Liebert Hinet 15kVA User manual

Category
Uninterruptible power supplies (UPSs)
Type
User manual

This manual is also suitable for

Manual Reference number : 6390001 H - 2 (12/01) Rev ENP Au 07/2002
H
H
I
I
N
N
E
E
T
T
U
U
P
P
S
S
S
S
Y
Y
S
S
T
T
E
E
M
M
1
1
0
0
3
3
0
0
k
k
V
V
A
A
3
3
x
x
1
1
U
U
s
s
e
e
r
r
M
M
a
a
n
n
u
u
a
a
l
l
(08/01) Page I
This manual describes Hinet Series UPS with the following P.N. :
Part Numbering System
HNLCD- XX X X X X X X X
Free Option
0 = No additional option
1 = SNMPE3 card
Insulation Transformer
0 = No Ins. Transformer
1 = Ins. Transf. for 10kVA Unit
2 = Ins. Transf. for 20kVA Unit
3 = Ins. Transf. for 30kVA Unit
Frequency Converter
0 = No Frequency Converter
1 = Frequency Converter
3° Harmonic Filter
0 = No 3° Harmonic Filter
1 = 3° Harmonic Filter
THDi Reduction Filter
0 = No THDi Reduction Filter
1 = THDi filter for 10kVA Unit
2 = THDi filter for 15-20kVA Unit
3 = THDi filter for 30kVA Unit
Internal Batteries
0 = No Internal Battery
1 = 1 Battery String
2 = 2 Battery Strings
3 = 3 Battery Strings
4 = 4 Battery Strings
Output Power
0 = 10kVA
1 = 15kVA
2 = 20kVA
3 = 30kVA
Model
33 = 3 Phase-Input, 3 Phase-Output
31 = 3 Phase-Input, 1 Phase-Output
IMPORTANT
All models in the UPS range are similar in both operation and use.
Hinet UPS System USER MANUAL
Page II (12/01)
Options Part Numbers
OPTIONS (Rev 07/2002)
Description Part Number
Hinet Internal Extended Battery Kit HNINTBATT
Hinet Battery Connecting Kit HNBATTCABLE
Hinet External Battery Cabinet HNBATTCAB
38Ah, 5 Years Batteries for External Battery Cabinet (32 Bloks x 12V ) HN38AH5Y
65Ah, 5 Years Batteries for External Battery Cabinet (32 Bloks x 12V) HN65AH5Y
Hinet Additional Communications Card Kit (Relays) HNRELAYCARD
Hinet Communication SNMP card SNMPE3
Remote Alarm Monitor HNRAM
PLEASE NOTE:
These products are intended for Commercial/Industrial use only, and are not
suitable for use in any life supporting applications.
USER MANUAL Hinet UPS System
(12/01) Page III
IMPORTANT INSTRUCTIONS FOR SAFE USE
? The UPS must be commissioned by a Liebert approved engineer before it is put into service. Failure to observe this
condition will invalidate any implied warranty.
? Do not apply power to this equipment before it has been commissioned by a Liebert approved engineer. This
information is required to substantiate any warranty claims that might be made.
? If you encounter any problems with the procedures contained in this manual you should seek immediate assistance
from the Liebert Sales Office from whom the equipment was purchased. Alternatively, contact the Liebert's Customer
Service & Support department at the address shown below:
Liebert Hiross Service
Customer Service and Support Department
Via Risorgimento 16
20098 S. Giuliano M.se
Milan - Italy
Telephone +39 (0) 298250310
Fax +39 (0) 298250346
This department also arranges service contracts and full commissioning service.
? These units contain no user serviceable parts.
? Due to risk of electrical shock or burn do not attempt to gain internal access
? The UPS is for indoor use only.
It must be protected from rain or excessive moisture and installed in a clean environment, free from flammable liquids,
gasses, or corrosive substances.
Do not put drinks, plants, or any other containers holding liquids, on top of the unit.
? Competent personnel must be consulted if liquid spills into the product.
? Ventilation grills are provided beneath and at the front of the cabinet. Do not block or cover these openings otherwise
overheating may occur and UPS operation become unreliable.
Never insert any object into these ventilation holes or openings.
? Do not place magnetic storage media on top of the unit as it can corrupt the data stored on them.
WARNING
This is a CLASS A Uninterruptible Power Supply (UPS) product. In a domestic environment, this product
may cause radio interference, in which case, the user may be required to take additional measures.
? Storing:
Should the equipment not be installed immediately it must be stored in a room so as to protect it against excessive
humidity (not higher than 90%) and against very high heat sources (not higher than +40°C), and moistureless.
CAUTION: Additionally, make sure that not more than 6 months passed from the time the battery had last been
recharged.
After such period temporarily connect the UPS to mains and activate it for the time required to recharge the batteries.
Hinet UPS System USER MANUAL
Page IV (12/01)
? Batteries:
The following general battery safety precautions and WARNINGS must be observed at all times:
a) Particular attention should be paid to the recommendations concerning local environmental conditions and the
provision of protective clothing, first aid and fire-fighting facilities.
b) A battery can present risk of electric shock or burn from high short circuit currents.
c) When connected in a string the voltage could be 400V d.c.. This voltage is potentially lethal. Always observe high
precautions.
d) Only qualified personnel must install or service batteries.
e) Eye protection must be worn to prevent injury from accidental electrical arcs.
f) Remove rings, watches, necklace’s, bracelets and all metal objects.
g) Only use tools with insulated handles.
h) Wear rubbers gloves and a rubber apron when handling batteries.
i) If a battery leaks electrolyte, or is otherwise physically damaged, it must be placed in a container resistant to
sulphuric acid and disposed of in accordance with local regulations.
j) If electrolyte comes into contact with the skin the affected area must be washed immediately with clean water.
k) Batteries must always be disposed of according to local environmental laws.
Guide to the Instructions
The warning triangle indicates all the personal safety instructions.
Follow these instructions carefully to avoid injury.
USER MANUAL Hinet UPS System
(12/01) Page V
Hinet UPS System USER MANUAL
Page VI (12/01)
Table of Contents
1 GENERAL DESCRIPTION..........................................................................................................................................1
1.1 INTRODUCTION...........................................................................................................................................................1
1.2 EQUIPMENT CONSTRUCTION.......................................................................................................................................1
1.2.1 Principle of operation ...................................................................................................................................... 2
1.2.2 UPS Power Configuration............................................................................................................................... 3
1.2.3 Battery fuses switch..........................................................................................................................................3
2 INSTALLATION (MECHANICAL) ...........................................................................................................................5
2.1 PRELIMINARY CHECKS ...............................................................................................................................................5
2.1.1 Material admittance......................................................................................................................................... 5
2.1.2 Identification..................................................................................................................................................... 5
2.1.3 Packing material removal................................................................................................................................ 5
2.1.4 Moving the cabinets .........................................................................................................................................5
2.1.5 Placing it in the operative position.................................................................................................................. 5
2.1.6 Clearances........................................................................................................................................................6
2.1.7 Raised floor installation................................................................................................................................... 6
2.1.8 Cable entry ....................................................................................................................................................... 6
2.1.9 UPS Mechanical Characteristics..................................................................................................................... 6
3 INSTALLATION (ELECTRICAL) .............................................................................................................................7
3.1 POWER CABLING ........................................................................................................................................................7
3.1.1 Power Cable connections................................................................................................................................. 7
3.1.2 Safety earth....................................................................................................................................................... 7
3.1.3 Protective devices............................................................................................................................................. 7
3.2 SETTING STANDARD RELAY CARD.............................................................................................................................9
3.2.1 Setting options on the standard Relay Card....................................................................................................9
3.2.2 Remote EPO (Emergency Power Off)............................................................................................................10
3.2.3 Emergency Power Off (E.P.O.) push-button connection ..............................................................................10
3.2.4 Connection to Personal Computer................................................................................................................. 10
3.2.5 UPS Monitoring.................................................................................................................................................... 11
4 OPERATOR CONTROL PANEL .............................................................................................................................13
4.1 INTRODUCTION.........................................................................................................................................................13
4.2 LCD CONTROL PANEL..............................................................................................................................................14
4.2.1 Control panel indicator LEDs........................................................................................................................ 14
4.2.2 STATUS ALARM MENU................................................................................................................................ 16
4.2.3 COMMAND MODE MENU ..........................................................................................................................17
4.2.4 EVENT HISTORY MENU.............................................................................................................................. 18
4.2.5 OPERATING LANGUAGE MENU ............................................................................................................... 19
4.2.6 CLOCK MENU...............................................................................................................................................19
4.2.7 UPS SETTING MENU................................................................................................................................... 19
5 OPERATING INSTRUCTIONS ................................................................................................................................21
5.1 INTRODUCTION.........................................................................................................................................................21
5.2 POWER SWITCHES ....................................................................................................................................................21
5.2.1 UPS Start-Up instructions..............................................................................................................................22
5.2.2 Inverter Turn-on and LCD panel LEDs activation .......................................................................................22
5.2.3 Load insertion test.......................................................................................................................................... 22
5.2.4 Hinet UPS switch-off Procedure.................................................................................................................... 23
5.2.5 Manual bypass procedure.............................................................................................................................. 23
5.2.6 Return from Manual Bypass to normal Operation........................................................................................ 24
5.2.7 Emergency Power Off (EPO)......................................................................................................................... 24
6 TECHNICAL SPECIFICATION...............................................................................................................................25
7 OPTIONAL EQUIPMENT.........................................................................................................................................28
7.1 COMMUNICATION CARD KIT (RELAYS)....................................................................................................................28
USER MANUAL Hinet UPS System
(12/01) Page VII
7.2 SNMP CARD............................................................................................................................................................28
7.3 UPGRADE KIT ...........................................................................................................................................................28
7.4 ISOLATION TRANSFORMER (INTERNAL OPTION).....................................................................................................28
7.5 INPUT FILTER FOR CURRENT THD REDUCTION (INTERNAL OPTION)......................................................................28
7.6 INPUT 3° HARMONICS FILTER (INTERNAL OPTION)..................................................................................................28
7.7 INTERNAL EXTENDED BATTERY KIT........................................................................................................................28
7.8 BATTERY CONNECTING KIT .....................................................................................................................................28
7.9 EXTENDED BATTERY CABINET ................................................................................................................................29
7.10 BATTERIES FOR EXTERNAL BATTERY CABINET .......................................................................................................30
7.11 REMOTE ALARM MONITOR......................................................................................................................................31
7.12 FREQUENCY CONVERTER.........................................................................................................................................32
8 LIMITED WARRANTY .............................................................................................................................................33
Hinet UPS User Manual
(12/01) Page 1
1 General Description
1.1 Introduction
This chapter describes the purpose, principle of operation and user controls of the Hinet series on-line Uninterruptible
Power Supply (UPS).
The Hinet series UPS is connected between a critical load, such as a computer, and the mains. Its purpose is to provide
the load with regulated power under all rated load and input supply conditions; i.e. the power provided by the UPS will
be protected from any voltage or frequency variations on the input power supply, or variations in the supply due to
electrical noise, and will continue during periods of input power supply failure. A battery provides a standby power
source for the UPS when the input power supply fails.
1.2 Equipment construction
The equipment is constructed around a steel frame with removable panels. The door can be open to give easy access to
the input, bypass, output, reserve line circuit breakers and battery C.B. fused switch, while protecting them from
accidental operation.
An LCD control panel on the front of the cabinet permits the operator to monitor the UPS.
The cabinet houses both the power components and the batteries.
It is carried on four wheels. Jacking feet help to support the UPS, and also prevent it from moving once it has been
wheeled into its final position. These feet are also used to secure the equipment to its shipping pallet during transit.
Cooling is by internal fan. Air is drawn in from beneath the UPS and exhausted through ventilation grills of the front
panel. These areas must be kept free of anything that may avoid the air flow into and out of the unit.
Figure 1-1 Front view of the Hinet cabinet. Note the location of the Operator control panel
EMERGENCY
Hinet
NORMAL
ALARM
LOAD ON INVERTER
LOAD ON BYPASS
NEXT
BACK
MENU
CLEAR
ENTER
Hinet UPS User Manual
Page 2 (12/01)
1.2.1 Principle of operation
Normal operation
During normal operation, i.e. when the UPS input supply is present and within specification, both the converter and
inverter sections are active and the automatic by-pass is turned on to connect the inverter output to the critical load
terminals. The battery fuse-holder switch is also closed and the battery is therefore permanently float charged at the d.c.
terminals voltage level.
Mains Failure
If the mains has a failure or is out of tolerance the converter will be supplied from the battery, while the inverter will
continue to operate for a period of time which depends on the load and the capacity of the battery. If the mains supply
has not returned within this time, the inverter will go off automatically and an alarm condition will appear on the UPS
operator control panel.
Critical load will not be interrupted in the event of a drop or return of the AC power mains.
Return of power mains
When the mains returns within the required tolerance, the converter will be automatically supplied from mains,
supplying power to the inverter and recharging the battery at the same time. There will be no interruption of the critical
load.
UPS fault
In the event of an inverter failure, the automatic by-pass will automatically transfer the load onto the mains with no
interruption. In such an event, request qualified technical assistance.
The load will be transferred with no interruption if the inverter is synchronised with the mains; if this is not the case,
there will be an interruption of some milliseconds.
The intervention of the automatic by-pass line is shown on the front panel by the yellow led on.
WARNING
CAUTION: When the load is being supplied from the bypass line through the automatic bypass, it is connected
directly to the mains supply and is therefore no longer protected against main faults.
Maintenance Bypass
A second bypass circuit contained in the UPS cabinet, identified as the ‘Maintenance Bypass’ line is included to enable
the reserve supply to be made available to the load while facilitating a safe working environment for carrying out
scheduled UPS system maintenance or trouble shooting. The circuit is manually selected by the Manual Bypass Switch
(3) which can be padlocked in the OFF position.
WARNING
CAUTION: If an automatic circuit breaker device is not present in the input distribution panel, there remains a
dangerous voltage at the output terminals and also on the input terminals of the UPS module that is switched off.
Note: The load is not protected from main aberrations when operating on the maintenance bypass mode .
Hinet UPS User Manual
(12/01) Page 3
Figure 1-2 Hinet’s “Common Bypass” configuration
LEGENDA
?
INPUT MAINS SWITCH
?
RESERVE LINE SWITCH (Bypass)
?
MAINTENANCE BYPASS SWITCH
?
UPS OUTPUT SWITCH
?
BATTERY FUSES SWITCH
?
STEP-UP CONVERTER
?
INVERTER
?
AUTOMATIC BYPASS
?
BATTERY
??
EXTERNAL BATTERY PLUG
These links must be removed for split bypass
1.2.2 UPS Power Configuration
Figure 1-2 illustrates the Hinet UPS in what is known as the “Common Bypass” configuration. In the “Split Bypass”
configuration the static bypass line is connected by a separate power switch to a dedicated `bypass' power source that
also feeds the maintenance bypass line. Where a separate power source is not available the Reserve and Converter input
supply connections would be linked together.
With the exception of the maintenance bypass switch (3), all the isolators shown must be closed during normal UPS
operation.
1.2.3 Battery fuses switch
The battery is connected to the d.c. bus through a battery fuses switch (5) fitted inside the UPS cabinet.
UP
Output
UP
Input
UPS
Hinet UPS User Manual
Page 4 (12/01)
Hinet UPS User Manual
(12/01) Page 5
2 Installation (Mechanical)
2.1 Preliminary Checks
Before installing the UPS hardware the following preliminary checks must be carried out:
1. Verify that the UPS room satisfies the environmental conditions stipulated in the equipment specification, paying
particular attention to the ambient temperature and air exchange system.
2.1.1 Material admittance
1. Remove any packaging debris, then visually examine the UPS and battery equipment for transit damage, both
internally and externally. Report any such damage to the shipper immediately.
2. Afterwards ascertain that the material supplied is as that reported on the freight bill.
2.1.2 Identification
The equipment supplied is provided with an adhesive identification label placed on the UPS rear panel reporting type of
UPS model and power.
The cases utilised to transport the equipment must be unpacked as specified by the procedure stated below.
2.1.3 Packing material removal
During this operation observe the indications (FRAGILE, UP) printed on the case to avoid damaging the UPS Hinet.
To remove the packing material proceed in the following manner:
- Place the equipment on the floor as instructed on the outer case (UP, DOWN).
- Use the extractor to remove the top of the crate .
- Remove the extruded elements utilised as packing protection.
- Use the extractor to remove all lateral sides of the crate
- Slide the forks of the lift truck under the UPS and after having lifted it a few centimeters from the floor, back up and
lay it down.
Hinet is provided with wheels to easily move it around.
- Do not throw away the packing material it might be used again to repack the equipment if having to send it back or to
send it to maintenance centres or for removal purposes.
- Check that the equipment has not been damaged. If otherwise immediately contact the Sales Representative.
2.1.4 Moving the cabinets
WARNING
Ensure that any lifting equipment used for moving the UPS cabinet has sufficient lifting capacity.
ENSURE THAT THE UPS WEIGHT IS WITHIN THE DESIGNATED WEIGHT LOADING (KG) OF ANY
HANDLING EQUIPMENT. SEE THE UPS SPECIFICATION FOR WEIGHT DETAILS.
The UPS can be lifted using a fork lift. Take care when using either method not to damage the UPS castors located on
the bottom of the unit.
2.1.5 Placing it in the operative position
The UPS cabinets are fitted with castors on the base to allow ease of movement and positioning.
WARNING
Castors are of sufficient strength for movement across even surfaces only. Castor failure could occur if subjected to
shock loading
When the equipment has been finally positioned ensure the adjustable feet are set so that the UPS will remain stationary
and stable
The place chosen must guarantee:
- easy connection;
Hinet UPS User Manual
Page 6 (12/01)
- enough space to easily work on UPS;
- exchange of air sufficient enough to dispel heat produced by UPS;
- protection against atmospheric agents;
- protection against excessive humidity and very high heat sources;
- protection against dust;
- compliance with the current fire prevention norms.
- operative environment temperature within +20° C and +25° C. The batteries are at maximum efficiency in this
temperature range.
2.1.6 Clearances
Cooling air enters the module through ventilation grills located at the bottom of the cabinet and is exhausted through the
fan grills located on the front panel; you must therefore allow for a minimum gap of 170 mm behind the unit to allow
adequate air flow. Clearance around the front of the equipment should be sufficient to enable free passage of personnel
with the door fully opened.
2.1.7 Raised floor installation
If the equipment is to be located on a raised floor it must be mounted on a pedestal suitably designed to accept the
equipment point loading. Refer to the base view to design this pedestal.
2.1.8 Cable entry
Cables can enter for 'Hinet' UPS cabinet from rear side.
2.1.9 UPS Mechanical Characteristics
MECHANICAL
CHARACTERISTICS
UNITS
Rated power kVA 10 15 20 30
Height
mm 1220
Width
mm 530
Depth
mm 950
Weight:
Hinet cabinet
185
with 1 battery strings
275
with 2 battery strings
365
with 3 battery strings
Kg
455
with 4 battery strings
545
Unit Shipping Weight
With Standard Battery
320 410 410 500
Colour
RAL 7035 Metal Covers
RAL 7042 Plastic Door
Ventilation
- forced
Air flow full speed
Air flow half speed
m
3
/h
600
300
Protection grade
- IP 20
Cable entry
- Bottom
Hinet UPS User Manual
(12/01) Page 7
3 Installation (Electrical)
The UPS requires «power» cabling once it has been mechanically installed. All «auxiliary» cables, whether screened or
not, should be run separate from the power cables in metal conduits or metal ducts which are electrically bonded to the
metalwork of the cabinets to which they are connected.
3.1 Power Cabling
WARNING
BEFORE CABLING-UP THE UPS, ENSURE THAT YOU ARE AWARE OF THE LOCATION AND OPERATION
OF THE EXTERNAL ISOLATORS THAT CONNECT THE UPS INPUT/BYPASS SUPPLY TO THE MAINS
DISTRIBUTION PANEL.
CHECK THAT THESE SUPPLIES ARE ELECTRICALLY ISOLATED, AND POST ANY NECESSARY WARNING
SIGNS TO PREVENT THEIR INADVERTENT OPERATION.
3.1.1 Power Cable connections
The terminal block is at the rear of the cabinet.
The bar near the terminals blocks can be used to fasten the cable to the UPS through cable clamps.
3.1.2 Safety earth
The safety earth bus-bar is located near the UPS output terminals. The safety earth cable must be connected to the earth
terminal and bonded to each cabinet in the system.
All cabinets and cable trunking must be earthed in accordance with local regulations.
WARNING
FAILURE TO FOLLOW ADEQUATE EARTHING PROCEDURES CAN RESULT IN ELECTRIC SHOCK
HAZARD TO PERSONNEL, OR THE RISK OF FIRE, SHOULD AN EARTH FAULT OCCUR.
BEFORE ANY OTHER CABLE CONNECTION THE PE SAFETY CONDUCTOR SHALL BE CONNECTED
3.1.3 Protective devices
Input supply protection:
All supplies to the UPS must be provided with three phase power breakers or fuses, a split bypass system will require
two devices. To avoid random tripping on start up due to initial inrush current, a circuit Breaker type C (or slower) is
recommended. Refer to the following table in order to choose site supply fuses, circuit breakers and power isolators
appropriate to the UPS current rating.
Protection against earth faults (RCD devices):
In the event of a differential (RCD) device being installed upstream of the input supply, one must take into account the
transient and steady state earth leakage currents that are produced during start-up of the UPS.
The presence of an RFI suppression filter inside the UPS, determines a residual earth current no greater than 500 mA.
Only RCD delayed device Type A must be used (suited to unidirectional current).
Model Rating 10kVA 15kVA 20kVA 30kVA
Max input current at Nominal Input
Voltage (including battery charger)
16.7A 25.3A 33.5A 50.5A
Hinet UPS User Manual
Page 8 (12/01)
Figure 3-1 Wiring on the UPS Hinet.
1) Ground (Onto this terminal connect the
ground wire incoming from the UPS input
mains power supply)
2) Input Mains phase U1
3) Input Mains phase V1
4) Input Mains phase W1
5) Input Mains Neutral N1
6) Input Reserve (Bypass) phase U3
7) Input Reserve (Bypass) Neutral N3
8) Battery Positive (ext. Battery input)
9) Battery Negative (ext. Battery input)
10) Output UPS phase U2
11) Output UPS Neutral N2
12) Ground (ground lead towards users)
NOTE
Note:. the maximum cable size that can be connected to the UPS power terminal blocks is 35 mm²
N
L1
L2
L3
Hinet UPS User Manual
(12/01) Page 9
3.2 Setting standard Relay Card
The pre-settings required are only those which concern the interfaces wiring the external devices, i.e., personal
computer, safety switch, remote panel.
3.2.1 Setting options on the standard Relay Card
A standard Relay Card is situated on Hinet’s on the left side of the rear panel. This card is typically supplied and is
factory pre-set to operate with the PC.
When the operation is through the Remote Alarm Panel, the factory will deliver the card already preset to operate with
the cited panel.
A second card will be available on request on the right side of the rear panel.
Figure 3-2 Setting options on the standard Relay card
FUNCTION
JUMPER CLOSED JUMPER OPEN
Use With PC
JP4 JP5
Use With Remote Panel
JP5 JP4
EPO Enabled
- JP6
EPO Disabled
JP6 -
JP1 -
Serial Communication
JP2 -
JP3 -
Hinet UPS User Manual
Page 10 (12/01)
3.2.2 Remote EPO (Emergency Power Off)
A connection is provided for a switch, which can be located remotely from the UPS, and which has the same function as the internal
EPO switch. When it is operated it shuts down the inverter, and inhibits the static switch so that power is removed from the load.
WARNING
Pressing the Remote EPO pushbutton will turn the inverter off and remove power from the load.
The mains input, bypass input and battery terminals still carry lethal voltages after pressing the EPO switch. Do not remove cover
from these parts. Only competent personnel must remove protection panel held in place with screws.
3.2.3 Emergency Power Off (E.P.O.) push-button connection
Refer to figure 3-2 to make a push-button connection to the standard Relay Card.
1. Get a suitably long (not more than 100 m.) two-wire cable (0.6 sq. mm cross section)
2. Connect one end of the cable to the N.C. pins of a fire preventing button (Fig. 3-2).
3. Connect the other end to the standard Relay Card connector M2.
3.2.4 Connection to Personal Computer
The Hinet UPS contains a standard DB9 Female connector located on the rear of the UPS .
Several signals are provided on this port and assigned as follow:
PIN Description
1 Low Battery (N.O.)
2
UPS TxD (typical RS-232 levels)
3
UPS RxD (typical RS-232 levels)
4 N.C.
5 Common
6 N.C.
7 Low Battery (N.O.)
8 Mains Fail (N.O.)
9 Mains Fail (N.O.)
PIN ASSIGNMENT
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43

Liebert Hinet 15kVA User manual

Category
Uninterruptible power supplies (UPSs)
Type
User manual
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI