HK Instruments FloXactTM-R100 User manual

  • Hello! I am an AI chatbot trained to assist you with the HK Instruments FloXactTM-R100 User manual. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
Copyright HK Instruments 2023 www.hkinstruments. Installaon version 4.0 2023
INSTALLATION
INSTRUCTIONS
Measurement probe
FloxactTM
READ THESE INSTRUCTIONS CAREFULLY BEFORE
ATTEMPTING TO INSTALL, OPERATE OR SERVICE THIS
DEVICE.
• Failuretoobservesafetyinformaonandcomplywith
instruconscanresultinPERSONALINJURY,DEATHAND/OR
PROPERTY DAMAGE.
• Toavoidelectricalshockordamagetoequipment,disconnect
powerbeforeinstallingorservicinganduseonlywiringwith
insulaonratedforfulldeviceoperangvoltage.
• Toavoidpotenalreand/orexplosiondonotuseinpotenally
ammableorexplosiveatmospheres.
• Retaintheseinstruconsforfuturereference.
• Thisproduct,wheninstalled,willbepartofanengineered
systemwhosespecicaonsandperformancecharacteriscs
arenotdesignedorcontrolledbyHKInstruments.Review
applicaonsandnaonalandlocalcodestoassurethatthe
installaonwillbefunconalandsafe.Useonlyexperiencedand
knowledgeabletechnicianstoinstallthisdevice.
To measureair ow accurately in a venlaonduct, use a special
FloXact™measurementprobetogetherwithaDPT-Flowtransmit-
ter.
TherearetwoFloXact™modelsavailable:RmodelforroundductsandLforrectangularducts.Inordertoachievethebestaccuracy,itis
recommendedtousetwoFloXact™-Lprobesiftheheightofarectangularductismorethan350mm,threeprobesiftheductsizeis700mmor
more,andfourprobesiftheductsizeis1000mmormore.
FloXact™-R modelsavailable:100,125,160,200,250,315,400and450andallotherstandardroundductsizesupto1200mm.
FloXact™-L modelsavailable:250,300…1200(50mmsteps)
Lengthoftheprobe(L)isdenedbythewidth(W)oftheduct.(Seestep5).
Othersizesareavailableonrequest.
Example:
fora160mmroundduct,chooseFloXact-R160probe,andfora500x400mmrectangularduct,choosetwoFloXact-L500probes.
step 2: SELECTING THE CORRECT DPT-FLOW MODEL
INTRODUCTION
STEp 1: SELECTING THE CORRECT FLOXACTTM PROBE
WARNING
ItisrecommendedtouseDPT-Flow-1000-AZ-DmodelwithFloXactTMprobesbecausedynamicductpressureisrarelyover500Pa.Typical
pressurerangeinavenlaonductis0…250Pa.
ThemeasurementrangeofDPT-Flow-1000-AZ-Dis0...1000Pa.
Copyright HK Instruments 2023 www.hkinstruments. Installaon version 4.0 2023
STEP 3: INSTALLATION - MOUNTING THE PROBE MOUNTING THE PROBE continued
Figure 1 - Mounng
Figure 2 - Air ow direcon
1)CheckthatthesizeoftheFloXact™probecorrespondswiththe
ductorterminaltowhichitisgoingtobeinstalled.
2)Drillaø25mmholeintotheduct
3)PlacetheFloXact™probe(s)intotheductthroughthehole.
6)ConnectthetubesfromtheFloXact™pressureinletstotheinletin
thepressuretransmier.Connecttheplustubetotheplusinletand
theminustubetotheminusinlet.
• IfmorethanoneFloXactTMprobesused,uset-hoseconnectorto
connecttubesfromseparateprobes.
5)Aachtheprobe(s)intotheductwithtwoscrews.
Figure 3 - Aaching with screws
• Forroundducts,werecommendinstallingtheFloXact™probe
horizontallyintheduct.
4)Checkthatairowdireconintheductcorrespondswiththe
indicaonontheFloXact™probe.
Figure 4
FloXactTM-Lmounng
FloXactTM-Rmounng
When do I need more than one probe? – Check step 1.
• Fornonstandardapplicaons,pleasecontactyournearest
distributororthefactory.
FloXactTM-Rmounngwithtwoprobes.
Copyright HK Instruments 2023 www.hkinstruments. Installaon version 4.0 2023
STEP 4: CORRECT POSITIONING OF THE PROBE
Figure 5 - Correct posioning of the probe: minimum straight duct approach
Roundducts:
D=ductdiameter
Rectangularducts:
Ifthereisahorizontalcurveorchangeintheductsize,D=widthoftheduct
Ifthereisavercalcurveorchangeintheductsize,D=heightoftheduct
Copyright HK Instruments 2023 www.hkinstruments. Installaon version 4.0 2023
Thesellerisobligatedtoprovideawarrantyofveyearsforthedeliv-
eredgoodsregardingmaterialandmanufacturing.Thewarrantyperiod
isconsideredtostartonthedeliverydateoftheproduct.Ifadefect
inrawmaterialsora producon aw isfound, theseller isobligated,
whentheproductissenttothesellerwithoutdelayorbeforeexpira-
onofthewarranty,toamendthemistakeathis/herdiscreoneither
by repairing the defecve product or by delivering free of charge to
thebuyeranewawlessproductandsendingittothebuyer.Delivery
costsfortherepairunderwarrantywillbepaidbythebuyerandthe
return costs by the seller. The warranty does not comprise damages
causedbyaccident,lightning,oodorothernaturalphenomenon,nor-
malwearandtear,improperorcarelesshandling,abnormaluse,over-
loading,improperstorage,incorrectcareorreconstrucon,orchanges
andinstallaonworknotdonebytheseller.Theseleconofmaterials
fordevicespronetocorrosionisthebuyer’sresponsibility,unlessother-
wiseislegallyagreedupon.Shouldthemanufactureralterthestructure
ofthedevice,thesellerisnotobligatedtomakecomparablechanges
todevicesalreadypurchased.Appealingforwarrantyrequiresthatthe
buyerhascorrectlyfullledhis/herduesarisenfromthedeliveryand
stated in the contract. The seller will give a new warranty for goods
thathavebeenreplacedorrepairedwithinthewarranty,howeveronly
totheexpiraonoftheoriginalproduct’swarrantyme.Thewarranty
includestherepairofadefecvepartordevice,orifneeded,anewpart
ordevice,butnotinstallaonorexchangecosts.Undernocircumstance
isthesellerliablefordamagescompensaonforindirectdamage.
STEP 5: Selecting the kv value
WARRANTY POLICY
Figure 6 - Rectangular duct
InFloXact™-RmodelsthereisonlyoneKVvalueanditreadsonthelabeloftheprobe.FortheFloXact™-LKVvaluemustbedeterminedbydimen-
sions(widthandheight)oftheduct.
RECYCLING/DISPOSAL
The parts le over from installaon should be
recycled according to your local instrucons.
Decommissioned devices should be taken to a
recyclingsitethatspecializesinelectronicwaste.
Theairvolumecanbedeterminedwiththe
followingformula:
Q = KV x √Pfs
Q=airvolumeinl/s
K
V=KVvalueinl/s/Pa
Pfs=pressuredierence
 measuredbytheFloXactsck
in Pa
Thetableisforairwith1.20kg/m3density
(20°C,50%rHand1013mbar).
TheK-valuefordierentdensiesisdeter-
minedwiththefollowingformula:
CorrectedK-value=Kv*√(ρ/1.20)
K-factor=921xBx(H-0,025n)l/s
B=ductwidthinmeter
H=ductheightinmeter
n=numberofFloXactused
Forintermediatesizes,contactouroce.
Figure 7 - Round duct
/