AKCESS System Manual RC.IU.B1.22 4/99.1 3-31
Connectingg
On/Off Inputs The RTC has four sets of terminals for on/off inputs. Each set of terminals is labeled with the name of
the device for which the terminals are intended.
Connecting
Relay Outputs Controlled loads are connected to their RTC terminals by wiring to the common and either the normally
open (“NO”) or normally closed (“NC”) screw terminals labeled for the particular load.
RTC Power
Connections Power connections (24 VAC, +10% / -15%) are made to the terminals labeled “24 VAC.”
Inspection of the
Installed RTC When an RTC Rooftop Controller is ready for operation, you should be able to observe the following,
proceeding clockwise around the board from the power terminal strip:
1. Power connections (24 VAC) have been made to the “24 VAC” terminal.
2. Controlled loads are connected to the relay output terminal strips (labeled C, NO, and NC for
Common, Normally Open, and Normally Closed) for Fan, Damper, Cool 1, etc.
3. Loads to be monitored are connected to the on/off input terminals (labeled N and L for Neutral
and Line) for appropriate devices.
4. Connection has been made to the I/O network of an AKC 55 at the “NETWORK” terminals.
5. Sensor connections have been made to the terminal strips labeled for Zone Humidity, Outside
Humidity, Zone Temperature, etc. For temperature sensors, only SIG and GND connections
have been made, and for humidity sensors, 12V, SIG, and GND have been connected.
6. The Service LED will normally blink briefly when the network is scanned, but if the service
LED remains steadily on, or blinks constantly, the RTC board is defective and should be
replaced.
7. If this board is the last node on a run, make sure that it is terminated by using one of the
terminators supplied with the AKC 55.