................................................................
1
1.3 General information ..................................................................................................................................................................................................................
1
1.4 ECA 82 compatibility with other optional cards .............................................................................................................................................................
1
1.5 ECA 82 compatibility with the ECL Comfort controller and applications .............................................................................................................
1
2 Getting started 2
2.1 Installation ....................................................................................................................................................................................................................................2
2.2 Starting up ....................................................................................................................................................................................................................................
3
2.3 Service pin and neuron ID ......................................................................................................................................................................................................
3
2.4 XIF le and program ID ............................................................................................................................................................................................................
4
3 Node object 5
3.1 Mandatory network variables ...............................................................................................................................................................................................5
3.1.1 Network variable 1. Node request: Input ..........................................................................................................................................................................
5
3.1.2 Network variable 3. Setting time and date: Input ..........................................................................................................................................................
6
3.1.3 Network variable 2. Node status: Output .........................................................................................................................................................................
7
3.1.4 Network variable 4. Alarm: Output ......................................................................................................................................................................................
7
4 Weather compensator object 9
4.1 Network variables 5. & 11. Setpoints, circuit I & II: Input ............................................................................................................................................10
4.2 Network variable 8. Setpoints, hot water setting: Input ...........................................................................................................................................
10
4.3 Network variables 15. & 16. & 59. Control of valves and mode: Input ..................................................................................................................
11
4.4 Network variable 21. Control of pumps: Input ..............................................................................................................................................................
11
4.5 Network variable 55. Control of the week plan ............................................................................................................................................................
12
4.6 Network variables 34. & 36. Actual power input from node in the network. Input ........................................................................................
13
4.7 Network variables 36. & 37. Actual ow input from a node in the network. Input .........................................................................................
14
4.8 Handling energy and ow input from the network ....................................................................................................................................................
14
4.8.1 Setting time constants ...........................................................................................................................................................................................................
14
4.8.2 Setting the ow or energy reference ................................................................................................................................................................................
15
4.9 Network variable 53. Outdoor temperature input ......................................................................................................................................................
15
4.10 Network variable 54. Outdoor temperature input ......................................................................................................................................................
16
4.11 General handling of outdoor temperature input ........................................................................................................................................................
16
4.12 Network variables 6. 7. & 17.-20. & 46.–49. Temperature sensors 1-10: Output .................................................................................................
16
4.13 Network variables 9. & 12. Setpoint concerning circuit I & II: Output ...................................................................................................................
17
4.14 Network variable 10. Setpoints concerning hotwater setting: Output ...............................................................................................................
17
4.15 Network variables 13. & 14. & 61. Status of valves, optimizer status and relative ...........................................................................................
18
humidity ......................................................................................................................................................................................................................................
18
4.16 Network variable 22. Reading o time and date: Output .........................................................................................................................................
19
4.17 Network variable 33. Pump status ....................................................................................................................................................................................
19
4.18 Network variable 56. Reporting week plan in ECL Comfort. Output
....................................................................................................................19
4.19 Network variables 57. & 58. & 60. Controller mode status, circuit I & II & III. Output ......................................................................................
20
4.20 Network variables 42. & 43. Actual power delivered from pulse module. Output .........................................................................................
20
4.21 Network variables 44. & 45. Actual ow delivered from pulse module. Output .............................................................................................
20
4.22 Network variables 27. – 30. Sensor references 3-6. Output ......................................................................................................................................
21
DH-SMT/DK VI.7F.C5.02 © Danfoss 12/2007
Instructions ECA 82 LONworks in the ECL Comfort 200/300/301
5 Manufacturer-dened section 22
5.1 Network variables 23. & 24. Analog outputs 1 & 2: Input ......................................................................................................................................... 22
5.2 Network variables 25. & 26. Analog inputs 1 & 2: Output ........................................................................................................................................
23
5.3 Network variables 19. & 20. Parameter command and response .........................................................................................................................
23
5.3.1 Learn eld ..................................................................................................................................................................................................................................
23
5.3.2 Selector eld ..............................................................................................................................................................................................................................
24
5.3.3 Value eld ....................................................................................................................................................................................................................................
24
5.3.4 Parameters, grey side of the ECL card, circuit I .............................................................................................................................................................
26
5.3.5 Parameters, yellow side of the ECL card, circuit I. .......................................................................................................................................................
28
5.3.6 Parameters, grey side of the ECL card, circuit II ...........................................................................................................................................................
29
5.3.7 Parameters, yellow side of the ECL card, circuit II .......................................................................................................................................................
30
5.3.8 Parameters, gray side of the ECL card, circuit III ...........................................................................................................................................................
31
5.3.9 ECL Comfort status information .........................................................................................................................................................................................
31
5.3.9.1 Selector 250 details .................................................................................................................................................................................................................
31
5.3.9.2 Selector 251 details .................................................................................................................................................................................................................
31
5.3.9.3 Selector 252 details .................................................................................................................................................................................................................
31
5.3.10 ECA 82 set-up and details .....................................................................................................................................................................................................
32
5.3.10.1 Software version in ECA 82
...................................................................................................................................................................................................32
5.3.10.2 SendHeartBeat ..........................................................................................................................................................................................................................32
5.3.10.3 Voltage update ..........................................................................................................................................................................................................................32
5.3.10.4 ECL checks for adjustments .................................................................................................................................................................................................32
5.3.10.5
Application loaded in the ECL Comfort ...........................................................................................................................................................................32
5.3.11 Alarm limit conguration ......................................................................................................................................................................................................
32
5.3.12 Alarm code readout ................................................................................................................................................................................................................
33
5.3.13 Accumulated energy or ow preload ...............................................................................................................................................................................
33
6 Thumb rules for network design in heating systems 35
6.1 Considerations before implementing communication .............................................................................................................................................35
6.1.1 What are the basic needs for information ......................................................................................................................................................................
35
6.1.2 What is the nal number of nodes in the network .....................................................................................................................................................
36
6.1.2.1 Parallel network .......................................................................................................................................................................................................................
36
6.1.2.2 Backbone network ..................................................................................................................................................................................................................
36
6.1.3 Bandwidth considerations ...................................................................................................................................................................................................
36
6.1.3.1 Total number of controllers in network ..........................................................................................................................................................................
38
6.2 Update of SNVT from ECL Comfort ...................................................................................................................................................................................
39
6.2.1 Minimize copy of data on the network ............................................................................................................................................................................
39
6.2.2 Note down the neuron ID .....................................................................................................................................................................................................
39
DH-SMT/DK VI.7F.C5.02 © Danfoss 12/2007 1
Instructions ECA 82 LONworks in the ECL Comfort 200/300/301
1 Introduction
1.1 Scope
This ECA 82 option for ECL Comfort is based on Echelons® LONworks®. The ECA 82 can be used in ECL Comfort
200 and 300-301 series. In the remaining part of these instructions, the type designation ECL Comfort will be
used.
1.2 About the implementation in the LONworks protocol
The following instruction describes the parameters that can be communicated between a LONworks network
and ECL Comfort. The build-up of the physical network is not described. For further information see Echelons
homepage: http://www.echelon.com/.
The instruction is divided into three main sections:
1. The LonMark node object is used to the extent that functions are supported in ECL Comfort. The
functions from the node object that are supported in ECL Comfort are described in “Node object.
2. The basic parameters behind weather compensation are described separately in the section on the
weather compensator object.
3. Parameters that are special for ECL Comfort are described separately in the manufacture-dened
section.
1.3 General information
1. The possibilities for communication depend on the application loaded in the ECL Comfort. This ECA
82 is designed to t all applications card. Hardware conguration settings and future parameters
might not be supported.
2. Only one kind of communication can be used in the ECL Comfort. It is not possible to run RS232
together with ECA 82 communication.
1.4 ECA 82 compatibility with other optional cards
ECA 71 ECA 73 ECA 80 ECA 81 ECA 83 ECA 84 ECA 85 ECA 86 ECA 87 ECA 88
No No Yes No Yes No Yes Yes No Yes
1.5 ECA 82 compatibility with the ECL Comfort controller and applications
ECA 82 is fully compatible with ECL Comfort controllers as of version 1.11. Older ECL Comfort controllers versions
are also compatible with ECA 82 but in some cases with limited functionality.
2 VI.7F.C5.02 © Danfoss 12/2007 DH-SMT/DK
Instructions ECA 82 LONworks in the ECL Comfort 200/300/301
2 Getting started
The ECA 82 can be used together with ECL Comfort 200, 300 and 301. It is not possible to use the ECA 82
together with ECL Comfort 100.
Further information on the operation of ECL Comfort is comprised by the instructions supplied with the ECL
Card.
2.1 Installation
Step 1:
Dismount cover plate B on the back of the ECL Comfort using a small slice cutter nipper.
Step 2:
Mount ECA 82 in the slides and press it gently into the connector on the ECL Comfort print board.
Step 3:
Mount the new cover plate B, which is delivered with the option card.
DH-SMT/DK VI.7F.C5.02 © Danfoss 12/2007 3
Instructions ECA 82 LONworks in the ECL Comfort 200/300/301
Pin connection:
1: LON data 1, left side pin of the connector.
2: Middle pin of the connector. Do not use!
3: LON data 2, right side pin of the connector.
The FTT10 transceiver is based on a balanced bus. LON data 1 and 2 can be reversed.
2.2 Starting up
When starting up the ECA 82, a period of about 30 seconds will elapse during which the database from the
controller will be copied. During this starting up period it is not possible to come into contact with the ECA 82,
neither from ECL Comfort nor from the network. The starting-up period will occur on the reset/power up of the
controller/ECA 82, and when an application change is made in ECL Comfort.
After starting up, the following parameters can be activated via the ECL Comfort user interface:
Line 196 in circuit I is the service pin.
Line 197 in circuit I is the ECA 82 reset.
Lines 196 and 197 can be can accessed by scrolling down through the lines on the installer page (grey page) with
the arrow down key.
The lines can be activated/deactivated with the +/- keys (see the instructions for the application card).
At wink command, the display will ash until any key on ECL Comfort is pressed.
2.3 Service pin and neuron ID
The ECA 82 does not have any hardware service pin. The service pin is activated from the ECA 82 software
application. This means that it is not possible to send any service pin if the ECA 82 is put in non-congured
mode. If the ECA 82 anyhow is set in non-congured mode, the unique neuron ID number is required to set
the ECA 82 back in congured mode. If the ECA 82 is decommissioned or non-congured without having the
neuron ID, the ECA 82 is damaged! The system integrator is responsible for making a note of the neuron ID.
4 VI.7F.C5.02 © Danfoss 12/2007 DH-SMT/DK
Instructions ECA 82 LONworks in the ECL Comfort 200/300/301
2.4 XIF le and program ID
The XIF le can be found on the internet.
Before using a XIF le, check the software version in the ECA 82. The software version can be read directly on
the memory IC on the ECA 82 card, see Figure 1 and Table 1. The Software version can also be found using the
network in parameter nviParamCmd/nvoParamResp, selector 1000, see 5.3.10.1 Software version in ECA 82.
When using the ECA 82, a XIF le which ts the software version is required.
Figure 1: Turn the ECA 82 to see the software version (the backside of the module)
ECA 82 software version Text on IC label XIF le name Program ID
1.4 087B1564 VER 1.4 ECL14.XIF ECL
1.5 087B1564 VER 1.5 ECL15.XIF ECL
1.6 087B1564 VER 1.6 ECL16.XIF ECL
1.9 087B1564 VER 1.9 ECL19.XIF ECL
2.11 087B1564 VER 2.11 ECL211.XIF ECL
3.0 087B1564 VER 3.0 ECA82 v30.XIF ECL 30
Table 1: ECA 82 software versions and XIF le
The XIF le can be loaded directly from the ECA 82 via the LON network for example by using the LONMaker for
Windows.
The XIF les can also be downloaded from the internet: http://heating.danfoss.com.
DH-SMT/DK VI.7F.C5.02 © Danfoss 12/2007 5
Instructions ECA 82 LONworks in the ECL Comfort 200/300/301
3 Node object
The node object is used for controlling and establishing the status of the node. It is thus possible to ask for and
receive the status of the actual condition of the node.
Mandatory Nework variables
Optional network variables
Input
Network
Variables
Output
Network
Node Object
Type #0
nv 2
nvoStatus
SNVT_obj_status
nv 1
nviRequest
SNVT_obj_request
nv 4
nvoAlarm
SNVT_alarm
nv 3
nviTimeSet
SNVT_time_stamp
Figure 2: Node object
NV NR Name SNVT Type
(SNVT Index)
Class Description
1 NviRequest SNVT_obj_request Ram Request object status
3 NviTimeSet SNVT_time_stamp Ram Set time and date
Table 2: SNVT input
NV NR Name SNVT Type
(SNVT Index)
Class Description
2 NvoStatus SNVT_obj_status Ram Status of node
4 NvoAlarm SNVT_Alarm Ram Alarm reporting
Table 3: SNVT output
3.1 Mandatory network variables
3.1.1 Network variable 1. Node request: Input
network input SNVT_obj_request nviRequest;
6 VI.7F.C5.02 © Danfoss 12/2007 DH-SMT/DK
Instructions ECA 82 LONworks in the ECL Comfort 200/300/301
Valid range
The following parameters are supported:
0: RQ_NORMAL: Set controller in normal mode after override (manual mode).
The following functions are only active in manual mode.
SNVT_setting nviValve_1 & 2. (Valve control)
SNVT_state nviControl. (Pump control)
SNVT_object_request nviRequest.RQ_OVERRIDE.
SNVT_object_request nviRequest.RQ_RMV_OVERRIDE.
SNVT_volt nviAnalogOut_1 & 2.
Returning to normal from manual mode set circuit I and II in automatic mode.
1: RQ_DISABLED: Not supported.
2: RQ_UPDATE_STATUS. Update object status: nvo_obj_status and nvoTime.
3: RQ_SELF_TEST: Not supported.
4: RQ_UPDATE_ALARM. Sends actual status on nvoAlarm to the network via SNVT_alarm (alarm on/o).
5: RQ_REPORT_MASK: Not supported.
6: RQ_OVERRIDE. Override from comfort to setback and vice versa. ¹)
7: RQ_ENABLE: Not supported.
8: RQ_RMV_OVERRIDE. Delete override between comfort and setback. Return to condition before override.
9: RQ_CLEAR_STATUS: Delete all bits in SNVT_obj_status nvoStatus.
10: RQ_CLEAR_ALARM: Delete alarms entered in nvoAlarm SNVT_alarm
11: RQ_ALARM_NOTIFY_ENABLED: Enable alarm reporting in nvoAlarm.
12: RQ_ALARM_NOTIFY_DISABLED: Disable alarm reporting in nvoAlarm.
13: RQ_MANUAL_CTRL. Set controller in manual mode in all circuits. ²)
14: RQ_REMOTE_CTRL: Not supported.
15: RQ_PROGRAM: Not supported.
¹) Can only be activated if the controller is set in manual mode by the network or controller user interface.
²) If the controller is parked in line B at the user’s side (yellow), the valve and pump status is overridden by the controller, in order to
give the locally positioned user a possibility manually to override the controller user interface. The override from the controller
user interface can be avoided in ECL Comfort 300 by removing the ECL card from the controller. Without the ECL card the controller
will lock the keyboard after 5 minutes. Line B on the users side is designed to secure that a manual control can be carried out
locally directly without distortions from the network.
3.1.2 Network variable 3. Setting time and date: Input
network input SNVT_time_stamp nviTimeset;
The actual time and date entered in the ECL can be set here.
Valid range
Year 1996-2026
Month 1-12
Day 1-31 ¹)
Hour 0-23
Minute 0-59
¹) The number of days depends on the month in question. If an attempt is made to set more days than in the month, the request
will be rejected and nvoAlarm SNVT_ALARM is updated (the alarm function has to be enabled to get an alarm, see 3.1.1).
DH-SMT/DK VI.7F.C5.02 © Danfoss 12/2007 7
Instructions ECA 82 LONworks in the ECL Comfort 200/300/301
3.1.3 Network variable 2. Node status: Output
network output SNVT_obj_status nvoStatus;
SNVT uses this input to report on the node status.
The following points are supported:
Over_range: Set if an input value from the network is higher than the
max permissible value.
Under_range: Set if an input value from the network is under the min
permissible value.
Manual_control: Set if the controller has been set in manual mode from the network, or if the
controller is set in manual mode from ECL Comfort user interface.
In_alarm: Set if an alarm has been set.
In_override: Set if the controller overrides between comfort/setback from the network.
alarm_notify_disabled: Alarm reporting in nvoAlarm disabled.
3.1.4 Network variable 4. Alarm: Output
network output SNVT_Alarm nvoAlarm;
The possibilities for alarm reporting are:
Input value out of range alarm.
Alarm on all physical sensors
Alarm sensor - reference 2-8.
Alarm on relative humidity level.
Bit reporting of 32 alarm conditions.
Indication of sensor - reference alarm on time:0 min, 10 min, 30 min and 60 min
Time and date for latest alarm occurrence.
History buer with the latest 4 occurred SNVT alarm indexes.
The alarm function is enabled from nviRequest.RQ_ALARM_NOTIFY_ENABLE and disabled from nviRequest.
RQ_ALARM_NOTIFY_DISABLE
All alarm levels are congured in 5.3.11 Alarm limit conguration
If an illegal date or year is entered via nviTimeSet SNVT_time_stamp, an alarm type 1 will be activated and the
year or day will show the illegal value.
Alarm type:
Value Identier Notes
0 AL_NO_CONDITION No alarm condition present
1 AL_ALM_CONDITION Invalid value set in nviTimeset
9 AL_LOW_LMT_ALM_1 Alarm low limit alarm 1: Attempt to set parameter under legal value
10 AL_LOW_LMT_ALM_2 Alarm low limit alarm 2: Value under congured level has expired
11 AL_HIGH_LMT_ALM_1 Alarm high limits alarm 1: Attempt to set parameter higher than legal value
12 AL_HIGH_LMT_ALM_2 Alarm high limits alarm 2: Value higher than congured level has expired
0xFF AL_NUL Value not available
8 VI.7F.C5.02 © Danfoss 12/2007 DH-SMT/DK
Instructions ECA 82 LONworks in the ECL Comfort 200/300/301
Priority level:
Value Identier Notes
0 PR_LEVEL_0 Lowest alarm priority level. Alarm reported on sensor - Reference 2-8 value
1 PR_LEVEL_1 Alarm reports sensor - reference 2-8 value has been active for 10 minutes
2 PR_LEVEL_2 Alarm reports sensor - reference 2-8 value has been active for 30 minutes
3 PR_LEVEL_3 Highest alarm priority level. Alarm reports sensor - reference 2-8 value has
been active for 60 minutes
0x PR_NULL No alarms present on sensor - reference 2-8
index_to_SNVT The SNVT index for the latest expired alarm is presented.
Value[4]
The value eld is used for alarm reporting. Each alarm status is represented by 1 bit. 1 means alarm on,
0 means alarm o. 9 alarms can be reported the structure for decoding. The alarm report can be read in Table 4 -
Table 6.
nvoAlarm.value[0] bit nr Alarm status at Alarm limit congured in selector
0 Temperature sensor 1 1018
1 Temperature sensor 2 1019
2 Temperature sensor 3 1020
3 Temperature sensor 4 1021
4 Temperature sensor 5 1022
5 Temperature sensor 6 1023
6 Temperature sensor 7 (ECA 86) 1024
7 Temperature sensor 8 (ECA 86) 1025
Table 4: nvoAlarm.value [0]
nvoAlarm.value[0] bit nr Alarm status at Alarm limit congured in selector
0 Temperature sensor 9 (ECA 86) 1026
1 Temperature sensor 10 (ECA 86) 1027
2 Sensor 2 - reference 2 1028
3 Sensor 3 - reference 3 1029
4 Sensor 4 - reference 4 1030
5 Sensor 5 - reference 5 1031
6 Sensor 6 - reference 6 1032
7 Sensor 7 - reference 7 (ECA 86) 1033
Table 5: nvoAlarm.value [1]
nvoAlarm.value[2] bit nr Alarm status at Alarm limit congured in
0 Sensor 8 - reference 8 (ECA 86) Selector 1034
1 Relative humidity 1 (ECA 62) Selector 1035
2 Relative humidity 2 (ECA 62) Selector 1036
Table 6: nvoAlarm.value [2]
year, month, day, hour, minute:
The time for the latest alarm is reported. The time is determined by the ECL Comfort clock.
alarm_limit[4]
This is a 4 value FIFO buer that indicates the latest 4 present alarms, which have an SNVT index.
Transmission
Generating alarms in ECA 82:
Sensor 1-6: 2 * SendHeartBeat. Default 10 sec.
Sensor - reference 2-6: 4 * SendHeartBeat. Default 20 sec.
Sensor 6-10 and sensor - reference 7 and 8 (ECA 86):
8 * SendHeartBeat. Default 40 sec.
DH-SMT/DK VI.7F.C5.02 © Danfoss 12/2007 9
Instructions ECA 82 LONworks in the ECL Comfort 200/300/301
4 Weather compensator object
Here the parameters necessary to provide weather compensation are described. The values involved are divided
into mandatory network variables and optional network variables.
5
nviTSetptRoom_1
SNVT_temp_setpt
15, 16,
59
nviValve_1 & 2 & 3
SNVT_setting
Input
Network
Variables
Output
Network
Variables
ECL Comfort
Weather compensator object
22
nvoTime
SNVT_time_stamp
11
nviTSetptRoom_2
SNVT_temp_setpt
9
nvoTSetptRoom_1
SNVT_temp_setpt
17-20
nvoSensorNr_3 - 6
SNVT_temp
8
nviTSetptHW
SNVT_temp_setpt
10
nvoTSetptHW
SNVT_temp_setpt
6, 7
nvoSensorNr_1 - 2
SNVT_temp
12
nvoSetptRoom_2
SNVT_temp_setpt
21
nviControl
SNVT_state
56
nvoWeekplan
SNVT_str_asc
33
nvoControl
SNVT_state
55
nviWeekplan
SNVT_str_asc
34, 36
nviActPower_1 & 2
SNVT_power_f
13, 14,
61
nvoValve_1 & 2 & 3
SNVT_setting
35, 37
nviActFlow_1 & 2
SNVT_flow_f
42, 43
nvoActPower_1 & 2
SNVT_power_f
44, 45
nvoActFlow_1 & 2
SNVT_flow_f
46-49
nvoSensorNr_7 - 10
SNVT_temp
27-30
nvoRef_Nr_3 - 6
SNVT_temp
53
nviOutdoortemp
SNVT_temp
54
nviOutdoortemp_p
SNVT_temp_p
57,
58, 60
nvoMode_1 & 2 & 3
SNVT_hvac_mode
Figure 3: Object details
NV NR (index) Name SNVT Type Description
5 nviSetptRoom_1 SNVT_temp_setpt Setpoints concerning circuit I
8 nviSetptHW SNVT_temp_setpt Hot water setpoint.
11 nviSetptRoom_2 SNVT_temp_setpt Setpoints concerning circuit II
15, 16, 59 nviValve_1 & 2 & 3 SNVT_setting Control of valves (triacs)
21 nviControl SNVT_state Control of pumps (relays)
55 nviWeekplan SNVT_str_asc Setting of week plan all circuits
34, 36 nviActPower_1 & 2 SNVT_power_f Power input from LON device (heat meter).
35, 37 nviActFlow_1 & 2 SNVT_ow_f Flow input from LON device (ow meter).
53 nviOutdoortemp SNVT_temp Outdoor temperature input from LON network.
54 nviOutdoortemp_p SNVT_temp_p Outdoor temperature input from LON network.
Table 7: SNVT input
10 VI.7F.C5.02 © Danfoss 12/2007 DH-SMT/DK
Instructions ECA 82 LONworks in the ECL Comfort 200/300/301
NV NR
(index)
Name SNVT Type Send Heart
Beat
Description
6, 7 nvoSensorNr_1–2 SNVT_temp *2 Sensor values
9 nvoTSetptRoom_1 SNVT_temp_setpt No Setpoints, circuit I
10 nvoTSetptHW SNVT_temp_setpt No Setpoints, hot water.
12 nvoTSetptRoom_2 SNVT_temp_setpt No Setpoints, circuit II.
13, 14, 61 nvoValve_1 & 2 & 3 SNVT_setting 5 sec Status of valves up/down/stopped.
17-20 nvoSensorNr_36 SNVT_temp *2 Sensor values 3-6.
22 nvoTime SNVT_time_stamp *8 Time and date set in ECL Comfort
33 nvoControl SNVT_state 5 sec Status of pumps (relays).
56 nvoWeekplan SNVT_str_asc No Week plan setting, all circuits.
57, 58, 60 nvoMode_1 & 2 & 3 SNVT_hvac_mode 5 sec Controller mode, circuit I & II
42, 43 nvoActPower_1& 2 SNVT_power_f *8 Actual power
44, 45 nvoActFlow_1 & 2 SNVT_ow_f *8 Actual ow
46-49 nvoSensorNr_7-10 SNVT_temp *8 Sensor values from ECA 86
27-30 nvoRef_Nr_3-6 SNVT_temp *4 References for sensor 3-6.
Table 8: SNVT output details
The SendHeartBeat value can be adjusted in 5.3.10.2, page 32.
4.1 Network variables 5. & 11. Setpoints, circuit I & II: Input
network input SNVT_temp_setpt nviTSetptRoom_1;
network input SNVT_temp_setpt nviTSetptRoom_2;
Field denitions
Field Parameter Valid Range Resolution
occupied_cool Proportional band 1.00 .. 250.00 K 1.00
standby_cool Parallel displacement -9.00 .. 9.00 K 1.00
unoccupied_cool Heating cut-out 10.00 .. 30.00
o
C 1.00
occupied_heat Setpoint comfort period 10.00 .. 30.00
o
C 1.00
standby_heat Heat curve 0.20 .. 3.40 0.10
unoccupied_heat Setpoint setback period 10.00 .. 30.00
o
C 1.00
Validation of data
If input is set to a value outside the valid area, the setting is ignored in ECL Comfort and nvoTSetptRoom_1 or 2.
The error is reported in nvoStatus.under_range / over_range.
Default value
Default value set in the SNVT: All elds = 0 at start-up.
4.2 Network variable 8. Setpoints, hot water setting: Input
network input SNVT_temp_setpt nviTSetptHW;
DH-SMT/DK VI.7F.C5.02 © Danfoss 12/2007 11
Instructions ECA 82 LONworks in the ECL Comfort 200/300/301
Field denitions
Field Parameter Valid Range Resolution
occupied_cool Hot water temp. di. 1.00 .. 250.00
o
C 1.00
standby_cool Charging temp. - relative 1.00 .. 30.00 K 1.00
unoccupied_cool Dierence 1 - cut-out temp. 1.00 .. 30.00 K 1.00
occupied_heat Setpoint comfort period 10.00 .. 110.00
o
C 1.00
standby_heat Dierence 2 - cut-in temp. 1.00 .. 30.00 K 1.00
unoccupied_heat Setpoint setback period 10.00 .. 110.00
o
C 1.00
The proportional band of the hot water is set in network input SNVT_temp_setpt nviTSetptRoom_2, occupied_
cool.
Default value
Default value set in the SNVT: All elds = 0 at start-up.
4.3 Network variables 15. & 16. & 59. Control of valves and mode: Input
network input SNVT_setting nviValve_1;
network input SNVT_setting nviValve_2;
network input SNVT_setting nviValve_3;
The valve and controller mode can be controlled by these.
nviValve_1 control valve 1 (triac 1 and 2) and the controller mode circuit I.
nviValve_2 control valve 2 (triac 3 and 4) and the controller mode circuit II.
nviValve_3 controller mode circuit II.
Function:
0 SET OFF => Setback mode
1 SET ON => Comfort mode
2 SET DOWN => Valve down
3 SET UP => Valve up
4 SET STOP => Stop valve
5 SET STATE => Automatic mode
6 SET NUL => Standby mode
Setting: Not used
Rotation: Not used
The valve can only be controlled if the controller is in manual mode.
Manual mode (for all circuits) can be entered in nviRequest, see 3.1.1.1. Node request: Input.
4.4 Network variable 21. Control of pumps: Input
Network input SNVT_state nviControl;
Pumps (relay) can be controlled by this input.
Valid range
For all values: 1 = relay in, no connection, 0 = relay out, connection.
12 VI.7F.C5.02 © Danfoss 12/2007 DH-SMT/DK
Instructions ECA 82 LONworks in the ECL Comfort 200/300/301
Bit 0: Standard relay 1
Bit 1: Standard relay 2
Bit 2: Standard relay 3
Other values are not supported.
Relays placed on optional cards (ECA 80 & ECA 86) cannot be controlled from the ECA 82. The application in ECL
Comfort always control optional relays.
The pumps can only be controlled if the controller is in manual mode.
Manual mode (for all circuits) can be entered in nviRequest, see 3.1.1.1. Node request: Input page 9 or directly at the ECL Comfort.
In some applications the ECL Comfort overwrites the specied setting from the network. In sequence controllers (C75)
non-valid relay combinations are overwritten by the ECL Comfort. Do not use this override function in the applications F05 and
F06.
4.5 Network variable 55. Control of the week plan
network input SNVT_str_asc nviWeekplan;
A new week plan can be set and the actual week plan already set in the controller can be requested. Request
status of the week plan already set in controller for readout in nvoWeekplan.
Field ascii[0] - ascii[29] must contain the value 0x00;
Field ascii[30] must contain an value indicating which week plan to report.
Field ascii[30] value Week plan area
0x10 Week days in circuit I
0x11 Weekend in circuit I
0x20 Week days in circuit II
0x21 Weekend in circuit II and all days circuit III
Table 9: Request week plan setting
The week plan is divided into ½ hour intervals. The week plan can contain a maximum of 3 periods a day. Each
eld ascii[0] - [29] is a char build of 8 bit. Each of these bits represent ½ hour in the week plan. The exact position
can be found using Table 10.
DH-SMT/DK VI.7F.C5.02 © Danfoss 12/2007 13
Instructions ECA 82 LONworks in the ECL Comfort 200/300/301
Field ascii[30] = 0x10 or 0x20 ascii[30] = 0x11 Ascii[30] = 0x21
ascii[0] Monday 0.00-3.30 Saturday 0.00-3.30 Saturday 0.00-3.30
ascii[1] Monday 4.00-7.30 Saturday 4.00-7.30 Saturday 4.00-7.30
ascii[2] Monday 8.00-11.30 Saturday 8.00-11.30 Saturday 8.00-11.30
ascii[3] Monday 12.00-15.30 Saturday 12.00-15.30 Saturday 12.00-15.30
ascii[4] Monday 16.00-19.30 Saturday 16.00-19.30 Saturday 16.00-19.30
ascii[5] Monday 20.00-23.30 Saturday 20.00-23.30 Saturday 20.00-23.30
ascii[6] Tuesday 0.00-3.30 Sunday 0.00-3.30 Sunday 0.00-3.30
ascii[7] Tuesday 4.00-7.30 Sunday 4.00-7.30 Sunday 4.00-7.30
ascii[8] Tuesday 8.00-11.30 Sunday 8.00-11.30 Sunday 8.00-11.30
ascii[9] Tuesday 12.00-15.30 Sunday 12.00-15.30 Sunday 12.00-15.30
ascii[10] Tuesday 16.00-19.30 Sunday 16.00-19.30 Sunday 16.00-19.30
ascii[11] Tuesday 20.00-23.30 Sunday 20.00-23.30 Sunday 20.00-23.30
ascii[12] Wednesday 0.00-3.30 All days 0.00-3.30, circuit III
ascii[13] Wednesday 4.00-7.30 All days 4.00-7.30, circuit III
ascii[14] Wednesday 8.00-11.30 All days 8.00-11.30, circuit III
ascii[15] Wednesday 12.00-15.30 All days12.00-15.30, circuit III
ascii[16] Wednesday 16.00-19.30 All days 16.00-19.30, circuit III
ascii[17] Wednesday 20.00-23.30 All days 20.00-23.30, circuit III
ascii[18] Thursday 0.00-3.30
ascii[19] Thursday 4.00-7.30
ascii[20] Thursday 8.00-11.30
ascii[21] Thursday 12.00-15.30
ascii[22] Thursday 16.00-19.30
ascii[23] Thursday 20.00-23.30
ascii[24] Friday 0.00-3.30
ascii[25] Friday 4.00-7.30
ascii[26] Friday 8.00-11.30
ascii[27] Friday 12.00-15.30
ascii[28] Friday 16.00-19.30
ascii[29] Friday 20.00-23.30
ascii[30] Information about the circuit for which the data apply, see Table 9 for decoding.
Table 10: Week day decoding
Error codes are reported in nvoWeekplan see 4.18 page 27.
Error causes: No value set in ascii[30] or too many periods set in one day.
4.6 Network variables 34. & 36. Actual power input from node in the network. Input
network input SNVT_power_f nviActPower_1;
network input SNVT_power_f nviActPower_2;
Input unit = Watt.
Valid input range 0 .. 2,999 * 10
12
watt. (Max value in the ECL Comfort display).
Actual energy input can be delivered for circuit I and II. The input can be used in controller for energy limitation.
See 4.8 for details setting up the ECL Comfort for energy input.
14 VI.7F.C5.02 © Danfoss 12/2007 DH-SMT/DK
Instructions ECA 82 LONworks in the ECL Comfort 200/300/301
4.7 Network variables 36. & 37. Actual ow input from a node in the network. Input
network input SNVT_ow_f nviActFlow_1;
network input SNVT_ow_f nviActFlow_2;
Input unit = liter / second.
Valid range 0 .. 833 liter / second (0..2999 m
3
/ h).
The actual ow input can be delivered for circuit I and II. The input can be used in controller for ow limitation.
See 4.8 for details setting up the ECL Comfort for ow input.
4.8 Handling energy and ow input from the network
This input is only active in an ECL Comfort without a pulse input. If a pulse module is connected, the actual
power information is delivered as pulses. The ECL Comfort is limited to one type of input ow/energy at each
circuit.
When an update occurs on this input, some extra parameters will expire in the ECL Comfort service parameters
list (grey side of the application card).
Lines 110 - 115 expire in the controller user interface.
Line 114 has to be set to 1.
Line 115 has to be setup on the controller user interface in order to choose how the power is displayed in the
controller user interface.
Value line 115 Flow/energy unit Range in ECL Range in SNVT
O None None
1 l/h 0 - 2999 0 - 0.8 l/s
2 l/h 0 - 2999 0 - 0.8 l/s
3 m3/h 0.0 - 299.9 0 - 83,3 l/s
4 m3/h 0.0 - 299.9 0 - 83,3 l/s
5 m3/h 0.0 - 299.9 0 - 83,3 l/s
6 m3/h 0 - 2999 0 - 833 l/s
7 kW 0.0 - 299.9 0.0 - 299.9
8 kW 0.0 - 299.9 0.0 - 299.9
9 kW 0 - 2999 0 - 2999
10 MW 0.0 - 299.9 0.0 - 299.9
11 MW 0.0 - 299.9 0.0 - 299.9
12 MW 0 - 2999 0 - 2999
13 GW 0.0 - 299.9 0.0 - 299.9
14 GW 0.0 - 299.9 0.0 - 299.9
15 GW 0 - 2999 0 - 2999
Table 11: Conguration of ECL Comfort ow / energy input
4.8.1 Setting time constants
When the ECL Comfort CPU receives ow/ energy data, it will apply some ltering to the received data. Limiting
of ow/energy consumption takes place by integral control. For both these processes, i.e. the ltering of the
received data and the integral control, the ECL Comfort needs a time constant. These time constants are
determined by lines 113 and 112, respectively.
Lines 112 and 113 can be set for circuit I as well as circuit II. When setting the lines, you change between circuits I
and II by pressing the circuit I/II button.
DH-SMT/DK VI.7F.C5.02 © Danfoss 12/2007 15
Instructions ECA 82 LONworks in the ECL Comfort 200/300/301
Line Range Default value Description
112 1 – 250 40 Line 112 is a time constant for integral control of ow/energy limiting. A high value of
112 means fast control, a low value means slow (more stable) control
113 1 – 250 2 Line 113 is a time constant for digital ltering of ow/energy input data. When line 113
is set to 1, no ltering is applied. A high value of 113 means that a degree of ltering
applied
Table 12: Adjustment of time constants
4.8.2 Setting the ow or energy reference
Before the ECL Comfort can perform ow/energy limitation, a reference ow or energy value must be entered
for each circuit where ow/energy limitation should be active. The ow/energy reference value works dierently
for a heating circuit as for a domestic hot-water circuit.
Heating circuit:
For a heating circuit (circuit I or II in the ECL Comfort), the ow/energy reference is determined indirectly by the
ECL Comfort in accordance with the actual outdoor temperature. For a heating circuit the ECL Comfort thus
performs outdoor temperature dependent ow/energy limitation. The ECL Comfort Installers Guide (‘grey
section, Service Parameters) describes the functions and set-up of return temperature limiting in a heating
circuit. Flow/energy limitation works according to the same principle. The ow/energy reference is determined
according to an outdoor temperature curve:
Desired flow / energy
Line 116
Line 117
Outdoor temp.
-15 0 +15
Figure 4: Principle of the ow/energy limitation
The maximum and minimum of the curve shown in Figure 4 are determined by the lines 116 and 117,
respectively. The corresponding x-coordinates are identical to the x-coordinates of the return temperature
limitation curve. See the ECL Comfort Installers Guide on how to read and write the x-coordinates.
Line Range Default value Description
116 * 2999 Line 116 is the maximum y-coordinate of the ow/ energy limiting curve
117 * 2999 Line 117 is the minimum y-coordinate of the ow/ energy limiting curve
Table 13: Flow/energy limitation
For a domestic hot-water circuit, the ow/energy reference is entered directly into line 111.
4.9 Network variable 53. Outdoor temperature input
network input SNVT_temp nviOutdoortemp;
Resolution: 0.1
o
C. (The resolution in ECL Comfort display is 1
o
C.
The temperature 0.5
o
C – 1.49
o
C is shown as 1
o
C in the display).
Valid range -64
o
C - 192
o
C.
See 4.11 for details concerning outdoor temperature input.
16 VI.7F.C5.02 © Danfoss 12/2007 DH-SMT/DK
Instructions ECA 82 LONworks in the ECL Comfort 200/300/301
4.10 Network variable 54. Outdoor temperature input
network input SNVT_temp_p nviOutdoortemp_p;
Resolution: 0.01
o
C. (The resolution in ECL Comfort display is 1
o
C).
Valid range -64
o
C - 192
o
C.
See 4.11 for details concerning outdoor temperature input.
4.11 General handling of outdoor temperature input
In order to use this input for weather compensation in the ECL Comfort, no physical outdoor sensor can be
connected. If a physical sensor is mounted, the outdoor temperature input will come from the ECL controller.
The physical sensor always has the highest priority.
The ECL Comfort must act as a slave (no outdoor sensor connected) in order to use outdoor sensor values from
the network. This inuences the possibility of combining the controller with other remote controllers: ECA 60,
ECA 61 and ECA 63.
The connection can be veried: Outdoor temperature is shown in the controller display at the user side, line A,
bottom left.
-64
o
C indicates a short-circuited sensor.
192
o
C indicates that no sensor mounted.
4.12 Network variables 6. 7. & 17.-20. & 46.–49. Temperature sensors 1-10: Output
network output SNVT_temp nvoSensorNr_1
network output SNVT_temp nvoSensorNr_2;
network output SNVT_temp nvoSensorNr_3;
network output SNVT_temp nvoSensorNr_4;
network output SNVT_temp nvoSensorNr_5;
network output SNVT_temp nvoSensorNr_6;
network output SNVT_temp nvoSensorNr_7;
network output SNVT_temp nvoSensorNr_8;
network output SNVT_temp nvoSensorNr_9;
network output SNVT_temp nvoSensorNr_10;
Measured temperature values from the ECL Comfort sensors are sent to the network.
Valid range
Measured temperatures within the range -58 °C - 158 °C can be indicated.
192
o
C indicates that no sensor has been installed.
-64
o
Cindicates that the sensor has been short-circuited.
Updating speed
The built-in sensors (sensors 1-6) have an update period of 2 * SendHeartBeat.
The ECA 86 sensors connected (sensors 7-10) have an update period of 8 * SendHeartBeat. The update sequence
is illustrated in Figure 5 at a SendHeartBeat value = 5 sec.
DH-SMT/DK VI.7F.C5.02 © Danfoss 12/2007 17
Instructions ECA 82 LONworks in the ECL Comfort 200/300/301
Update of sensor values
0
1
2
3
0 5 10 15 20 25 30 35 40 45 50 55 60
Time sec
update
Sensors 1- 6 Sensors 7-10
Figure 5: Update of sensor values
For further information regarding update periods, see Table 28 in 6.2, page 39.
Sensors nr 7–10 can either be ECA 86 sensors or used to report specially congured sensors. The sensor
conguration depends on the application card and user conguration
4.13 Network variables 9. & 12. Setpoint concerning circuit I & II: Output
network output SNVT_temp_setpt nvoSetptRoom_1;
network output SNVT_temp_setpt nvoSetptRoom_2;
Field denitions:
Field Parameter Valid range
occupied_cool Proportional band 1,00.. 250.00 K
standby_cool Parallel displacement -9.00 .. 9.00 K
unoccupied_cool Heating cut-out 10.00 .. 30.00
o
C
occupied_heat Setpoint comfort period 10.00 .. 30.00
o
C
standby_heat Heat curve 0.20 .. 3.40
unoccupied_heat Setpoint setback period 10.00 .. 30.00
o
C
For all elds: 0x7FFF (-273,17
o
C) means that data are unavailable. Only parameters supported in the controller
application are updated.
Transmission
The setpoint is updated at start up and when the setpoint is changed by the ECL Comfort or network.
4.14 Network variable 10. Setpoints concerning hotwater setting: Output
network output SNVT_temp_setpt nvoSetptHW;
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43

Danfoss ECA 82, LonWorks in the ECL Comfort Operating instructions

Type
Operating instructions

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI