Copyright HK Instruments 2023 www.hkinstruments. Installaon version 4.0 2023
Thesellerisobligatedtoprovideawarrantyofveyearsforthedeliv-
eredgoodsregardingmaterialandmanufacturing.Thewarrantyperiod
isconsideredtostartonthedeliverydateoftheproduct.Ifadefect
inrawmaterialsora producon aw isfound, theseller isobligated,
whentheproductissenttothesellerwithoutdelayorbeforeexpira-
onofthewarranty,toamendthemistakeathis/herdiscreoneither
by repairing the defecve product or by delivering free of charge to
thebuyeranewawlessproductandsendingittothebuyer.Delivery
costsfortherepairunderwarrantywillbepaidbythebuyerandthe
return costs by the seller. The warranty does not comprise damages
causedbyaccident,lightning,oodorothernaturalphenomenon,nor-
malwearandtear,improperorcarelesshandling,abnormaluse,over-
loading,improperstorage,incorrectcareorreconstrucon,orchanges
andinstallaonworknotdonebytheseller.Theseleconofmaterials
fordevicespronetocorrosionisthebuyer’sresponsibility,unlessother-
wiseislegallyagreedupon.Shouldthemanufactureralterthestructure
ofthedevice,thesellerisnotobligatedtomakecomparablechanges
todevicesalreadypurchased.Appealingforwarrantyrequiresthatthe
buyerhascorrectlyfullledhis/herduesarisenfromthedeliveryand
stated in the contract. The seller will give a new warranty for goods
thathavebeenreplacedorrepairedwithinthewarranty,howeveronly
totheexpiraonoftheoriginalproduct’swarrantyme.Thewarranty
includestherepairofadefecvepartordevice,orifneeded,anewpart
ordevice,butnotinstallaonorexchangecosts.Undernocircumstance
isthesellerliablefordamagescompensaonforindirectdamage.
STEP 5: Selecting the kv value
WARRANTY POLICY
Figure 6 - Rectangular duct
InFloXact™-RmodelsthereisonlyoneKVvalueanditreadsonthelabeloftheprobe.FortheFloXact™-LKVvaluemustbedeterminedbydimen-
sions(widthandheight)oftheduct.
RECYCLING/DISPOSAL
The parts le over from installaon should be
recycled according to your local instrucons.
Decommissioned devices should be taken to a
recyclingsitethatspecializesinelectronicwaste.
Theairvolumecanbedeterminedwiththe
followingformula:
Q = KV x √Pfs
Q=airvolumeinl/s
K
V=KVvalueinl/s/Pa
Pfs=pressuredierence
measuredbytheFloXactsck
in Pa
Thetableisforairwith1.20kg/m3density
(20°C,50%rHand1013mbar).
TheK-valuefordierentdensiesisdeter-
minedwiththefollowingformula:
CorrectedK-value=Kv*√(ρ/1.20)
K-factor=921xBx(H-0,025n)l/s
B=ductwidthinmeter
H=ductheightinmeter
n=numberofFloXactused
Forintermediatesizes,contactouroce.
Figure 7 - Round duct