Air Monitor Corporation ELECTRA-flo Ultra Installation Procedures Manual

Type
Installation Procedures Manual
ELECTRA-flo Probe Arrays - Ultra
INSTALLATION PROCEDURE
WARRANTY
Air Monitor Corporation (hereinafter referred to as "Seller") warrants that at the time of shipment, products sold
pursuant to this contract will be free from defects in materials and workmanship, and will conform to the
specifications furnished or approved in writing by Seller. No warranty is given that delivered products will conform
to catalog sheets, data sheets, and the like, which are subject to change without notice.
Seller will repair or replace, at its option, any products listed under this warranty which is returned freight pre-
paid to Seller and within the earlier of three (3) years after start-up or thirty-nine (39) months after shipment, prove
upon test and examination by Seller to be defective within the terms of this warranty. The warranty period for
any item repaired or replaced shall be for the time remaining on the warranty period for the original components.
Purchaser shall notify Seller in writing of such defect within sixty (60) days of discovery of the defect.
This warranty does not extend to any product sold by Seller which has been the subject of misuse, neglect,
accident, damage or malfunction caused by interconnection with equipment manufactured by others, improper
installation or storage, or used in violation of instructions furnished by Seller, nor does it extend to any product
which has been repaired or altered by persons not expressly approved by Seller.
Seller shall not be liable for any special or consequential damages or for loss of damage directly or indirectly
arising from the use of the products.
The warranty set forth above is in lieu of all other warranties either express or implied and constitutes the full extent
of Air Monitor Corporation's liability to the customer, or any other party for breach of warranty. THERE ARE NO
EXPRESS WARRANTIES EXCEPT AS SET FORTH HEREIN. THERE ARE NO IMPLIED WARRANTIES OF
MERCHANTABILITY OR FITNESS FOR ANY PARTICULAR PURPOSE, WHICH ARE PARTICULARLY
DISCLAIMED.
INSPECTION & HANDLING. The ELECTRA-flo Probe Arrays should be carefully inspected for damage prior to installation.
Report damage to your Freight Department, or contact delivery carrier.
Almost any means of handling can be utilized depending on the length of the probes. Probes may be handled
while in any position; however, it is important not to drop or mishandle the probes such that damage is done to the
sensing holes, tubular members, signal connection fittings, end studs, or mounting plates.
ELECTRA-flo Probe Arrays – Ultra – Installation Procedure
LOCATION OF PROBES.
When installing the ELECTRA-flo probes, select a location that meets or exceeds the Minimum Installation
Requirements.
When more than the combined upstream and downstream minimum requirement for undisturbed straight duct is
available, distribute the excess duct length in proportion to the minimum requirements.
Avoid locating the probes where they will be exposed to condensing moisture, such as downstream of a coil or
humidifier.
Contact Air Monitor's Applications Engineering Department for guidance when the intended installation location
does not meet the Minimum Installation Requirements.
MINIMUM INSTALLATION REQUIREMENTS.
Turbulent Airflow. The aerodynamic design of the ELECTRA-flo sensor aperture will permit accurate flow
measurement in the presence of moderate air turbulence. The distances from air turbulence producing fittings,
transitions, etc., shown below are required to assure accurate airflow measurement.
Stratified Airflow. The ELECTRA-flo should be mounted so that the probe crosses any stratified airflow - not
parallel to the flow. This mounting arrangement will permit the probe to sense the wide range of velocities present in
stratified airflow.
Airborne Contaminants. The levels of air filtration and cleanliness associated with commercial HVAC systems
are satisfactory for the ELECTRA-flo. Applications containing airborne contaminants or condensing moisture may
impair measurement accuracy and functionality.
Minimum Requirements. The ELECTRA-flo locations shown below are the minimum clearance required from
air turbulence producing sources. Wherever possible, the ELECTRA-flo should be installed where greater runs of
straight duct or clearances exist.
- 2 -
ELECTRA-flo Probe Arrays – Ultra – Installation Procedure
-3-
INSTALLATION CONFIGURATIONS. Depending upon the size of the duct, the quantity of probes will range
between one and four per probe array. Based upon the quantity of probes in a particular array, use one of the
following generic layouts for determining proper probe spacing and configurations.
ELECTRA-flo Probe Arrays – Ultra – Installation Procedure
-4-
GENERAL PROBE INSTALLATION
All probes for an array are packaged together when shipped from the Factory. The probes and the transmitter for a
particular measurement location can be identified by means of the ESID # on the end of each probe, transmitter
package, and the transmitter itself.
Each probe has an airflow arrow on the mounting plate to assist in correct installation relative to the direction of
airflow in the duct.
For rectangular ducts, the standard arrangement is for the probe(s) to be mounted on the short side (height) of the
duct, with the probe(s) running parallel with the long dimension (width) of the duct. Refer to Page 3 to determine
probe spacing.
For circular ducts with more than one probe, the probes must be staggered along the axis of the duct to provide
clearance as they cross over each other in the center. The radial dimension (R) on the outside of a duct of known
diameter (D) with N (quantity) of probes can be determined by the following formula:
For probes larger than 72", do not attempt to install with just one person.
For probes 96" or more in length, refer to the next page.
N
2
D14.3
R =
The ESID # on the Transmitter and on the Probe(s) must match.
DO NOT MIX AND MATCH
Confirm the number of Probes needed for each Transmitter by
referring to the provided Factory Set-Up Sheet.
CAUTION: DO NOT BEND PROBES
ELECTRA-flo Probe Arrays – Ultra – Installation Procedure
-5-
INSTALLING PROBES 96" OR MORE IN LENGTH
ELECTRA-flo probe arrays having probe lengths between 96" and 144" are provided with a probe center support
assembly to structurally support against the effects of gravity, vibration, and the force of the moving airflow.
All ELECTRA-flo probes must be handled carefully during installation to avoid damaging any of the thermal sensors.
Due to their greater cantilevered weight, larger probes will require two people during installation; one outside the duct
to insert the probe, and a second person inside the duct to support and guide the probe into its end support hole.
After the ELECTRA-flo probes are fully mounted in the duct, install the center support by connecting it to the
individual probes using the U-bolt hardware provided. The center support goes on the downstream side of the
ELECTRA-flo probes (see Figure below):
– CAUTION –
DO NOT ATTEMPT TO INSTALL ELECTRA-FLO PROBES
LARGER THAN 72" WITH JUST ONE PERSON.
SUPPORT CLAMP DETAIL
Tighten the self-locking nuts so the center support is firmly attached to the probe(s), but not so tight as to deform
either the center support or the probes. Slide the center support mounting brackets outward so they come in
contact with the duct walls, then secure in place with the end support screws provided.
Finally, position the center support so that the clearance between the center support and the duct wall is the same
at both ends, then tighten the mounting bracket bolts. See Figure below:
MOUNTING BRACKET DETAIL
Front View Side View
Front View Side View
ELECTRA-flo Probe Arrays – Ultra – Installation Procedure
-6-
EXTERNALLY MOUNTED PROBES.
Mounting requires a 1.25" hole on one side of the duct, and a 3/8" hole on the other side for the threaded end
support for ducts wider than 18". See Figure A below for mounting details.
Figure A
External mount probes are shipped with a 1/4" thick neoprene mounting gasket.
INTERNALLY MOUNTED PROBES.
Mounting requires a single 1/2" diameter hole to allow the signal cable to be run to the transmitter. See Figure B
below for mounting details.
Figure B
ELECTRA-flo Probe Arrays – Ultra – Installation Procedure
-7-
CABLE CONNECTIONS.
All cables to connect the probes and transmitter are included.
All probes have integral cables terminated with positive locking plug-in connectors.
The cable length on each probe has been Factory selected based upon size of the duct and the quantity of
probes. Cables connecting probe to probe will range in length from 2' to 5'. The one probe that connects to the
transmitter will have a standard length 10' cable, with optional 50' and 100' long cables.
Multiple externally mounted probes connect to each other in a daisy chain methods, with the first or closest
probe in the chain connecting to the transmitter. See Figure below.
Multiple internally mounted probes are connected in parallel to a central junction box mounted inside the duct,
with the junction box connecting to the transmitter. See Figure below.
ELECTRA-flo Probe Arrays – Ultra – Installation Procedure
TRANSMITTER INSTALLATION.
The transmitter must be located so that the single cable from the probe array will reach the receptacle in the
bottom of the transmitter. Standard cable length is 10', with optional 50' and 100' cables available.
Mount the transmitter to a vertical surface in an upright position. Avoid locations subject to excessive amounts of
vibration.
The transmitter's enclosure has a NEMA 1 rating, requiring that it be mounted in a moderately clean indoor
environment with temperature ranges between –20ºF and 140ºF.
Consult the ELECTRA-flo Transmitter O&M manual for details related to power and signal wire connections,
configuration options, and start-up.
See drawings below for transmitter dimensions and installation clearances.
Thermal Air Flow Transmitter
ELECTRA-
flo
MIR ONITORA
CORPORATION
1050 Hopper Avenue • Santa Rosa, CA 95403 • 707-544-2706 • www.airmonitor.com
CUSTOMER SERVICE. Air Monitor Corporation provides in-house technical support for all our products:
Monday through Friday, 7 am to 5 pm (pst)
Phone: 707-544-2706 or 1-800-AIRFLOW / Fax: 707-526-2825
If after contacting the Customer Service Department it is determined that equipment will require return to Air Monitor
Corporation for further repair, a Return Authorization number will be issued. A Confirmation of Return Authorization with
shipping instructions will be sent via facsimile. Equipment to be returned to Air Monitor should be returned in its original
shipping container if possible. If this is not possible, ensure equipment is packaged sufficiently to protect it during
shipment.
Caution: All damage occurring during transit is the Customer’s responsibility.
List the Return Authorization (R/A) number on the packing list and clearly mark this number on the outside of each
shipping container. Costs associated with the return of equipment to Air Monitor Corporation are the customer’s
responsibility regardless whether the repair/return is under warranty. Once the Customer Service Department determines
that the equipment repair is under warranty, the item will be repaired and returned to the customer at no charge. If the
equipment is not under warranty, customer will need to approve a repair quote which will be invoiced along with return
shipping charges.
INSTALL35A (07/07)
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8

Air Monitor Corporation ELECTRA-flo Ultra Installation Procedures Manual

Type
Installation Procedures Manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI