Greengate NeoSwitch - 120/277/347V Dual Tech/Single Level Wall Switch Sensor (Ground Required) Installation guide

Type
Installation guide

This manual is also suitable for

Installation Instructions
Eaton’s Cooper Controls Business
203 Cooper Circle
Peachtree City, Georgia 30269
www.coopercontrol.com
Model # ONW-D-1001-347-W
Model # ONW-D-1001-347-V
Model # ONW-D-1001-347-LA
Model # ONW-D-1001-347-G
Model # ONW-D-1001-347-B
NeoSwitch Dual Technology Single Relay
Occupancy Sensing Wall Switch
(Ground Required)
• Readallinstructionsonbothsidesofthis
sheetrst
• InstallinaccordancewithALLlocalcodes
• Forindooruseonly
General Information
Technology:PassiveInfrared(PIR)andUltrasonic(US)
Electrical Ratings:
347VAC:
• Incandescent/Tungsten–
Max.load:4.3amps,1500W,50/60Hz
• Fluorescent/Ballast–
Max.load:4.3amps,1500W,50/60Hz
Ballast Compatibility:Compatiblewithmagneticand
electronicballasts
No Minimum Load Requirement
Time Delays:Self-Adjusting,15seconds/test(10min
Auto),Selectable5,15,30minutes
Coverage:Majormotion–1000sq.ft.
Minormotion–300sq.ft.
Light Level Sensing:0to200foot-candles
Operating Environment:
• Temperature:32°F–104°F(0°C–40°C)
• RelativeHumidity:20%to90%non-condensing
Housing:Durable,injectionmoldedhousing.
PolycarbonateresincomplieswithUL94VO.
Size:
• MountingPlate/StrapDimensions:
4.35"Hx1.732"W(110.49mmx44mm)
• ProductHousingDimensions:2.618"Hx1.752"
Wx1.9"D(66.5mmx44.5mmx48.26mm)
LED Indicators:RedLEDindicatesPIRdetection;
GreenLEDindicatesUltrasonicdetection.
Specifications
Description
Coverage
TheONW-D-1001-347OccupancySensingWallSwitchisaPassiveInfrared(PIR)andUltrasonic(US)motion
sensinglightingcontrolandconventionalwallswitchall-in-one,usedforenergysavingsandconvenience.
ThesensorcombinesPIRandUStechnologiestomonitoraroomforoccupancy.
PIR Technology
Thesensor’ssegmentedlensdividesthefield-of-viewintosensorzones,anddetectsthechangesintemperature
thatarecreatedwhenaperson,orpartofapersonassmallasahand,passesintooroutofasensorzone.
US Technology
Thesensorproducesalowintensity,inaudiblesound.Itdetectsoccupancyfromchangesintheacousticwaves
causedbymotion,suchasreachingforatelephone,turningapageinabook,walkingintoaroom,turningina
swivelchair,etc.Thesensordoesnotrespondtoaudiblesound.
DualTechnologysensorsensurethegreatestsensitivityandcoveragefortoughapplicationsthussavingadditional
energy.PIRisusedtoturnthelightsONandtheneitherorbothtechnologiesareusedtokeepthelightsON.
TheONW-D-1001-347allowsthecontrolofoneloadwithoneoccupancysensorswitch.
ThesensorcanbeconfiguredtoenhanceenergysavingsbysettingtheunitforManualONoperation.
InAutomaticONMode,
thelightsturnONautomaticallywhenapersonenterstheroom.InManualONMode,the
lightsareturnedONbypressingtheuniversallyrecognizedlighticonpushbutton.Ineithermode,thelightsstayON
aslongasthesensordetectsmotionintheroom.Whentheroomisvacated,thelightsturnOFFautomaticallyaftera
presettimedelayinterval.
Thesensorincludesself-adaptivetechnologythatcontinuallyadjuststoconditionsbyadjustingsensitivityandtime
delayinreal-time.Byadjustingsensitivityandtimedelayautomatically,thesensorismaximizingthepotentialenergy
savingsthatareavailableintheparticularapplication.
TheDaylightingfeaturepreventslightsfromturningON,whentheroomisadequatelyilluminatedbynaturallight.
TheWalk-ThroughfeaturemaximizesenergysavingsbynotleavingthelightsONafteramomentaryoccupancy.
ThesensorwillswitchthelightsONwhenitdetectsapersonenteringthearea.Ifthesensordoesnotcontinueto
detectmotion20secondsfollowingtheinitialactivation,itwillautomaticallygotoashorter2minutetimedelay.
TheON/OFFButtonDisableOption–WhenselectedthisoptiondisablestheON/OFFbutton(s)andsensor
becomesautomaticonlycontrol.
TheONW-D-1001-347isdesignedforofficesupto300squarefeet.
Location
WheninstallingtheONW-D-1001-347inanewjunctionbox,choosetheswitchlocationcarefullytoprovideoptimum
coverageoftheoccupiedarea.Whenreplacinganexistingwallswitch,bearinmindthattheremustbeaclear
line-of-sightbetweenthesensorandtheareatobecovered.AvoidpointingtheONW-D-1001-347directlyintothe
hallwaywhereitmaydetectpassers-by.
Installation
TheONW-D-1001-347canbeinstalledinanystandardsinglegangbox.Itmay
beinstalledinthesamemannerasanordinarywallswitch.
• WiretheONW-D-1001-347asdescribedinthewiringsection
• MounttheONW-D-1001-347inthejunctionbox
Wiring
CAUTION: Before installing or performing any service on a Greengate system, the power MUST be turned
OFF at the branch circuit breaker. According to NEC 240-83(d), if the branch circuit breaker is used
as the main switch for a fluorescent lighting circuit, the circuit breaker should be marked “SWD.” All
installations should be in compliance with the National Electric Code and all state and local codes.
NOTE REGARDING COMPACT FLUORESCENT LAMPS: The life of some compact fluorescent lamps (CFLs) is
shortened by frequent automatic or manual switching. Check with CFL and ballast manufacturer to determine the
effects of cycling.
1. MakesurepoweristurnedOFFatthebranchcircuitbreaker.
2.Wireunitsasshowninwiringdiagramsperapplicablevoltagerequirements.
3.Mountunittowallbox.
4.TurnpowerbackONatthebranchcircuitbreakerandwait2minutesfortheunittostabilize.
5.Makenecessaryadjustments.(SeeCheckoutandAdjustmentssection)
6.Installwallswitchplate.
LOAD
347 VAC
BLACK
BLUE
NEUTRAL
GROUND
GREEN
Wiring Diagram 1:
347 VAC single level
single circuit wiring diagram
LOAD 1
347 VAC
BLACK
BLUE
NEUTRAL
GROUND
GREEN
LOAD 2
A/B SWITCHING USING TOGGLE
SWITCH TO TURN OFF SECOND LOAD
Wiring Diagram 2:
347 VAC single level switch
dual level wiring using a toggle
switch wiring diagram
,
36
8
,
Minor Motion, IR
Major Motion, IR
20
,
Maximum coverage area may
vary somewhat according to room
shape and the presence of obstacles.
The NEMA WD 7 Guide and robotic
method were utilized to verify
coverage patterns.
Minor Motion, Ultrasonic
Major Motion, Ultrasonic
,
10
8
,
,
15
20
,
P/N 9850-000314-01
Eaton’s Cooper Controls Business
203 Cooper Circle
Peachtree City, Georgia 30269
www.coopercontrol.com
Printed in Malaysia
Sensitivity Adjustments
Ultrasonic Sensitivity(GreenLED)–Usingasmallflatheadscrewdriverturnthe
greenpotentiometersothatthearrowpointsU P.
1. Standindifferentareasoftheroomandwaveyourhands.
2. IftheGreenLEDdoesnotturnON,increasetheUSsensitivitybyturningthe
greenpotentiometerclockwiseinsmallincrements.RepeatStep1.
3. Standstillthreetofourfeetawayfromsensorforfiveseconds.LEDshouldnot
turnON.
4. IfGreenLEDturnsONwithoutmotionorisconstantlyONdecreasethe
US sensitivitybyturninggreenpotentiometercounter-clockwiseinsmall
decrements.RepeatStep3.
Note:DoNotadjustsensitivityhigherthannecessary.
PIR Sensitivity
1. Standindifferentareasoftheroomandwaveyourhands.
2. IftheRedLEDdoesnotturnON,checkforanyobstructions.
3. Standstillthreetofourfeetawayfromsensorforfiveseconds.LEDshouldnot
turnON.
4. IfRedLEDturnsONwithoutmotionorisconstantlyONadjustPIRsensitivityto50%bymovingDIPSwitch5up.
Field-of-view outside the space
1. AdjustPIRsensitivityto50%bymovingDIPswitch5up.
2. Usenon-reflectivetapestripstocovertheportionsofthesensorlensthatviewoutsidethespace.
3. AdjustUltrasonicSensitivity.
ON/OFF Disabled Feature
1. ON/OFFButtonDisableOption–Whenselected
thisoptiondisablestheON/OFFbuttonandsensor
becomesautomaticonlycontrolregardlessofthe
settingforautomaticormanualactivation.Thisfeature
willnotallowsomeonetoturnlight(s)OFFviathe
pushbuttonwhilepeopleareincommonareassuchas
restroom,breakroomandcopyroomareas.
Daylight Adjustments
TheDaylightingfeaturepreventsthelightsfromturningONwhentheroomisadequatelyilluminatedbynaturallight.Ifthereis
enoughlightintheroomregardlessofoccupancy,thesensorwillholdthelightsOF F.Ifthereisnotenoughlightintheroom,the
sensorwillallowthelightstoturnONwhenoccupied.ThesensorwillnotallowtheDaylightingfeaturetoturntheloadOFFuntilthe
spaceisvacantorthelightlevelrisesabovethesetpointandthetimedelayexpires.WhileinManualActivationMode,ifsomeone
attemptstoturntheloadONandthereissufficientdaylightavailabletheDaylightingfeaturewillholdthelightsOF F.
1. Setthelightlevelwhentheambientlightisatthelevelwherenoartificiallightisneeded.Ifthisfeatureisnotneeded,leavethe
lightlevelatmaximum(fullyCW).
2. Withtheload(s)ON,putthesensorintoTestMode.ToplaceintoTestMode,toggleDIPswitch8outofitscurrentposition,wait
3secondsandthenbackintoitsoriginalposition.
3. Setthelightleveltominimum(fullyCCW).
4. Letthesensortime-outsolightsareOFF.Enterthe
spaceandlightsshouldremainOF F.
5. Makesurenottoblockthesensorfromthedaylight
sourceandadjustthelightlevelpotentiometerCWin
smallincrements.(Pause5secondsbetween
eachadjustment)
6. LightswillnotturnONuponoccupancyactivation,
whentheambientlightlevelexceedsthedaylight
thresholdsetting.
Time Delay Adjustments
Peoplewhoremainverystillforlongperiodsoftimemayneedalongertimedelaythanthedefaultsettingof10minutes.As
longastheself-adjustingfeatureisenabled,theswitchwillrespondtoeachpairoffalse-OFFswithnonormalOFFinbetween,by
alternatelymakingslightadjustmentstoeithertimedelay(by2minuteincrements)orsensitivity,sothereshouldbenoneedfor
manualadjustment.Ifmanualadjustmentisdesired,refertoTimeDelaysettingsinDIPswitchlegend.
ResetsensortimedelaytofactorysettingsbymovingDIPswitches1and2down.(IfDIPswitches1and2arealreadydown,
toggleDIPswitch1outofitscurrentposition,wait3seconds,andthenbacktoitsoriginalposition)
Override
TheOverridesettingallowsthesensortooperateasaserviceswitchintheunlikelyeventoffailure.
1. MoveDIPswitch12up.
2. ThepushbuttoncanbeusedtomanuallyturnlightsONorOFF.
Warranties and Limitation of Liability
DIP Switch Settings
Troubleshooting
Pleaserefertowww.coopercontrol.comundertheLegalsectionforourtermsandconditions.
Checkout and Adjustment
LOAD 1
BLACK
BLUE
NEUTRAL
THREE-WAY WIRING DIAGRAM:
LIGHTS WILL TURN OFF, WHEN UNIT THAT WAS TURNED ON LAST AND/OR DETECTED MOTION LAST TIMES-OUT.
GROUND
GREEN
347
VAC
BLACK
BLUE
GROUND
GREEN
TRAVELLER
WIRES
Wiring Diagram 3: 347 VAC single level single circuit three-way wiring diagram
CAUTION: If a room is wired for two circuits using two separate hot leads, it is very important to connect only one circuit
per relay. Both circuits must be fed from the same phase.
Issue Possible Causes Suggestions
Lights
Will Not
Turn ON
automatically
SensorisinManualONmode
Presspushbutton.IfAutoModeis
desiredchangeActivationModetoAuto.
SensorwasturnedOFFmanually.Ifthe
SensorwasturnedOFFmanuallybefore
thetimedelayexpired,lightswillremain
OFFfortheremainderofthetimedelay
PressthepushbuttontoturnthelightsbackON
DaylightingFeatureEnabled
IfalllightsarerequiredtoturnON
adjustdaylightpotentiometer
Powerinterruption Checkincomingvoltageand/orwiring
Lights
Will Not
Turn ON
manually
DaylightingFeatureEnabled
IfalllightsarerequiredtoturnON
adjustdaylightpotentiometer
Powerinterruption Checkincomingvoltageand/orwiring
ON/OFFButtonDisabled MoveDIPSwitch7down
If lights will still not turn ON, set sensor to override mode and call Technical Services at 1-800-553-3879
Lights
Will Not
Turn OFF
automatically
Override MakesuresensorisnotinOverrideMode
Self-Adjust
IfsensorisinSelf-AdjustMode,itmaybe
possiblefortheunittohaveincreasedthetime
delaytoa30minutedelay.Ifthelightsdonot
turnOFFafter30minutesfollownextstep.
30MinuteDelay
Maximumtimedelayis30Minutes.CheckDIP
SwitchestoverifyDIPSwitchsettings.Iflightsdo
notturnOFFatthesettimedelay,checknextstep
UltrasonicSensitivitysetHigh
Lowersensitivitybyturninggreen
potentiometerCCWinsmalldecrements
PIR
activatedbyheatsource
otherthanoccupant
MoveDIPSwitch5up
Lights
Will Not
Turn OFF
manually
CallTechnicalServices
ON/OFFButtonDisabled MoveDIPSwitch7down
If lights will still not turn OFF, call Technical Services at 1-800-553-3879
12345678
5 Minutes
15 Sec Test/Auto*
Time Delay
DIP Switch
Activation PIR Sensitivity Not UsedOverrideMaintain Lights On Not Used
Relay 1 Not Used
ON/OFF ButtonWalk-Through Mode
15 Minutes
12
DIP Switch Legend
121196
Disable
Enable
43
Auto
Manual
5
Full
50%
8
Enable
Disable
7
Disable
Enable
10
Either
Both
Default =
30 Minutes
*Self-Adjusts to
10 min. user
mode
9101112
AdjustmentsshouldbemadewiththeHVACsystemONsothattheinstallerwillbeabletodetecttheeffectofairflowonthe
operationoftheONW-D-1001-347.Useonlyinsulatedtoolstomakeadjustments.
Immediatelyafterapplyingpowertothelightingcircuit,waitapproximatelytwominutesfortheswitchtopower-upandstabilize.
Self-Adjust
Sensorisshippedinself-adjustmode.Thisappliestotime
delay,USandPIRsensitivity.InpreparationfortheInstaller
Test,thetimedelayissetto15seconds,afterthesensoris
installed,poweredONandhasstabilized,theunitwilltime-
out15secondsafterthelastmotiondetected.Coverageand
sensitivitycanbeconfirmedbywatchingtheGreen(US)and
Red(PIR)indicatorLEDsonthefrontofthesensor,while
movingaroundtheroom.
1. WalkaroundtheroomandmonitorLEDs.
2. Standindifferentpartsoftheroomandwaveyour
hands.LEDsshouldonlyturnONforonesecondwith
eachmotion.(IfLEDsdonotturnON,gotoInstaller
Adjustments–SensitivityAdjustmentSection)
3. Standstillthreetofourfeetawayfromsensorfor
fiveseconds.LEDsshouldnotturnON.(IfanyLED
turnsON,noteLEDandgotoInstallerAdjustments–
SensitivityAdjustmentssection)
4. Walkoutsidetheroomandwait15secondsforthelightstoturnOFF.(IflightsdonotturnOFFgotoInstaller
AdjustmentsSection)
5. Re-entertheroomtoactivatesensor.(IflightsdonotturnONgotoTroubleshootingSection)
6. Atthispointyoucanexittheroomandletthesensortime-out.Whenthesensortimes-outandisOFFwithpowerONforfive
minutes,theunitwillgotoa10minuteTimeDelayusermodesetting.
Note:ToplaceintoTestMode,toggleDIPSwitch12outofitscurrentposition,wait3seconds,andthenbackintoitsoriginalposition.
ON/OFF Button
PIR Lens
DIP Switches
Ultrasonic Detection
Daylight
Sensor Level
Adjustment
Ultrasonic
Sensitivity
Adjustment
Red (PIR) & Green (US)
Detection LEDs
1 and 2
12
345678
9101112
12345678
9101112
Installer Adjustments
  • Page 1 1
  • Page 2 2