Danfoss ECA 82, LonWorks in the ECL Comfort Operating instructions

Type
Operating instructions
ECA 82 LONworks for ECL Comfort 200/300
DH-SMT
VI.7F.C4.02 @ Danfoss 12/2004
ECA 82
LONworks in the ECL Comfort 200/300/301
Instructions
Page 2 of 48 VI.7F.C4.02 @ Danfoss 12/2004 DH-SMT
Table of Contents
1 Introduction 4
1.1 Scope 4
1.2 About the implementation in the LONworks protocol 4
1.3 General information 4
1.4 ECA 82 compatibility with other options card 4
1.5 ECA 82 compatibility with the ECL Comfort controller and applications 5
2 Getting started 6
2.1 Installation 6
2.2 Starting up 7
2.3 Service pin and neuron ID 7
2.4 XIF file 8
3 Node object 9
3.1 Mandatory network variables 9
3.1.1 1. Node request: Input 9
3.1.2 3. Setting time and date: Input 10
3.1.3 2. Node status: Output 11
3.1.4 4. Alarm: Output 11
4 Weather compensator object 15
4.1 5. & 11. Setpoints, circuit I & II: Input 16
4.2 8. Setpoints, hot water setting: Input 17
4.3 15. & 16. Control of valves and mode: Input 17
4.4 21. Control of pumps: Input 18
4.5 55. Control of the week plan 18
4.6 34. & 36. Actual power input from node in the network. Input 20
4.7 36. & 37. Actual flow input from a node in the network. Input 20
4.8 Handling energy and flow input from the network 20
4.8.1 Setting time constants 21
4.8.2 Setting the flow or energy reference 21
4.9 53. Outdoor temperature input 22
4.10 54. Outdoor temperature input 23
4.11 General handling of outdoor temperature input 23
4.12 6. 7. & 17.- 20. & 46. – 49. Temperature sensors 1 - 10: Output 23
4.13 9. & 12. Setpoint concerning circuit I & II: Output 24
4.14 10. Setpoints concerning hotwater setting: Output 25
4.15 13. & 14. Status of valves, optimizer status and relative humidity 25
4.16 22. Reading off time and date: Output 26
DH-SMT VI.7F.C4.02 @ Danfoss 12/2004 Page 3 of 48
4.17 33. Pump status 26
4.18 56. Reporting week plan in ECL Comfort. Output 27
4.19 57. & 58. Controller mode status, circuit I & II. Output 27
4.20 42. & 43. Actual power delivered from pulse module. Output 27
4.21 44. & 45. Actual flow delivered from pulse module. Output 28
4.22 27. – 30. Sensor references 3-6. Output 28
5 Manufacturer-defined section 29
5.1 23. & 24. Analog outputs 1 & 2: Input 30
5.2 25. & 26. Analog inputs 1 & 2: Output 30
5.3 19. & 20. Parameter command and response 30
5.3.1 Learn field 31
5.3.2 Selector field 31
5.3.3 Value field 31
5.3.4 Parameters, grey side of the ECL card, circuit I. 34
5.3.5 Parameters, yellow side of the ECL card, circuit I. 35
5.3.6 Parameters, grey side of the ECL card, circuit II. 36
5.3.7 Parameters, yellow side of the ECL card, circuit II. 37
5.3.8 Parameters, gray side of the ECL card, circuit III 38
5.3.9 ECL Comfort status information 38
5.3.9.1 Selector 250 details 38
5.3.9.2 Selector 251 details 38
5.3.9.3 Selector 252 details 38
5.3.10 ECA 82 set-up and details 39
5.3.10.1 Software version in ECA 82 39
5.3.10.2 SendHeartBeat 39
5.3.10.3 Voltage update 39
5.3.10.4 ECL checks for adjustments 39
5.3.10.5 Application loaded in the ECL Comfort 39
5.3.11 Alarm limit configuration 40
5.3.12 Alarm code readout 40
5.3.13 Accumulated energy or flow preload 41
6 Thumb rules for network design in heating systems 42
6.1 Considerations before implementing communication 42
6.1.1 What are the basic needs for information 42
6.1.2 What is the final number of nodes in the network 43
6.1.2.1 Parallel network 43
6.1.2.2 Backbone network 44
6.1.3 Bandwidth considerations 44
6.1.3.1 Total number of controllers in network 46
6.2 Update of SNVT from ECL Comfort 47
6.2.1 Minimize copy of data on the network 47
6.2.2 Note down the neuron ID 47
Page 4 of 48 VI.7F.C4.02 @ Danfoss 12/2004 DH-SMT
1 Introduction
Scope
This ECA 82 option for ECL Comfort is based on Echelons® LONworks®.
The ECA 82 can be used in ECL Comfort 200 and 300-301 series. In the remaining part
of these instructions, the type designation ECL Comfort will be used.
1.2 About the implementation in the LONworks protocol
The following instruction describes the parameters that can be communicated between
a LONworks network and ECL Comfort. The build-up of the physical network is not
described. For further information see Echelons homepage: http://www.echelon.com/.
The instruction is divided into three main sections:
1. The LonMark node object is used to the extent that functions are supported in ECL
Comfort. The functions from the node object that are supported in ECL Comfort are
described in “Node object”.
2. The basic parameters behind weather compensation are described separately in the
section on the weather compensator object.
3. Parameters that are special for ECL Comfort are described separately in the
manufacture-defined section.
1.3 General information
1. The possibilities for communication depend on the application loaded in the ECL
Comfort. This ECA 82 is designed to fit all applications card. Hardware configuration
settings and future parameters might not be supported.
2. Only one kind of communication can be used in the ECL Comfort. It is not possible to
run RS232 together with ECA82 communication.
1.4 ECA 82 compatibility with other options card
ECA 80 ECA 81 ECA 83 ECA 84 ECA 85 ECA 86 ECA 87 ECA 88
Yes No Yes No Yes Yes No Yes
DH-SMT VI.7F.C4.02 @ Danfoss 12/2004 Page 5 of 48
1.5 ECA 82 compatibility with the ECL Comfort controller and applications
App. card ECL Comfort 300-301 controller
Version 1.05 Version 1.06 Version 1.07 Version 1.08 Version 1.09
C14 CI05
C25 CI05 ECA 82 v. 1.4- 1.9 ECA 82 v. 1.4-1.9 ECA 82 v. 1.4-1.9 ECA 82 v. 1.4-1.9 ECA 82 v. 1.9
C37 CI05 ECA 82 v. ECA 82 v. 1.4-1.9 ECA 82 v. 1.4-1.9 ECA 82 v. 1.4-1.9 ECA 82 v. 1.9
C37 CI08 ECA 82 v. 1.4-1.9 ECA 82 v. 1.4-1.9 ECA 82 v. 1.4-1.9 ECA 82 v. 1.4-1.9 ECA 82 v. 1.9
C47 CI05 ECA 82 v. 1.4-1.9 ECA 82 v. 1.4-1.9 ECA 82 v. 1.4-1.9 ECA 82 v. 1.4-1.9 ECA 82 v. 1.9
C47 CI08 ECA 82 v. 1.4-1.9 ECA 82 v. 1.4-1.9 ECA 82 v. 1.4-1.9 ECA 82 v. 1.9 ECA 82 v. 1.9
C55 CI05 ECA 82 v. 1.4-1.9 ECA 82 v. 1.4-1.9 ECA 82 v. 1.4-1.9 ECA 82 v. 1.4-1.9 ECA 82 v. 1.9
C60 CI05 ¹) ECA 82 v. 1.4-1.9 ECA 82 v. 1.4-1.9 ECA 82 v. 1.4-1.9 ECA 82 v. 1.4-1.9 ECA 82 v. 1.9
C62 CI05 ²) ECA 82 v. 1.4-1.9 ECA 82 v. 1.4-1.9 ECA 82 v. 1.4-1.9 ECA 82 v. 1.4-1.9 ECA 82 v. 1.9
C66 CI05 ECA 82 v. 1.4-1.9 ECA 82 v. 1.4-1.9 ECA 82 v. 1.4-1.9 ECA 82 v. 1.4-1.9 ECA 82 v. 1.9
C66 CI08 ECA 82 v. 1.4-1.9 ECA 82 v. 1.4-1.9 ECA 82 v. 1.4-1.9 ECA 82 v. 1.4-1.9 ECA 82 v. 1.9
C67 CI05 ECA 82 v. 1.4-1.9 ECA 82 v. 1.4-1.9 ECA 82 v. 1.4-1.9 ECA 82 v. 1.4-1.9 ECA 82 v. 1.9
C67 CI08 ECA 82 v. 1.4-1.9 ECA 82 v. 1.4-1.9 ECA 82 v. 1.4-1.9 ECA 82 v. 1.9 ECA 82 v. 1.9
C75 CI05 ECA 82 v. 1.4-1.9 ECA 82 v. 1.4-1.9 ECA 82 v. 1.4-1.9 ECA 82 v. 1.4-1.9 ECA 82 v. 1.9
¹) Sensor 6 cannot be shown if applications card <= CI05.
