AKCESS System Manual RC.IU.B1.22 4/99.1 6-13
Chapter 6 - 3 VLT
®
Electronic Drive Interface
An AKC 55 can control and monitor Danfoss VLT
®
electronic drives that have an Echelon interface.
Each AKC 55 can support a maximum of one VLT
®
per compressor, one per condenser group, and one
per AHU. In the following section, we’ll discuss these applications one by one.
VLT
®
Configuration
for Compressors
Configuration of a VLT for variable speed compressor control begins when inverter control is selected on
the configuration screen for a compressor. Normally there is only one variable speed compressor in a
suction group, and conventionally it is compressor number one. Here’s the configuration screen for
compressor 1 of a suction group:
For the field Inverter control there are three selections: NONE, VO, and VLT
®
. After VLT
®
is
selected as the type of control, the settings for inverter operation (minimum speed, maximum speed,
etc.) are entered.
VLT
®
Resets, Proof,
and Faults The example screen shown above contains the default values, which should be changed only by a
knowledgeable technician.
When a VLT
®
first begins to run (time = r), fault-checking occurs constantly (every 1-3 seconds). If a
fault is detected, the VLT
®
is reset.
Inverter max resets is the number of resets which can accumulate in the reset counter (a space in the
AKC 55’s memory) before the VLT
®
is placed in bypass. The reset counter is cleared whenever no
resets have occurred in the past 12 hours. In the case of the unit whose screen is shown above, if the
reset counter = 3, a reset will place the unit into bypass mode.
If at time = (r + proof delay) there is no proof signal, the VLT
®
is put directly into bypass mode by the
AKC 55 (see below under Inverter Status).
Continuing Configuration Now go to the Configure Rack screen and select Board & Points, then select the far right icon at the
bottom of the screen (a big “O” for “Other”), then select VLT
®
from the Other Controllers menu.
Once that selection is made, this screen appears: