INSTALLATION
INSTRUCTIONS
DIFFERENTIAL PRESSURE TRANSMITTERS
DPT-2W Series
READ THESE INSTRUCTIONS CAREFULLY BEFORE
ATTEMPTING TO INSTALL, OPERATE OR SERVICE THIS DEVICE.
• Failuretoobservesafetyinformaonandcomplywith
instruconscanresultinPERSONAL INJURY, DEATH AND/OR
PROPERTY DAMAGE.
• Toavoidelectricalshockordamagetoequipment,disconnect
powerbeforeinstallingorservicinganduseonlywiringwith
insulaonratedforfulldeviceoperangvoltage.
• Toavoidpotenalreand/orexplosiondonotuseinpotenally
ammableorexplosiveatmospheres.
• Retaintheseinstruconsforfuturereference.
• Thisproduct,wheninstalled,willbepartofanengineered
systemwhosespecicaonsandperformancecharacteriscs
arenotdesignedorcontrolledbyHKInstruments.Review
applicaonsandnaonalandlocalcodestoassurethatthe
installaonwillbefunconalandsafe.Useonlyexperiencedand
knowledgeabletechnicianstoinstallthisdevice.
SPECIFICATIONS
ThankyouforchoosinganHKInstrumentsDPTseriesdierenal
pressuretransmier.TheDPTseriesisintendedforuseincommer-
cial environments. The DPT-2W series dierenal pressure trans-
mierprovidesa4–20mAloopoutput.
All DPT-2W series dierenal pressure transmiers are available
withdisplayand/orowlinearoutput.
DPT-2WseriesdevicesarecommonlyusedinHVAC/Rsystemsfor:
•fan,blowerandltermonitoring
•pressureandowmonitoring
•valveanddampercontrol
•pressuremonitoringincleanrooms
SPECIFICATIONS
Performance
Accuracy:
±1.5%FSoveroperaontemperaturerange:
-10...50°C%/FSfromhighestpressure
range(including:generalaccuracy,temperaturedri,
linearity,hysteresis,andrepeonerror)
Long term stability:
Typical1year:±8Pa;DPT-2W-2500
Thermal eects:
Temperaturecompensatedacrossthefullspectrumof
capability.
Overpressure:
Proofpressure:25kPa
Burstpressure:30kPa
Zeropointcalibraon:
Manualpushbuon
Response me:
4.0sor0.8s,selectable
Technical Specicaons
Media compability:
Dryairornon-aggressivegases
Measuring units:
Pa
Measuring element:
Piezoresisve
Enviroment:
Operangtemperature:-10...50°C
Storagetemperature:-20...70°C
Humidity:0to95%rH,noncondensing
Physical
Dimensions:
Case:90.0x95.0x36.0mm
Weight:
150g
Mounng:
2each4.3mmscrewholes,onesloed
Materials:
Case:ABS
Lid:PC
Ductconnectors:ABS
Tubing:PVC
Protecon standard:
IP54
Display: (Oponal)
31/2digitLCDdisplay
Size:45.7mmWx12.7mmH
Electrical connecons:
2screwterminalblock
Wire:1224AWG(0.2–1.5mm2)
Cable entry:
Strainrelief:M16
Conduitknockout:16mm
Pressure ngs:
Male5.0mmand6.3mm
Electrical
Voltage:
Circuit:2-wire
Supply:10–35VDC
Supply(Current):32mAmaximum
Output:4–20mAloop
Zero/Spanoutputcalibratedwithin±0.08mA
Maximumload= Supply-10V
 0,020A
Minimumload:20Ω
Powerconsumpon:<1.2W
Conformance
MeetsrequirementsforCEmarking:
EMCDirecve2014/30/EU
RoHSDirecve2011/65/EU
WEEEDirecve2012/19/EU
INTRODUCTION
APPLICATIONS
WARNING
COMPANY WITH
MANAGEMENT SYSTEM
CERTIFIED BY DNV GL
= ISO 9001 = ISO 14001 =
RoHS 2
2011/65/EU
Copyright HK Instruments 2017 www.hkinstruments.Installaon version 5.0 2017
Figure 1c - Applicaon connecons
Figure 1b - Mounng orientaon
SCHEMATICS
DIMENSIONAL DRAWINGS
INSTALLATION
Figure 1a - Surface mounng
STEP 1: MOUNTING THE DEVICE
1)Mountthedeviceinthedesiredlocaon(seestep1).
2)Openthelidandroutethecablethroughthestrainreliefand
connectthewirestotheterminalblock(s)(seestep2).
3)Thedeviceisnowreadyforconguraon.
WARNING!Applypoweronlyaerthedeviceisproperlywired.
1)Selectthemounnglocaon(duct,wall,panel).
2)Usethedeviceasatemplateandmarkthescrewholes.
3)Mountwithappropriatescrews.
Jumpers
Terminal
block
Pressure
sensor
Connecon
for oponal
display
LED
Zero buon
J3
J2
J1 4–20 mA
4–20 mA
POLARITY FREE
90.0
77.0
71.5
53.0
4.3
95.0
36.0
Pa
YES NO NO
Stac pressure Filter/Damper
monitoring
Fan/Blower
monitoring
Not
connected
Copyright HK Instruments 2017 www.hkinstruments.Installaon version 5.0 2017
STEP 2: WIRING DIAGRAMS SELECTING THE MEASUREMENT RANGE CONTINUED
ForCEcompliance,aproperlygroundedshieldingcableisrequired.
1)Unscrewthestrainreliefandroutethecable.
2)Connectthewiresasshowningure2.
3)Tightenthestrainrelief.
Figure 2 - Wiring diagram 4–20 mA
1)Selectthedesiredmeasurementrange.(seestep4)
2)Selectthedesiredresponseme.(seestep5)
3)Zerothedevice.(seestep6)
4)Connectthepressuretubes.Connectposivepressureto
portlabeled“+”andnegavepressuretoport“-.
7)Closethelid.Thedeviceisnowreadytobeused.
STEP 3: CONFIGURATION
STEP 4: SELECTING THE MEASUREMENT RANGE
A. For R8 models
1)Findtherequiredmeasurementrangeanddeterminetherange
numberintheheaderofChart1.
2)InstalljumpersonJ1,J2andJ3indevice,asshowninChart2.
 (Greycolourindicatesthatajumperisinstalled.ReferenceFigure
3forjumperinstallaon.)
No jumper
Circuit open
Jumper storedJumper installed
Circuit closed
(Grey colour indicates that a jumper is installed)
Figure 3 - Jumper installaon
4–20 mA
Power supply
10...35 VDC
A
4–20 mA
Polarity free
Range 1 Range 2 Range 3 Range 4 Range 5 Range 6 Range 7 Range 8
Pa -100...+100 0...100 0...250 0...500 0...1000 0...1500 0...2000 0...2500
Model DPT-2W-2500-R8
Chart 1 - R8 ranges
Chart 2 - R8 jumpers
Range 7 Range 8Range 1 Range 2 Range 3 Range 4 Range 5 Range 6
Jumper J1
Jumper J2
Jumper J3
(Grey colour indicates that a jumper is installed)
B. For R4 models
1)Findtherequiredmodelandmeasurementrangeanddeterminethe
rangenumberintheheaderofChart3.
2)InstalljumpersonJ2andJ3indevice,asshowninChart4.
 (Greycolourindicatesthatajumperisinstalled.ReferenceFigure3
forjumperinstallaon.)
Chart 3 - R4 ranges
Range 1 Range 2
DPT-2W-1000-R4 0...250 0...500
4-range models
Pa
DPT-2W-3000-R4 0...750 0...1500 Pa
DPT-2W-5000-R4 0...1250 0...2500 Pa
Range 3 Range 4
0...750
0...2250
0...1000
0...3000
0...3750 0...5000
Chart 4 - R4 jumpers
Range 1 Range 2 Range 3 Range 4
RESPONSE TIME SELECTION
Jumper J2
Jumper J3
(Grey colour indicates that a jumper is installed)
C. For R2 models
1)Findtherequiredmodelandmeasurementrangeanddeterminethe
rangenumberintheheaderofChart5.
2)InstalljumpersonJ2andJ3indevice,asshowninChart6.
 (Greycolourindicatesthatajumperisinstalled.ReferenceFigure3
forjumperinstallaon.)
Chart 5 - R2 ranges
Range 1 Range 2
DPT-2W-100-R2 0...50 0...100
2-range models
Pa
DPT-2W-±100-R2 -50...50 -100...100 Pa
DPT-2W-250-R2 0...100 0...250 Pa
DPT-2W-500-R2 0...250 0...500 Pa
DPT-2W-1000-R2 0...500 0...1000 Pa
DPT-2W-2500-R2 0...1500 0...2500 Pa
DPT-2W-5000-R2 0...2500 0...5000 Pa
Chart 6 - R2 jumpers
Range 1 Range 2
RESPONSE TIME SELECTION
Jumper J2
Jumper J3
(Grey colour indicates that a jumper is installed)
Copyright HK Instruments 2017 www.hkinstruments.Installaon version 5.0 2017
Thesellerisobligatedtoprovideawarrantyofveyearsforthedeliv-
eredgoodsregardingmaterialandmanufacturing.Thewarrantyperiod
isconsideredtostartonthedeliverydateoftheproduct.Ifadefectin
rawmaterialsoraproduconawisfound,thesellerisobligated,when
theproductissenttothesellerwithoutdelayorbeforeexpiraonof
thewarranty,toamendthemistakeathis/herdiscreoneitherbyre-
pairingthedefecveproductorbydeliveringfreeofchargetothebuy-
eranewawlessproductandsendingittothebuyer.Deliverycosts
fortherepairunderwarrantywillbepaidbythebuyerandthereturn
costsbytheseller.Thewarrantydoesnotcomprisedamagescausedby
accident, lightning, ood or other natural phenomenon, normal wear
andtear,improperorcarelesshandling,abnormaluse,overloading,im-
properstorage,incorrectcareorreconstrucon,orchangesandinstal-
laonworknotdonebythesellerorhis/herauthorizedrepresentave.
Theseleconofmaterialsfordevicespronetocorrosionisthebuyer’s
responsibility,unlessotherwiseislegallyagreedupon.Shouldtheman-
ufactureralterthestructureofthedevice,thesellerisnotobligatedto
makecomparablechangestodevicesalreadypurchased.Appealingfor
warrantyrequiresthatthe buyerhascorrectlyfullledhis/herdues
arisenfromthedeliveryandstatedinthecontract.Thesellerwillgive
anewwarrantyforgoodsthathavebeenreplacedorrepairedwithin
thewarranty,howeveronlytotheexpiraonoftheoriginalproduct’s
warrantyme.Thewarrantyincludestherepairofadefecvepartor
device, orifneeded,a new part or device, but not installaon or ex-
change costs. Underno circumstanceisthe seller liable fordamages
compensaonforindirectdamage.
Thezeropointshouldbeadjustedviamanualzeroing,onehouraer
installaonandatleastevery12monthsduringnormaloperaons.
Manualzeroing:
1)Note:supplyvoltagemustbeconnectedatleastonehourpriorto
zeropointadjustment.
2)Disconnectbothpressuretubesfromthepressureportslabeled+
and-.
3)Pushthezerobuonatleast4secondsunltheLEDlight(red)
showsonelongblink.(seeFigure4)
4)Thezeroingofthedevicewillproceedautomacally.Zeroingis
completewhentheLEDturnso.
5)Reinstallthepressuretubes,ensuringthehighpressuretubeis
connectedtotheportlabeled+,andthelowpressuretubeis
connectedtotheportlabled-.
STEP 6: ZEROING THE DEVICE
A. For R8 model:
Theresponsemeaectshowfastthetransmierreactstochangesin
thesystem.Theresponsemeisthemethedevicetakestoreach63
%ofthemeasuredvalue.Tosmoothoutunstablepressureuctuaons
inairowapplicaons,selectalongerresponseme.
Example:
Selectedresponseme:8.0seconds
Result: Output signal achieves a new value in 20 seconds (Response
me*5)
Usethezerobuontochangeresponseme:
1)Pushdownandreleasethebuonquickly.LEDemits2blinks.
Deviceissetwith8.0secondresponseme.
2)Pushdownandreleasethebuonquicklyagain.LEDemits3short
blinks.Deviceissetwith0.8secondresponseme.
B. For R2 and R4 models
UsethejumperJ1toselecttheresponseme.InstalljumpertoJ1to
set0.8sresponseme.RemovethejumperJ1toset4sresponseme.
(Seechart7)
STEP 5: SELECTING THE RESPONSE TIME
0.8 s 8 s
Jumper J1
MEASUREMENT RANGE SELECTION
MEASUREMENT RANGE SELECTION
(Grey colour indicates that a jumper is installed)
WARRANTY POLICY
a) Disconnect both pressure tubes from the pressure ports labeled
+ and –.
b) Push down the zero button (joystick) until the LED light (red)
turns on and the display reads “zeroing” (display option only). (see
Figure 6)
c) The zeroing of the device will proceed automatically. Zeroing is
complete when the LED turns off, and the display reads 0 (display
option only).
d) Reinstall the pressure tubes, ensuring the High pressure tube is
connected to the port labeled +, and the Low pressure tube is
connected to the port labeled −.
Press down buon
LED turns ON
LED
Figure 4
Chart 7
The parts le over from installaon should be
recycled according to your local instrucons.
Decommissioned devices should be taken to a
recyclingsitethatspecializesinelectronicwaste.