²) Only one room temperature sensor can be shown on the LON network.
Card index 08 (CI08) requires ECL version 1.08 or 1.09, otherwise a CI05 is loaded.
Updating ECA 82 from version 1.6 to 1.7 causes an error:
The error prevents writing some of parameters from the LON interface to the ECL
Comfort.
ECA 82 version 1.8 only exists in test samples.
Page 6 of 48 VI.7F.C4.02 @ Danfoss 12/2004 DH-SMT
2 Getting started
The ECA 82 can be used together with ECL Comfort 200, 300 and 301. It is not
possible to use the ECA 82 together with ECL Comfort 100.
Further information on the operation of ECL Comfort is comprised by the instructions
supplied with the ECL Card.
2.1 Installation
Step 1:
Dismount cover plate B on the back of the ECL Comfort using a small slice cutter
nipper.
Step 2:
Mount ECA 82 in the slides and press it gently into the connector on the ECL Comfort
print board.
Step 3:
Mount the new cover plate B, which is delivered with the option card.
DH-SMT VI.7F.C4.02 @ Danfoss 12/2004 Page 7 of 48
Pin connection:
1: LON data 1, left side pin of the connector.
2: Middle pin of the connector. Do not use!
3: LON data 2, right side pin of the connector.
The FTT10 transceiver is based on a balanced bus. LON data 1 and 2 can be reversed.
2.2 Starting up
When starting up the ECA 82, a period of about 30 seconds will elapse during which the
database from the controller will be copied. During this starting up period it is not
possible to come into contact with the ECA 82, neither from ECL Comfort nor from the
network. The starting-up period will occur on the reset/power up of the controller/ECA
82, and when an application change is made in ECL Comfort.
After starting up, the following parameters can be activated via the ECL Comfort user
interface:
Line 196 in circuit I is the service pin.
Line 197 in circuit I is the ECA 82 reset.
Lines 196 and 197 can be can accessed by scrolling down through the lines on the
installer page (grey page) with the arrow down key.
The lines can be activated/deactivated with the +/- keys (see the instructions for the
application card).
At wink command, the display will flash until any key on ECL Comfort is pressed.
2.3 Service pin and neuron ID
The ECA 82 does not have any hardware service pin. The service pin is activated from
the ECA 82 software application. This means that it is not possible to send any service
pin if the ECA 82 is put in non-configured mode. If the ECA 82 anyhow is set in non-
configured mode, the unique neuron ID number is required to set the ECA 82 back in
configured mode. If the ECA 82 is decommissioned or non-configured without having
the neuron ID, the ECA 82 is damaged! The system integrator is responsible for noting
down the neuron ID.
Page 8 of 48 VI.7F.C4.02 @ Danfoss 12/2004 DH-SMT
2.4 XIF file
The XIF file can be found on the internet
Before using a xif file, check the software version in the ECA 82. The software version
can be read directly on the memory IC on the ECA 82 card, see Figure 1 and Table 1.
The Software version can also be found using the network in parameter
nviParamCmd/nvoParamResp, selector 1000, see 5.3.10.1 Software version in ECA 82
Using the ECA 82 requires a XIF file which fits the software version.
Figure 1: Find ECA 82 software version
Table 1: ECA 82 software versions and XIF file
ECA 82 software version Text on IC label XIF file name
1.4 087B1564 VER 1.4 ECL14.XIF
1.5 087B1564 VER 1.5 ECL15.XIF
1.6 087B1564 VER 1.6 ECL16.XIF
1.9 087B1564 VER 1.9 ECL19.XIF
The XIF file can also be loaded directly from the ECA 82 via the LON network for
example by using the LONMaker for Windows.
The XIF files can be downloaded from the internet: http://heating.danfoss.com
DH-SMT VI.7F.C4.02 @ Danfoss 12/2004 Page 9 of 48
3 Node object
The node object is used for controlling and establishing the status of the node. It is
thus possible to ask for and receive the status of the actual condition of the node.
Mandatory Nework variables
Optional network variables
Input
Network
Variables
Output
Network
Variables
Node Object
Type #0
nv 2
nvoStatus
SNVT_obj_status
nv 1
nviRequest
SNVT_obj_request
nv 4
nvoAlarm
SNVT_alarm
nv 3
nviTimeSet
SNVT_time_stamp
Figure 2: Node object
Table 2: SNVT input
NV NR
Name SNVT Type
(SNVT Index)
Class Description
1 NviRequest SNVT_obj_request Ram Request object
status
3 NviTimeSet SNVT_time_stamp Ram Set time and
date
Table 3: SNVT output
NV NR
Name SNVT Type
(SNVT Index)
Class Description
2 NvoStatus SNVT_obj_status Ram Status of node
4 NvoAlarm SNVT_Alarm Ram Alarm reporting
3.1 Mandatory network variables
3.1.1 1. Node request: Input
network input SNVT_obj_request nviRequest;
Page 10 of 48 VI.7F.C4.02 @ Danfoss 12/2004 DH-SMT
Valid range
The following parameters are supported:
0: RQ_NORMAL: Set controller in normal mode after override (manual mode). The
following functions are only active in manual mode.
SNVT_setting nviValve_1 & 2. (Valve control)
SNVT_state nviControl. (Pump control)
SNVT_object_request nviRequest.RQ_OVERRIDE.
SNVT_object_request nviRequest.RQ_RMV_OVERRIDE.
SNVT_volt nviAnalogOut_1 & 2.
Returning to normal from manual mode set circuit I and II in automatic mode.
1: RQ_DISABLED: Not supported.
2: RQ_UPDATE_STATUS. Update object status: nvo_obj_status and nvoTime.
3: RQ_SELF_TEST: Not supported.
4: RQ_UPDATE_ALARM. Sends actual status on nvoAlarm to the network via
SNVT_alarm (alarm on/off).
5: RQ_REPORT_MASK: Not supported.
6: RQ_OVERRIDE. Override from comfort to setback and vice versa. ¹)
7: RQ_ENABLE: Not supported.
8: RQ_RMV_OVERRIDE. Delete override between comfort and setback. Return to
condition before override.
9: RQ_CLEAR_STATUS: Delete all bits in SNVT_obj_status nvoStatus.
10: RQ_CLEAR_ALARM: Delete alarms entered in nvoAlarm SNVT_alarm
11: RQ_ALARM_NOTIFY_ENABLED: Enable alarm reporting in nvoAlarm.
12: RQ_ALARM_NOTIFY_DISABLED: Disable alarm reporting in nvoAlarm.
13: RQ_MANUAL_CTRL. Set controller in manual mode in all circuits. ²)
14: RQ_REMOTE_CTRL: Not supported.
15: RQ_PROGRAM: Not supported.
!
¹) Can only be activated if the controller is set in manual mode by the network or controller
user interface.
!
²) Note: If the controller is parked in line B at the user’s side (yellow), the valve and pump
status is overridden by the controller, in order to give the locally positioned user a
possibility manually to override the controller user interface. The override from the
controller user interface can be avoided in ECL Comfort 300 by removing the ECL card
from the controller. Without the ECL card the controller will lock the keyboard after 5
minutes. Line B on the user’s side is designed to secure that a manual control can be
carried out locally directly without distortions from the network.
3.1.2 3. Setting time and date: Input
network input SNVT_time_stamp nviTimeset;
The actual time and date entered in the ECL can be set here.
DH-SMT VI.7F.C4.02 @ Danfoss 12/2004 Page 11 of 48
Valid range
Year 1996-2026
Month 1-12
Day 1-31 ¹)
Hour 0-23
Minute 0-59
¹) The number of days depends on the month in question. If an attempt is made to set more
days than in the month, the request will be rejected and nvoAlarm SNVT_ALARM is
updated (the alarm function has to be enabled to get an alarm, see 3.1.1).
3.1.3 2. Node status: Output
network output SNVT_obj_status nvoStatus;
SNVT uses this input to report on the node status.
The following points are supported:
Over_range: Set if an input value from the network is higher than the
max permissible value.
Under_range: Set if an input value from the network is under the min
permissible value.
Manual_control: Set if the controller has been set in manual mode from the
network, or if the controller is set in manual mode from ECL Comfort user
interface.
In_alarm: Set if an alarm has been set.
In_override: Set if the controller overrides between comfort/setback from the
network.
alarm_notify_disabled: Alarm reporting in nvoAlarm disabled.
3.1.4 4. Alarm: Output
network output SNVT_Alarm nvoAlarm;
The possibilities for alarm reporting are:
Input value out of range alarm.
Alarm on all physical sensors
Alarm sensor - reference 2-8.
Alarm on relative humidity level.
Bit reporting of 32 alarm conditions.
Indication of sensor - reference alarm on time:0 min, 10 min, 30 min and 60 min
Time and date for latest alarm occurrence.
History buffer with the latest 4 occurred SNVT alarm indexes.
The alarm function is enabled from nviRequest.RQ_ALARM_NOTIFY_ENABLE and
disabled from nviRequest.RQ_ALARM_NOTIFY_DISABLE
All alarm levels are configured in 5.3.11 Alarm limit configuration
If an illegal date or year is entered via nviTimeSet SNVT_time_stamp, an alarm type 1
will be activated and the year or day will show the illegal value.
Page 12 of 48 VI.7F.C4.02 @ Danfoss 12/2004 DH-SMT
Alarm type:
Value Identifier Notes
0 AL_NO_CONDITION No alarm condition present.
1 AL_ALM_CONDITION Invalid value set in nviTimeset.
9 AL_LOW_LMT_ALM_1 Alarm low limit alarm 1: Attempt to set
parameter under legal value.
10 AL_LOW_LMT_ALM_2 Alarm low limit alarm 2: Value under
configured level has expired.
11 AL_HIGH_LMT_ALM_1 Alarm high limits alarm 1: Attempt to set
parameter higher than legal value.
12 AL_HIGH_LMT_ALM_2 Alarm high limits alarm 2: Value higher than
configured level has expired.
0xFF AL_NUL Value not available
Priority level:
Value Identifier Notes
0 PR_LEVEL_0 Lowest alarm priority level. Alarm reported
on sensor - Reference 2-8 value.
1 PR_LEVEL_1 Alarm reports sensor - reference 2-8 value
has been active for 10 minutes.
2 PR_LEVEL_2 Alarm reports sensor - reference 2-8 value
has been active for 30 minutes.
3 PR_LEVEL_3 Highest alarm priority level. Alarm reports
sensor - reference 2-8 value has been active
for 60 minutes.
0xff PR_NULL No alarms present on sensor - reference 2-8.
DH-SMT VI.7F.C4.02 @ Danfoss 12/2004 Page 13 of 48
index_to_SNVT The SNVT index for the latest expired alarm is presented.
Value[4] The value field is used for alarm reporting. Each alarm status is represented
by 1 bit. 1 means alarm on, 0 means alarm off. 9 alarms can be reported the structure
for decoding. The alarm report can be read in Table 4 -Table 6.
Table 4: nvoAlarm.value [0]
nvoAlarm.value[0]
bit nr
Alarm status at Alarm limit configured in selector
0 Temperature sensor 1 1018
1 Temperature sensor 2 1019
2 Temperature sensor 3 1020
3 Temperature sensor 4 1021
4 Temperature sensor 5 1022
5 Temperature sensor 6 1023
6 Temperature sensor 7 (ECA
86)
1024
7 Temperature sensor 8 (ECA
86)
1025
Table 5: nvoAlarm.value [1]
nvoAlarm.value[1]
bit nr
Alarm status at Alarm limit configured in selector
0 Temperature sensor 9
(ECA 86)
1026
1 Temperature sensor 10
(ECA 86)
1027
2 Sensor 2 - reference 2 1028
3 Sensor 3 - reference 3 1029
4 Sensor 4 - reference 4 1030
5 Sensor 5 - reference 5 1031
6 Sensor 6 - reference 6 1032
7 Sensor 7 - reference 7
(ECA 86)
1033
Table 6: nvoAlarm.value [2]
nvoAlarm.value[2]
bit nr
Alarm status at Alarm limit configured in
0 Sensor 8 - reference 8
(ECA 86)
Selector 1034
1 Relative humidity 1 (ECA
62)
Selector 1035
2 Relative humidity 2 (ECA
62)
Selector 1036
Page 14 of 48 VI.7F.C4.02 @ Danfoss 12/2004 DH-SMT
year, month, day, hour, minute:
The time for the latest alarm is reported. The time is determined by the ECL Comfort
clock.
alarm_limit[4]
This is a 4 value FIFO buffer that indicates the latest 4 present alarms, which have an
SNVT index.
Transmission
Generating alarms in ECA 82:
Sensor 1-6: 2 * SendHeartBeat. Default 10 sec.
Sensor - reference 2-6: 4 * SendHeartBeat. Default 20 sec.
Sensor 6-10 and sensor - reference 7 and 8 (ECA 86):
8 * SendHeartBeat. Default 40 sec.
DH-SMT VI.7F.C4.02 @ Danfoss 12/2004 Page 15 of 48
4 Weather compensator object
Here the parameters necessary to provide weather compensation are described. The
values involved are divided into mandatory network variables and optional network
variables.
5
nviTSetptRoom_1
SNVT tem
p
set
p
t
15, 16
nviValve_1 & 2
SNVT_setting
In
p
ut
Network
Variables
Out
p
ut
Network
Variables
ECL Comfort
Weather compensator object
22
nvoTime
SNVT_time_stamp
11
nviTSetptRoom_2
SNVT_temp_setpt
9
nvoTSetptRoom_1
SNVT_temp_setpt
17-20
nvoSensorNr_3 - 6
SNVT_temp
8
nviTSetptHW
SNVT tem
p
set
p
t
10
nvoTSetptHW
SNVT tem
p
set
p
t
6, 7
nvoSensorNr_1 - 2
SNVT_temp
12
nvoSetptRoom_2
SNVT_temp_setpt
21
nviControl
SNVT_state
56
nvoWeekplan
SNVT_str_asc
33
nvoControl
SNVT_state
55
nviWeekplan
SNVT_str_asc
34, 36
nviActPower_1 & 2
SNVT_power_f
13, 14
nvoValve_1 & 2
SNVT_setting
35, 37
nviActFlow_1 & 2
SNVT_flow_f
42, 43
nvoActPower_1 & 2
SNVT_power_f
44, 45
nvoActFlow_1 & 2
SNVT_flow_f
46-49
nvoSensorNr_7 - 10
SNVT_temp
27-30
nvoRef_Nr_3 - 6
SNVT_temp
53
nviOutdoortemp
SNVT_temp
54
nviOutdoortemp_p
SNVT_temp_p
57, 58
nvoMode_1 & 2
SNVT_hvac_mode
Figure 3: Object details
Page 16 of 48 VI.7F.C4.02 @ Danfoss 12/2004 DH-SMT
Table 7: SNVT input
NV NR
(index)
Name SNVT Type
Description
5 nviSetptRoom_1 SNVT_temp_setpt Setpoints concerning circuit I
8 nviSetptHW SNVT_temp_setpt Hot water setpoint.
11 nviSetptRoom_2 SNVT_temp_setpt Setpoints concerning circuit II
15, 16 nviValve_1 & 2 SNVT_setting Control of valves (triacs)
21 nviControl SNVT_state Control of pumps (relays)
55 nviWeekplan SNVT_str_asc Setting of week plan all circuits
34, 36 nviActPower_1 & 2 SNVT_power_f Power input from LON device (heat
meter).
35, 37 nviActFlow_1 & 2 SNVT_flow_f Flow input from LON device (flow
meter).
53 nviOutdoortemp SNVT_temp Outdoor temperature input from
LON network.
54 nviOutdoortemp_p SNVT_temp_p Outdoor temperature input from
LON network.
Table 8: SNVT output details
NV NR
(index)
Name SNVT Type
Send
Heart
Beat
Description
6, 7 nvoSensorNr_1–2 SNVT_temp *2 Sensor values
9 nvoTSetptRoom_1 SNVT_temp_setpt No Setpoints, circuit I
10 nvoTSetptHW SNVT_temp_setpt No Setpoints, hot water.
12 nvoTSetptRoom_2 SNVT_temp_setpt No Setpoints, circuit II.
13, 14 nvoValve_1 & 2 SNVT_setting 5 sec Status of valves
up/down/stopped.
17-20 nvoSensorNr_3–6 SNVT_temp *2 Sensor values 3-6.
22 nvoTime SNVT_time_stamp *8 Time and date set in ECL
Comfort
33 nvoControl SNVT_state 5 sec Status of pumps (relays).
56 nvoWeekplan SNVT_str_asc No Week plan setting, all
circuits.
57, 58 nvoMode_1 & 2 SNVT_hvac_mode 5 sec Controller mode, circuit I
& II
42, 43 nvoActPower_1& 2 SNVT_power_f *8 Actual power
44, 45 nvoActFlow_1 & 2 SNVT_flow_f *8 Actual flow
46-49 nvoSensorNr_7-10 SNVT_temp *8 Sensor values from ECA
86
27-30 nvoRef_Nr_3-6 SNVT_temp *4 References for sensor 3-
6.
The SendHeartBeat value can be adjusted in 5.3.10.2, page 39.
4.1 5. & 11. Setpoints, circuit I & II: Input
network input SNVT_temp_setpt nviTSetptRoom_1;
network input SNVT_temp_setpt nviTSetptRoom_2;
DH-SMT VI.7F.C4.02 @ Danfoss 12/2004 Page 17 of 48
Field definitions
Field Parameter Valid Range Resolution
occupied_cool Proportional band 1.00 .. 250.00 K 1.00
standby_cool Parallel displacement -9.00 .. 9.00 K 1.00
unoccupied_cool Summer cut out 10.00 .. 30.00 °C 1.00
occupied_heat Setpoint comfort period 10.00 .. 30.00 °C 1.00
standby_heat Heat curve 0.20 .. 3.40 0.10
unoccupied_heat Setpoint setback period 10.00 .. 30.00 °C 1.00
Validation of data
If input is set to a value outside the valid area, the setting is ignored in ECL Comfort
and nvoTSetptRoom_1 or 2. The error is reported in nvoStatus.under_range /
over_range.
Default value
Default value set in the SNVT: All fields = 0 at start-up.
4.2 8. Setpoints, hot water setting: Input
network input SNVT_temp_setpt nviTSetptHW;
Field definitions
Field Parameter Valid Range Resolution
occupied_cool Hot water temp. diff. 1.00 .. 250.00 °C 1.00
standby_cool Charging temp. - relative 1.00 .. 30.00 K 1.00
unoccupied_cool Difference 1 - cut-out temp. 1.00 .. 30.00 K 1.00
occupied_heat Setpoint comfort period 10.00 .. 110.00 °C 1.00
standby_heat Difference 2 - cut-in temp. 1.00 .. 30.00 K 1.00
unoccupied_heat Setpoint setback period 10.00 .. 110.00 °C 1.00
The proportional band of the hot water is set in network input SNVT_temp_setpt
nviTSetptRoom_2, occupied_cool.
Default value
Default value set in the SNVT: All fields = 0 at start-up.
4.3 15. & 16. Control of valves and mode: Input
network input SNVT_setting nviValve_1;
network input SNVT_setting nviValve_2;
The valve and controller mode can be controlled by these.
nviValve_1 control valve 1 (triac 1 and 2) and the controller mode circuit I.
nviValve_2 control valve 2 (triac 3 and 4) and the controller mode circuit II.
Page 18 of 48 VI.7F.C4.02 @ Danfoss 12/2004 DH-SMT
Function:
0 SET OFF => Setback mode
1 SET ON => Comfort mode
2 SET DOWN => Valve down
3 SET UP => Valve up
4 SET STOP => Stop valve
5 SET STATE => Automatic mode
6 SET NUL => Standby mode
Setting: Not used
Rotation: Not used
!
Note: The valve can only be controlled if the controller is in manual mode.
Manual mode (for all circuits) can be entered in nviRequest, see 3.1.1.1. Node request:
Input.
4.4 21. Control of pumps: Input
Network input SNVT_state nviControl;
Pumps (relay) can be controlled by this input.
Valid range
For all values: 1 = relay in, no connection, 0 = relay out, connection.
Bit 0: Standard relay 1
Bit 1: Standard relay 2
Bit 2: Standard relay 3
Other values are not supported.
Relays placed on options cards (ECA 80 & ECA 86) cannot be controlled from the ECA
82. The application in ECL Comfort always control options relays.
!
Note: The pumps can only be controlled if the controller is in manual mode.
Manual mode (for all circuits) can be entered in nviRequest, see 3.1.1.1. Node request:
Input page 9 or directly at the ECL Comfort.
In some applications the ECL Comfort overwrites the specified setting from the
network. In sequence controllers (C75) non-valid relay combinations is overwritten by
the ECL Comfort. Do not use this override function in the applications F05 and F06.
4.5 55. Control of the week plan
network input SNVT_str_asc nviWeekplan;
A new week plan can be set and the actual week plan already set in the controller can
be requested.
Request status of the week plan already set in controller for readout in nvoWeekplan.
DH-SMT VI.7F.C4.02 @ Danfoss 12/2004 Page 19 of 48
Field ascii[0] - ascii[29] must contain the value 0x00;
Field ascii[30] must contain an value indicating which week plan to report.
Table 9: Request week plan setting
Field ascii[30] value Week plan area
0x10 Week days in circuit I
0x11 Weekend in circuit I
0x20 Week days in circuit II
0x21 Weekend in circuit II and all days circuit III
The week plan is divided into ½ hour intervals. The week plan can contain a maximum
of 3 periods a day. Each field ascii[0] - [29] is a char build of 8 bit. Each of these bit
represent ½ hour in the week plan. The exact position can be found using Table 10.
Table 10: Week day decoding
Field ascii[30] = 0x10 or
0x20
ascii[30] = 0x11 Ascii[30] = 0x21
ascii[0] Monday 0.00-3.30 Saturday 0.00-3.30 Saturday 0.00-3.30
ascii[1] Monday 4.00-7.30 Saturday 4.00-7.30 Saturday 4.00-7.30
ascii[2] Monday 8.00-11.30 Saturday 8.00-11.30 Saturday 8.00-11.30
ascii[3] Monday 12.00-15.30 Saturday 12.00-15.30 Saturday 12.00-15.30
ascii[4] Monday 16.00-19.30 Saturday 16.00-19.30 Saturday 16.00-19.30
ascii[5] Monday 20.00-23.30 Saturday 20.00-23.30 Saturday 20.00-23.30
ascii[6] Tuesday 0.00-3.30 Sunday 0.00-3.30 Sunday 0.00-3.30
ascii[7] Tuesday 4.00-7.30 Sunday 4.00-7.30 Sunday 4.00-7.30
ascii[8] Tuesday 8.00-11.30 Sunday 8.00-11.30 Sunday 8.00-11.30
ascii[9] Tuesday 12.00-15.30 Sunday 12.00-15.30 Sunday 12.00-15.30
ascii[10] Tuesday 16.00-19.30 Sunday 16.00-19.30 Sunday 16.00-19.30
ascii[11] Tuesday 20.00-23.30 Sunday 20.00-23.30 Sunday 20.00-23.30
ascii[12] Wednesday 0.00-3.30 All days 0.00-3.30, circuit III
ascii[13] Wednesday 4.00-7.30 All days 4.00-7.30, circuit III
ascii[14] Wednesday 8.00-11.30 All days 8.00-11.30, circuit III
ascii[15] Wednesday 12.00-15.30 All days12.00-15.30, circuit III
ascii[16] Wednesday 16.00-19.30 All days 16.00-19.30, circuit III
ascii[17] Wednesday 20.00-23.30 All days 20.00-23.30, circuit III
ascii[18] Thursday 0.00-3.30
ascii[19] Thursday 4.00-7.30
ascii[20] Thursday 8.00-11.30
ascii[21] Thursday 12.00-15.30
ascii[22] Thursday 16.00-19.30
ascii[23] Thursday 20.00-23.30
ascii[24] Friday 0.00-3.30
ascii[25] Friday 4.00-7.30
ascii[26] Friday 8.00-11.30
ascii[27] Friday 12.00-15.30
ascii[28] Friday 16.00-19.30
ascii[29] Friday 20.00-23.30
ascii[30] Information about the circuit for which the data apply, see Table 9 for decoding.
Error codes are reported in nvoWeekplan see 4.18 page 27.
Error causes: No value set in ascii[30] or too many periods set in one day.
Page 20 of 48 VI.7F.C4.02 @ Danfoss 12/2004 DH-SMT
4.6 34. & 36. Actual power input from node in the network. Input
network input SNVT_power_f nviActPower_1;
network input SNVT_power_f nviActPower_2;
Input unit = Watt.
Valid input range 0 .. 2,999 * 10
12
watt. (Max value in the ECL Comfort display).
Actual energy input can be delivered for circuit I and II. The input can be used in
controller for energy limitation.
See 4.8 for details setting up the ECL Comfort for energy input.
4.7 36. & 37. Actual flow input from a node in the network. Input
network input SNVT_flow_f nviActFlow_1;
network input SNVT_flow_f nviActFlow_2;
Input unit = liter / second.
Valid range 0 .. 833 liter / second (0..2999 m
3
/ h).
The actual flow input can be delivered for circuit I and II. The input can be used in
controller for flow limitation.
See 4.8 for details setting up the ECL Comfort for flow input.
4.8 Handling energy and flow input from the network
This input is only active in an ECL Comfort without a pulse input. If a pulse module is
connected, the actual power information is delivered as pulses. The ECL Comfort is
limited to one type of input flow/energy at each circuit.
When an update occurs on this input, some extra parameters will expire in the ECL
Comfort service parameters list (grey side of the application card). Lines 110 - 115
expire in the controller user interface.
Line 114 has to be set to 1.
Line 115 has to be setup on the controller user interface in order to choose how the
power is displayed in the controller user interface.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48

Danfoss ECA 82, LonWorks in the ECL Comfort Operating instructions

Type
Operating instructions

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI