
AKCESS System Manual RC.IU.B1.22 4/99.1 5-13
The Smart Case Controller continually adapts its superheat
target to changes in load on the evaporator so that refrigerant
flow is adjusted accordingly.
When target fixture temperature is achieved, the evaporator
status will change to Normal operation or Area control.
Area Control
(AKV valves) — (Occurs only when modulating control has been selected
during configuration.) The Smart Case Controller is supplying
sufficient refrigerant to maintain the target fixture temperature.
When Area Control status begins, the Smart Case Controller
learns the dynamics of the evaporator and optimizes internal
parameters for the modulated control function.
After fixture temperature reaches its target (if that target is
between 23 °F and 50 °F), and after a user-definable period
(default is 60 minutes), the status will change to Coil
conditioning.
Coil conditioning
(AKV valves) — (Occurs only when modulating control has been selected
during configuration, and only when target fixture temperature
is between 23 °F snf 50 °F.) Once each hour, the valve is
closed for 3 minutes to eliminate uneven frost build-up on the
evaporator. After 3 minutes, control reverts to normal
modulating control.
Low superheat
(AKV valves) — The Smart Case Controller has detected a negative superheat
for more than two minutes, and is reducing refrigerant flow to
correct the situation. The electronic expansion valve will close
for ten minutes, then enter Start-up status. This cycle will be
repeated until a positive superheat is established. After thirty
minutes in Low superheat status, an alarm will be generated.
Defrost — A scheduled or manually initiated defrost is in progress.
For fixtures with AKV valves, the valve is closed and the
defrost control relay is ON. For fixtures with KVQ valves,
the valve is open or closed (according to configuration by the
user). Make sure that the KVQ is configured to remain
open during gas defrost. The KVQ valve may not be used as
a suction stop.
Terminated defrost — The Smart Case Controller has terminated defrost and is
waiting for other coordinated controllers (if any) to terminate.
The valve remains in the state it was in during defrost.
Refrigeration will not resume until all coordinated defrosts
have been terminated.
Start after defrost — A transitional status following termination of defrost,
including drip down and fan delays.
After drip down, AKV valves begin to open at a predeter-
mined percentage for a maximum of two minutes to establish
minimum superheat. When fan delay is finished and minimum
superheat is reached, status will change to Cut-in.
After drip down, KVQ valves operate normally until the
completion of fan delay, when status changes to Normal
Operation.