Xtreme Power Conversion Corporaon
RELAY-MINI User’s Manual
Page 4
Dry Contact Card
Specicaons
Internal Circuit of DB9 port
DP9 Pin Assignment
Pin Assignment Funcon I/O
Pin 1 UPS Failure Output
Pin 2 UPS Summary Alarm Output
Pin 3 GND (Common for Pin 4) Power Ground
Pin 4 Remote Shutdown Input
Pin 5 Common for relays Power Supply
Pin 6 Bypass Acve Output
Pin 7 Baery Low Output
Pin 8 UPS On Output
Pin 9 Ulity Failure Output
All relays are rated at 24V, 1A. The shutdown pin (pin4 & pin3) only accepts 3-10s high level signal to perform the
UPS shutdown. Signal limited to 6V, 6mA. Otherwise, it’s necessary to add one resistor within DC current limitaon
in the serial loop of Remote Shutdown. (e.g. 2K resistor with at least 0.1W rang power). Refer to the diagrams in
Applicaon.
Relay Funcon Descripon
Acve Closed Status Acve Open Status Reason
Pin 1 & Pin 5 closed Pin 1 & Pin 5 open UPS internal failure
Pin 2 & Pin 5 closed Pin 2 & Pin 5 open UPS failure, ulity failure, low baery, bypass acve
Pin 6 & Pin 5 closed Pin 6 & Pin 5 open Bypass acve
Pin 7 & Pin 5 closed Pin 7 & Pin 5 open Baery voltage is low
Pin 8 & Pin 5 closed Pin 8 & Pin 5 open UPS is in online/double conversion mode
Pin 9 & Pin 5 closed Pin 9 & Pin 5 open Ulity failure/on baery mode