Danfoss RTC Rooftop Control Board Installation guide

  • Hello! I am an AI chatbot trained to assist you with the Danfoss RTC Rooftop Control Board Installation guide. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
Dimensions, RTC PC Board Dimensions, Box-mounted RTC
Addressing
Mounting
I/O Network Configuration
INSTRUCTIONS
RTC Rooftop Controller
Each RTC connected to an AKC 55 must have a unique
address starting with 01. Each address switch has an
arrow pointer which is also a screwdriver slot for setting the
address.
The RTC board has six pre-drilled bolt holes for use in
mounting. Use half-inch standoffs. Mount in accordance
with codes and good electrical practice.
Up to 95 I/O nodes (OI8, RO8, SI8, AKC 16x Smart Case
Controllers, RTC’s, etc) can be connected to one AKC 55.
A maximum of 5 cable runs (1 shown) can be used to connect
any combination of nodes to the AKC 55.
The total length of all I/O cable runs (including stubs) is limited
to 5000 feet. Use point-to-point (“daisy-chain” connections
between boards.
The last I/O board on each cable run must be terminated.
Terminations are supplied with the AKC 55 controller as shown.
When necessary, individual I/O boards can be placed on
individual stubs up to a maximum of 25 feet long off a main
cable run.
©4/99 Danfoss Inc. BRTC.499.2 [RTCInstall]
POWER SUPPLY
24 VAC
Service LED:
Flashing or Steady On - Replace board.
Off - Board OK.
Humidity Sensor
G connect to GND
H connect to SIG
V connect to 12V
L: Line
N: Neutral
G: Ground
Sensor Inputs: 4
Humidity and temperature
1: Zone Humidity 1
2: Zone Humidity 2
3: Outside Humidity
4: Zone Temperature 1
Not used
Not used
SENSOR INPUTS
Power supply
24V AC +10%/-15%
Input Power Fuse:
2 AMP
Output Ratings:
24 VAC
Fused: 2 AMPS
Connections
Relay Connection:
Wire to power for C
controlled load.
Wire to normally NO
open load
Wire to normally NC
closed load
Temperature Sensors: 4
PT 1000 OHM
8: Return Temperature
7: Supply Temperature
6: Outside Temperature
5: Zone Temperature 2
Temperature Sensor Wiring:
example: Type AKS 11
Terminal 1: SIG (Signal)
Terminal 2: GND (Ground
Note: no polarity requirement
Shield
A
B
Outside Temp
6
GND
Status Led's
for DI (Green)
Service
Relay
#6
91
0
5
4
3
6
7
8
2
91
0
5
4
3
6
7
8
2
ADDRESS
C
24 vac
G N L
Zone Humidity
SHIELD
12V
1
GND
SIG
1
Zone Temperature
12V
2
3
4
12V
SHIELD
GND
SIG
SHIELD
GND
SIG
GND
SIG
Outside
Humidity
21
12V
SHIELD
SIG
5
GND
SIG
2
Damper
NCCCNONC NO
Relay
# 2
Relay
# 1
Status LEDs
for RO (Green)
Fan
NONOC NC NCCNO CNC
Cool 3
Relay
#5
Relay
#3
Relay
#4
Addressing
Cool 1
Cool 2
1: Fan
2: Damper
3: Cool 1
4: Cool 2
RELAY OUTPUTS
24 VAC
L
Network Connection
Twisted Pair stranded 22AWG wire
with shield. Belden cable nos. 9841,
9464, 9461, 8762, 8761 or equivalent.
Note: There is no polarity requirement
on network terminals A and B. The shield
must be connected.
Supply Temp
Return Temp
Setting Module
B
NETWORK
87
SIG
GND
SIG
GND
A
SHIELD
N
Heat 1/ Cool 2
Fan
Cool 1
N
1
L
L
2
N
L
3
DIGITAL INPUTS
24 VAC
3: Heat 1/Cool 2
2: Cool 1
1: Fan
5: Cool 3
6: Heat 1
7: Heat 2
8: Heat 3
CNO NC NO NC C NO NC
Smoke/Filter
Relay
#7
Heat 1 Heat 2
Relay
#8
4
N
Heat 3
4: Smoke/Filter
N Neutral (Common)
L Line: 0 - 24 V AC
EMHS
Humidity &
Temperature
TD2
G
H
TD1
V
12V SIG GND SH SIG
GND GND
SIG
Temperature Sensor
TD1 connect to SIG *
TD2 connect to GND *
* No polarity
Humidity
Temperature
SIG GND
SIG GND
rtcwir3.dwg 2/00
+ 2
- 1
+ 1
- 2
Variable Outputs
(on RTV VO only)
VO#1 : for Variable Frequency Drive
VO#2 : for Modulating Damper Motor
/