Xtreme R90 User manual

Category
Uninterruptible power supplies (UPSs)
Type
User manual
R90 Online UPS
20kVA Model
User & Installaon Manual
www.xpcc.com | © 2015 Xtreme Power Conversion Corporaon. All rights reserved. (Rev 8/19/15)
Xtreme Power Conversion Corporaon
R90 Users Manual
Page 2
Uninterrupble Power Supply
Table of Contents
Introducon.................................................................................................6
Product Descripon..................................................................................... 6
Main Features..................................................................................................................................6
System Conguraon...................................................................................7
Unpacking the UPS..........................................................................................................................7
Installaon Notes.......................................................................................................................... 10
External Protecve Devices...........................................................................................................10
Power Cables.................................................................................................................................11
Power Cables Connecon............................................................................................................. 11
Baery Connecon....................................................................................................................... 13
UPS Mul-Module Installaon.......................................................................................................15
Operaon...................................................................................................18
Operaon Modes..........................................................................................................................18
Turn On / O the UPS....................................................................................................................19
Communicaon Port Denions (RS232, RS485)..........................................................................25
The Display....................................................................................................................................26
Display Messages.......................................................................................................................... 41
Opons..........................................................................................................................................43
Troubleshoong.........................................................................................44
Baeries.....................................................................................................45
Replacing The Baery....................................................................................................................45
Specicaons.............................................................................................46
Baery Runmes Using EBP32...................................................................47
Shipping List.............................................................................................. 47
Obtaining Service.......................................................................................48
Xtreme Power Conversion Limited Warranty..............................................49
Xtreme Power Conversion Corporaon
R90 Users Manual
Page 3
Uninterrupble Power Supply
Thank you for selecng this uninterrupble power supply (UPS). It provides you with protecon for connected
equipment. Please read this manual before installing the R90-20KVA model as it provides important informaon
that should be followed during installaon and maintenance of the UPS and baeries, allowing you to correctly
set up your system for the maximum safety and performance. Included is informaon on customer support and
service, if it is required. If you experience a problem with the UPS, please refer to the Troubleshoong secon in
this manual to correct the problem. If the problem is not corrected, please collect informaon so that the Technical
Support personnel can more eecvely assist you.
Xtreme Power Conversion Corporaon
R90 Users Manual
Page 4
Uninterrupble Power Supply
Important Safety Instrucons: (Save These Instrucons)
CAUTION! (UPS having Internal Baeries): Risk of electrical shock – Hazardous live parts inside this unit are ener-
gized from the baery supply even when the input AC power is disconnected.
CAUTION! (No User serviceable Parts): Risk of electrical shock, do not remove cover. No user serviceable parts
inside. Refer servicing to qualied service personnel.
CAUTION! (Non-isolated Baery supply): Risk of electric shock, baery circuit is not isolated from AC input, haz-
ardous voltage may exist between baery terminals and ground. Test before touching.
WARNING! (Fuses): To reduce the risk of re, replace only with the same type and size of fuse.
WARNING! Unit intended for installaon in a controlled environment.
CAUTION! Do not dispose of baeries in a re, the baery may explode.
CAUTION! Do not open or mulate the baery, released electrolyte is harmful to the skin and eyes.
CAUTION! A baery can present a risk of electric shock and high short circuit current. The following precauon
should be observed when working on baeries:
Remove watches, rings or other metal objects.
Use tools with insulated handles.
To reduce the risk of electric shock, disconnect the UPS from the main supply before installing a computer inter-
face signal cable. Reconnect the power cord only aer signaling interconnecons have been made.
Servicing of baeries should be performed or supervised by personnel with knowledge of baeries and the re-
quired precauons. Keep unauthorized personnel away from baeries.
These UPS units are extremely heavy. Cauon should be taken in moving and posioning equipment.
The instrucons contained within this safety manual are deemed important and should be closely followed at all
mes during installaon and follow-up maintenance of the UPS and baeries.
Xtreme Power Conversion Corporaon
R90 Users Manual
Page 5
Uninterrupble Power Supply
CAUTION
The unit has a dangerous amount of voltage. If the UPS indicator is on, the units outlets may have a
dangerous amount of voltage even when not plugged into the wall outlet because the baery may con-
nue to supply power.
Care should be taken to undertake installaon indoors, free from electrically-conducve parcles which
are under temperature and humidity control, in order to reduce the risk of electric shock.
It is best to disconnect the device using the power supply cord. Ensure that the equipment is placed in
a posion near the outlet where easily accessible.
Except for replacing the baeries, all servicing on this equipment must be carried out by qualied ser-
vice personnel.
Before conducng any maintenance, repair, or shipment, rst ensure that everything is turned o com-
pletely and disconnected.
For addional safety instrucons, please use the Safety Manual as a reference.
Special Symbols
The following symbols used on the UPS warn you of precauons:
RISK OF ELECTRIC SHOCK - Please observe the warning that a risk of electric shock is present
CAUTION: REFER TO OPERATOR’S MANUAL - Refer to the operators manual for addional informaon,
such as important operang and maintenance instrucons.
SAFE GROUNDING TERMINAL - Indicates primary safe ground
Please do not discard of the UPS or the UPS baeries as the UPS may have valve-regulated lead-acid bat-
teries. Please recycle baeries appropriately.
Xtreme Power Conversion Corporaon
R90 Users Manual
Page 6
Uninterrupble Power Supply
Introducon
The informaon provided in this manual covers three-phase 20kVA uninterrupble power systems, its basic func-
ons, operang procedures, opons available and emergency situaons. It also includes informaon on how to
ship, store, handle, and install the equipment. Only detailed requirements of the UPS units are described herein,
and installaon must be carried out in accordance with this manual. Electrical installaon must also carefully
follow local legislaon and regulaons. Only qualied personnel should conduct these installaons as failure to
acknowledge electrical hazards could prove to be fatal.
Product Descripon
Many dierent kinds of sensive electrical equipment can be protected by an Uninterrupble Power Supply (UPS)
including computers, workstaons, process control systems, telecommunicaons systems, sales terminals, other
crical instrumentaon, etc. The purpose of the UPS is to protect these systems from poor quality ulity power,
complete loss of power, or other associated problems.
Electrical interference exists in many forms, causing problems in AC power, from lightning, power company ac-
cidents and radio transmission motors, air condioners, and vending machines. Protecon of sensive electrical
equipment is vital to protect against power outages, low or high voltage condions, slow voltage uctuaons,
frequency variaons, dierenal and common-mode noise, transients, etc.
To prevent power line problems from reaching crical systems causing damage to soware, hardware, and equip-
ment malfuncons, the UPS maintains constant voltage, isolang crical load output and cleaning the ulity AC
power.
Main Features
This is a three phase input / three phase output high-frequency online UPS. The UPS protects against power fail-
ures, power sag, power surge, under-voltage, over-voltage, line noise, frequency variaons, switching transients,
and harmonic distoron which can all cause crical problems to supported sensive electronic equipment in the
market today.
Funcons and Features
3 phase input/output high-density UPS
Digital Control
o The UPS is controlled by Digital Signal Processor (DSP) which increases reliability, performance,
self-protecon, self-diagnoscs, etc.
Modular Design
Baery Conguraon
o The baery voltage can be congured based on needs
Charging Conguraon
o The charging current can be customized to meet site requirements
Intelligent Charging Method
o 1st stage = high current constant current charging to restore baeries to 90% capacity
o 2nd stage = constant current charging to assure baeries remain fully charged
o 3rd stage = oat charge
The 3-stage charging method extends the life of the baeries and guarantees rapid recharging
LCD Display
o Both LED and LCD displays allow for ease of use and availability of crical UPS status and opera-
onal parameters, including: input/output voltage, frequency and load %, baery %, ambient tem-
Xtreme Power Conversion Corporaon
R90 Users Manual
Page 7
Uninterrupble Power Supply
perature, etc.
EPO Funcon
System Conguraon
The UPS device and the internal baeries make up the system. Depending on the site and load requirements of the
installaon, certain addional opons are available for the soluon.
Planning a UPS system, the following should be taken into consideraon:
The total demand of the protected system shall dictate the output power rang (VA). Allow a margin for
future expansion or calculaon inaccuracies from measured power requirements.
Backup me required will indicate the baery size needed. If the load is less than the UPS nominal power
rang, then actual backup me is longer.
The following opons are available:
o Connecvity Opons –SNMP/WEB card
o Extended Baery Packs - minimum 1 required
See the Specicaon secon of this manual for addional model informaon.
Unpacking the UPS
1. Do not lean the UPS against anything when moving it out of the packaging.
2. Check the physical appearance of the UPS to see if it was damaged during transportaon. Do not switch on the
UPS if damage is found. Please contact your dealer or distributor immediately for assistance.
3. Check the accessories according to the packing list to assure that you have all required pieces.
R90-20K front view
R90-20KVA rear view diagram
Xtreme Power Conversion Corporaon
R90 Users Manual
Page 8
Uninterrupble Power Supply
EBP32 rear panel
R90-20K UPS + R90-EBP32 mounted in a rack
Xtreme Power Conversion Corporaon
R90 Users Manual
Page 9
Uninterrupble Power Supply
Shelf shipped with UPS & EBP32 for mounng in a rack
Note: this shelf must be used in order to support the weight of the equipment. Do not install UPS or EBP32 into a
rack without using this shelf
Front panel
Xtreme Power Conversion Corporaon
R90 Users Manual
Page 10
Uninterrupble Power Supply
Installaon Notes
Place the UPS in a clean, stable environment, avoiding vibraon, dust, humidity, ammable gas and liquid,
corrosive objects, etc. Check the operang temperature of the room where the UPS is being installed to
assure it is within range of UPS specicaon.
Baeries should be installed in an environment where the temperature is within the required specica-
ons of the product. Temperature is a major factor in determining baery life and capacity. Normal baery
installaon requires the temperature be maintained from 15°C to 25°C. Keep baeries away from heat
sources and main air venlaon areas.
WARNING!
Typical baery performance data is quoted for an operang temperature between 20°C and 25°C. Operang above
this range will reduce the baery life while operaon below this range will reduce the baery capacity.
If the equipment is not to be installed immediately, it must be stored in a room so as to protect it against excessive
heat and humidity sources.
CAUTION!
An unused baery must be recharged every 6 months. Temporarily connecng the UPS to a suitable AC source and
acvang the UPS for the me required to recharge the baeries is required.
To monitor the UPS with the soware, simply connect the RS232 cable to the UPS and to a computer.
External Protecve Devices
For safety reasons, it is necessary to install an external circuit breaker at the input AC ulity and to the baery.
External Baery
The UPS and its associated baeries are protected against the eect of over-current through a DC compable
thermo-magnec circuit breaker located close to the baery.
UPS Output
Any external distribuon board used for load distribuon shall be ed with protecve devices so as to avoid the
risk of UPS overload.
Over-Current Protecon
A protecon device shall be installed at the distribuon panel of the incoming ulity power, and should idenfy
the power cables current capacity as well as the overload capacity of the system.
CAUTION!
Select a thermo magnec circuit-breaker with an IEC 60947-2 trip curve C (normal) for 125% of the current as listed
below. 40A Input Circuit Breaker required
Xtreme Power Conversion Corporaon
R90 Users Manual
Page 11
Uninterrupble Power Supply
Power Cables
The cable design shall comply with the voltages and currents provided in this secon, and in accordance with local
electrical codes.
WARNING!
UPON STARTING, PLEASE ENSURE THAT YOU ARE AWARE OF THE LOCATION AND OPERATION OF THE EXTERNAL
ISOLATORS WHICH ARE CONNECTED TO THE UPS INPUT/BYPASS SUPPLY OF THE UTILITY DISTIRBUTION PANEL.
CHECK TO SEE IF THESE SUPPLIES ARE ELECTRICALLY ISOLATED, AND POST ANY NECESSARY WARNING SIGNS TO
PREVENT ANY INADVERTENT OPERATION
Cable Sizes
UPS MODEL
CABLE SIZES (THHW wiring at 75°C)
AC INPUT AC OUTPUT DC INPUT GROUNDING
R90-20K 8 awg 8 awg 6 awg 8 awg
CAUTION!
Protecve earth ground cable: connect each cabinet to an earth ground, following the shortest route possible.
WARNING!
FAILURE TO FOLLOW ADEQUATE GROUNDING PROCEDURES MAY RESULT IN ELECTROMAGNETIC INTERFERENCE
OR IN HAZARDS INVOLVING ELECTRICAL SHOCK AND FIRE.
Power Cables Connecon
Aer the equipment has been properly posioned and secured, connect the power cables as described below.
Verify the UPS is totally isolated from its external power source and all circuit breakers to the UPS are open. Check
to see that everything is electrically isolated, and post any necessary warning signs to prevent inadvertent opera-
on of the breakers.
Xtreme Power Conversion Corporaon
R90 Users Manual
Page 12
Uninterrupble Power Supply
Power cable connecon diagram
Select the appropriate power cable size, paying aenon to the diameter of the connecon terminal of the cable,
which should be greater than or equal to the connecon posts.
Wiring diagram
Xtreme Power Conversion Corporaon
R90 Users Manual
Page 13
Uninterrupble Power Supply
WARNING!
IF THE LOAD EQUPMENT IS NOT READY TO ACCEPT POWER WHEN THE UPS INSTALLATION IS OCCURING, ENSURE
THAT THE UPS OUTPUT CABLES ARE SAFELY ISOLATED AT THE CABLE ENDS.
CAUTION!
The earth ground and neutral bonding arrangement must be in accordance with local and/or naonal electrical
code pracces.
Baery Connecon
The UPS has a posive and negave double baery framework using a total of 32 baeries in series. A neutral
cable is retrieved from the joint between the cathode of the 16th and the anode of the 17th of the baeries. The
neutral cable, the baery posive cable, and the baery negave cable are then connected with the UPS. The
baeries between the anode and neutral connecon are called posive baeries, and the baeries between the
neutral and cathode are called the negave baeries. The connecon is shown in the diagram below.
± 192VDC baery connecon diagram internal EBP32
Note: The BAT + of the UPS Connecon Terminals is connected to the anode of the Posive Baery. The BAT – of
the UPS Connecon Terminals is connected to the cathode of the Posive Baery and the anode of the Negave
Baery. The BAT – is connected to the cathode of the Negave Baery.
Factory default sengs for the baery quanty is 32 pieces and for a baery capacity of 7AH (charger current =
1A programmable to 6A)
Xtreme Power Conversion Corporaon
R90 Users Manual
Page 14
Uninterrupble Power Supply
Note: Oponal 3rd party baery conguraons of ±192VDC/±204VDC/±216VDC/±240VDC can be used and are
available.
CAUTION!
Ensure correct polarity of the baery string series connecon (i.e. inter-er and inter block connecons are from
(+) to (-) terminals. DO NOT mix baeries with dierent capacity or dierent brands, or new or old baeries.
WARNING!
ENSURE CORRECT POLARITY OF STRING END CONNECTIONS TO THE BATTERY CIRCUIT BREAKER, AND FROM THE
BATTERY CIRCUIT BREAKER TO THE UPS TERMINALS (I.E. (+) TO (+) / (-) TO (-)). DISCONNECT ONE OR MORE
BATTERY CELL LINKS IN EACH TIER. DO NOT RECONNECT THESE LINKS AND DO NOT CLOSE THE BATTERY CIRCUIT
BREAKER UNLESS ALL CONNECTIONS ARE PROPERLY CHECKED AND APPROVED.
R90-20K to EBP32 baery connecon
Xtreme Power Conversion Corporaon
R90 Users Manual
Page 15
Uninterrupble Power Supply
UPS Mul-Module Installaon
The basic installaon procedure for a parallel system consisng of two or more R90-20KVA modules is that same
as that of a single module. The following provides installaon procedures related to a parallel system.
Cabinet Installaon
Connect all R90-20KVA UPS required in the parallel system as shown in the diagram below.
Note: If installing 5-6 units in parallel, remove the jumper cap J30 on the control inspecon board (MHTBJHR-
1CU04 in all UPS to be connected in parallel. If installing 7-10 units in parallel, remove the jumper cap J30/J31
on the control inspecon board (MHTBJHR1CU04 in all UPS to be connected in parallel. Make sure that each UPS
input breaker is in the “OFF” posion and there is no output from any UPS connected. The baery strings can be
connected separately or in parallel.
WARNING!
MAKE SURE THE N, A(L1), B(L2), AND C(L3) WIRING IS CORRECT, AND THAT GROUND IS CONNECTED.
Xtreme Power Conversion Corporaon
R90 Users Manual
Page 16
Uninterrupble Power Supply
Parallel Cable Installaon
The shielded and double insulated control cables must be interconnected in a ring-conguraon between UPS
modules as shown in the diagram below. The parallel control board is mounted in each UPS module. The ring-
conguraon ensures high-reliability of the control funcon.
Parallel connecon of UPS
Xtreme Power Conversion Corporaon
R90 Users Manual
Page 17
Uninterrupble Power Supply
Remote Emergency Power O (EPO) for Parallel Systems
EPO for parallel systems must be connected in parallel and installed as shown below. Once the EPO funcon of one
of the UPS in the parallel system is acvated, the UPS will send out a remote command and shut down the other
UPS’s in the parallel system.
CAUTION!
The remote emergency kill switch must be voltage-free and “normally open”.
EPO connecons for parallel systems
Xtreme Power Conversion Corporaon
R90 Users Manual
Page 18
Uninterrupble Power Supply
Requirements for a Parallel System
A group of parallel UPS modules behave as one large UPS system with the advantage of presenng higher reli-
ability. In order to assure that all modules are equally ulized and comply with relevant wiring regulaons, please
follow the requirements below.
1. All UPS modules must be of the same rang and be connected to the same bypass source.
2. The Bypass and Ulity input sources must be referenced to the same neutral potenal.
3. The outputs of all the UPS modules must be connected to a common output bus.
4. The length and specicaon of power cables including the bypass input cables and the UPS output cabi-
nets should be the same size. This facilitates load sharing when operang in bypass mode.
5. Up to 10 UPS modules may be paralleled with common baery if desired
Note: If installing 5-6 units in parallel, remove the jumper cap J30 on the control inspecon board (MHTBJHR-
1CU04 in all UPS to be connected in parallel. If installing 7-10 units in parallel, remove the jumper cap J30/J31 on
the control inspecon board (MHTBJHR1CU04 in all UPS to be connected in parallel.
Operaon
Operaon Modes
The UPS is a double-conversion online UPS that may operate in the following alternave modes.
Normal Mode
The recer / charger derives power from the AC input ulity and supplies DC power to the inverter while oang
and boost charging the baery simultaneously. The inverter then converts the DC power to AC power and supplies
the load.
Baery Mode (stored energy mode)
If the AC input ulity power fails, the inverter, which is operang from power supplied by the baery, supplies the
crical AC loads with power from the baeries. There is no power interrupon to the crical load. The UPS will
automacally return to Normal Mode when AC input ulity recovers.
Bypass Mode
If the inverter is not funconing correctly, or if an overload occurs, the stac transfer switch will be acvated to
transfer the load from the inverter supply to bypass supply without interrupon to the crical load. In the event
that the inverter output is not synchronized with the bypass AC source, the stac switch will perform a transfer of
the load from the inverter to the bypass with power interrupon to the crical AC loads. This is to avoid paralleling
of unsynchronized AC sources. This interrupon is programmable but typically set to be less than one electrical
cycle (less than 15ms at 50Hz or less than 13.3ms at 60Hz).
ECO Mode
When the UPS is in AC Model and the requirement to the load is not crical, the UPS can be set to ECO Mode in
order to increase the eciency of the power supplied. In ECO Mode, the UPS works in line-interacve mode, so
the UPS will transfer to bypass ulity. When the AC is out of the set window, the UPS will transfer from bypass to
inverter and supply power from the baeries, with the LCD displaying all related informaon.
Note: ECO mode is not available in parallel system conguraons.
Parallel Redundancy Mode (system expansion)
To achieve higher capacity and / or increase reliability, the output of up to ten (10) UPS modules can be pro-
grammed to operate in parallel, with the built-in parallel controller in each UPS ensuring automac load sharing.
Xtreme Power Conversion Corporaon
R90 Users Manual
Page 19
Uninterrupble Power Supply
Turn On / O the UPS
Connecng with Ulity
The UPS is a double-conversion online UPS that may operate in the following alternave modes.
CAUTION!
MAKE SURE PROPER GROUNDING IS IN PLACE.
Set the Baery Breaker to the “ON” posion according to the user manual.
Switch “ON” the UPS
CAUTION!
Check to see if the load is safely connected to the output of the UPS. If the load is not ready to receive power from
the UPS, make sure that it is safely isolated from the UPS output terminals.
The internal fan of the UPS will start spinning; the UPS will perform self-diagnoscs unl the unit beeps twice to
show the UPS is normal. The UPS then goes to bypass, Ulity LED and Bypass LED turn Green, the inverter is now
starng. When the inverter is checked “normal”, the UPS goes to Normal Mode and the load is supplied power by
the inverter.
Cold Start Procedure
CAUTION!
Follow these procedures when there is an input AC Ulity Failure but the baeries are normal.
Turn on the baery switch.
o The baery will feed the Auxiliary power board.
Trigger the Cold Start Buons of the modules respecvely using the ON BUTTON shown in the above dia-
gram.
o When baery is normal, the recer starts operaon. 30 seconds later the inverter starts and
operates, INV and Output light up.
CAUTION!
Wait for approximately 30 seconds before pressing the ON BUTTON.
Xtreme Power Conversion Corporaon
R90 Users Manual
Page 20
Uninterrupble Power Supply
Inverter O
When the Ulity is normal, press OFF BUTTON for approximately 1 second unl you hear a beep. The INVERTER
LED will exnguish, the BYPASS LED will be illuminated, then the UPS turns to bypass supply.
Disconnecng from Ulity
CAUTION!
This procedure should be followed to completely shut down the UPS and the LOAD. Aer all power switches, isola-
tors, and circuit breakers are opened, there will be no output power from the UPS.
Aer the inverter is o, turn the Ulity and Baery breakers to “OFF”. The LCD display will exnguish com-
pletely and the fan stops spinning in 60 seconds. If there are external baery packs connected, turn the
Baery breakers on each baery pack to the “OFF” posion.
WARNING!
Wait about 5 minutes for the internal DC bus bar capacitors to be completely discharged.
Computer Access
Connect one end of the RS232 communicaons cable to a computer and the other end to the RS232 port
on the UPS
Open the soware Muser4000, and choose “system” buon
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49