Danfoss air units and duct systems Installation guide

Type
Installation guide
Danfoss Air
Installation manual for Danfoss air units and duct systems
DANFOSS HEATING SOLUTIONS
MAKING MODERN LIVING POSSIBLE
Instructions Index
Index
2
VIEWA402
1 The Danfoss Air system
1.1 The Danfoss Air system. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.2 Before you start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
2 Unit installation
2.1 Installation of Air unit and condensate duct . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.2 Electrical installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2.3 Wireless connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.4 Setting up main air volume . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
3 Technical data
3.1 Dimensions - w1 unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
3.2 Dimensions - w2 unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
3.3 Dimensions - a2 unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
3.4 Dimensions - a3 unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
3.5 Detail - front panel removed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
3.6 Technical data - w1 unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
3.7 Technical data - w2 unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
3.8 Technical data - a2 unit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
3.9 Technical data - a3 unit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
4 Menu
4.1 Service menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
4.2 System reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
5 Valve installation
5.1 Location of valves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
5.2 Drilling holes in the ceiling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
5.3 Installing the valves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
6 Installing the duct system
6.1 General. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
6.2 Adaptation of ducts. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
6.3 Connecting the duct system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
6.4 Insulating the duct system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
6.5 Sound damping of the duct system. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
6.6 Roof terminals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
6.7 Adjusting the valves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
7 Setting up
7.1 Setting up the system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
1.1 Danfoss Air System
1.2 Before you start
Instructions The Danfoss Air System
3
VIEWA402
Congratulations on purchasing Danfoss Air, one
of the most advanced, efficient and quiet
ventilation systems with heat recovery on the
market.
On the following pages, we will take you through
the steps needed to properly install the duct
system and valves. If you follow these instruc-
tions, you can rest assured that your house will
have a well-functioning energy-efficient system.
This installation manual acts as a step-by-step
guide. For best results simply follow the instruc-
tions in the order they are given.
Please check that the shipment is complete
and has not been damaged. The ventilation unit
consists of:
• Wirelessremotecontrol-calledAirDialbelow
(4 AAA batteries included)
• Acommunicationmodule-henceforththe
CCM module
• Apowercable
• Acommunicationcable
• Awallbracket,incl.rubberstripandtworub-
ber separators (only w models)
• Aninstallationmanual(this)
• Auserguide
• Aquickguide(locatedbehindwallplateon
the wireless remote)
If you have ordered the complete Danfoss Air
Solution, there will be a complete packing list that
also follows the duct system. Please check that
packing list matches supplied components.
Instructions Unit installation
2.1 Installation of Air unit
and condensate line
Instructions for Air Units a
2
and a
3
– ceiling
units
On delivery, the connectors will be inverted to
save space. Pull out the spigots.
Turn the spigots around and mount using the
tapping screws included. If a power drill is used,
the lowest torque setting should be used.
The unit should be placed on a platform, made
as a sandwich of 16 mm plywood or MDF sheet,
sandwiched around a 50 mm wall batts. It is very
important that the unit is mounted completely
horizontal. Use spirit level to check.
Check adjustment
Please note! A siphon must always be fitted
on the unit. The siphon is a Danfoss accessory
which must be ordered separately.
Hose clamp
3/4” re-inforced hose
3/4” threaded fitting
Siphon installation - correct
Insulate
condensate
line
(frost proof)
Joist
Siphon
To drain
16 mm plywood
or MDF (2)
50 mm high
density
insulation
batts
Power supply
and connection
of CCM module
Siphon installation - wrong!
Joist
Siphon
To drain
If the unit is tilted, the function of the conden-
sate drain cannot be guaranteed, with risk of
water leakage as a result!
Mount the siphon on the rafter below the unit
or mount it in the room below the attic. If you
choose to mount your siphon in the attic, the
condensate duct must be made frost-proof.
Connect the pipe from the siphon to the conden-
sate spigot on the outlet. Lead the connected
pipe to the outlet, allowing for a gradient of min.
1 cm/metre.
Important: Remove front panel, and foam front
panel. Fill condensate tray, check the outlet and
reassemble.
Attic units a
2
and a
3
top view
Service area
Condensate drain
Ø19 (smooth)
Supply air
Exhaust air
Outdoor air (intake)
Discharged air
Power supply and
connection of CCM module
Important
Allow for 60 cm free space in front of unit, to
assure service access.
4
VIEWA402
Instructions Unit installation
5
VIEWA402
Wall Air units instructions w
1
& w
2
Place the wall mounting bracket on wall in
desired position, 75 mm from the bottom of the
bracket to the top of the unit, mark up- and drill
holes. Use screws suitable for the wall surface
(screws are not included).
Very important!
Ensure that the bracket is level.
Now hang unit onto wall
bracket, attach self-adhesive
foam blocks to lower rear
location on unit back plate
(absorbs potential vibrations
from unit to wall). Mount the siphon on the wall
below the unit.
Now fit the pipe from the siphon onto the sys-
tems condensate connector using the attached
pipe clip. The condensate is led from the siphon
on to the nearest outlet with a gradient of min.
1cm/metre. The condensate line must be insu-
lated where risk of freezing occurs.
Important: Remove front panel, and foam front
panel. Fill condensate tray, check the outlet and
reassemble.
75 mm
+
Rubber
separator
A
Detail A
Wall unit Top view
Condensate con-
nection
located here
(below unit)
Important
Allow for 60 cm
free space in
front of unit, to
assure service
access.
Instructions Unit installation
Ø19 mm
plastic pipe
Hose clamp
3/4” pipe
3/4” coupling
6
VIEWA402
Instructions Unit installation
2.2 Electrical installation
7
VIEWA402
Here is how
1. Connect power cable.
2. Plug in communication cable between com-
munication module and Air unit.
The cable cannot be fitted wrongly.
Important
If the communication module is mounted in
different floor than wireless remote, please check
if the deck construction contains elements that
will reduce transmission/receiving strength (i.e.
aluminum foil clad insulation material, or metal
grid, if deck is cast in concrete). If any such distur-
bances are present, the communication module
should be placed in same floor as wireless remote
control.
If an ethernet connection is already available in
the vicinity of the Air unit, place the communi-
cation module close to this, to allow for future
connection to PC.
Mounting CCM module in wall bracket
2
1
1. Hook the CCM on the wall bracket.
2. Press downwards to click the CCM into place.
Dismantling CCM module from wall bracket
2
1
1
1. Press in the two latches on the side.
2. Pull the CCM upwards.
NOTE:
If accessories are fitted (electrical preheating,
electrical afterheating, water heating surface or
geothermal surface), the pin on terminals 5 and
6 must be removed on the ventilation system
plug. See also the instructions included with the
accessories.
Communication cable
Power cable
Connection board (located
on underside of wall units,
or in end of attic units)
Communication module
(also has possibility of USB
or Ethernet connection)
White/orange
Orange
Black
White/blue
Blue
Black
Instructions Unit installation
2.3 Wireless connection
Upon first power up of CCM module, the green
LED will flash slowly - this indicates that the CCM
module has yet to be connected to the Air Dial.
To connect the Air Dial insert batteries. The Air
Dial will open up in a special mode, that leads the
installer through a step-by-step guide.
Follow the instruction in the guide:
1. Set language.
2. Create network (press button on CCM module
and then press Air Dial’).
3. Set basic step (setting up the main air volume).
4. Finish.
If the connection attempt is successful, the green
LED light up.
If the connection fails, the red LED on the com-
munication module will flash 5 times at low
speed. A failed connection will also be visible on
the wireless remote.
Troubleshooting if wireless connection fails:
• Connectiontowirelessremotewasnotat-
tempted within 2 minutes from pushing button
on the CCM - try again.
• Otherwirelessunitsinthevicinityareattempting
to connect to the CCM module - retry.
• Iftheabovedoesnotsolvetheproblem,there
is most likely inadequate signal strength. The
distance between the CCM module and the Air
Dial may be too great, or there is an obstacle
between the two devices.
If necessary, move the CCM module to the
same floor in the building and/or move it
closer to the Air Dial.
The communication cable can be lengthened
up to 200 m. Use a screened, double-twisted
cable with cross-section 24 AWG. Lengthen the
cable at the end with the wide 6-pin plug with
the finger terminals. Remember to refit the pin
between terminals 5 and 6 (unless a heating
surface has been fitted).
CCM moduleAir Dial
Installation of Air Dial - optimum placement
When mounting the Air Dial, please place according
to following guidelines to ensure best possible
accuracy (Air Dial has integrated temperature
sensor).
• Installatheightof80-150cmaboveoor
• Mountwhereremoteisclearofcurtains
• Mountinoccupiedzonewheretemperatureis
representative
• Donotmountinbathrooms
• Donotmountindirectsunlight
• Donotmountontoouterwall
• Donotmountdirectlyaboveheatsource
Carry out link test before the Air Dial is
mounted permanently on the wall
When the Air Dial has been registered on the
system, a link test should be carried out to ensure
that send/receive conditions are sufficient for the
required location. To carry out a link test:
1. Hold down the Air Dial button for 5 seconds.
The hidden Service menu appears (disappears
automatically after one hour).
2. Select the Link Test menu.
3. The Air Dial then tells you if the conditions are
satisfactory or not.
If the link test fails, the distance between the
CCM and the Air Dial is either too great or there
are metallic objects between the Air Dial and the
CCM which are disrupting the wireless connec-
tion. See troubleshooting above.
Mounting the Air Dial in wall bracket
8
VIEWA402
Instructions Unit installation
2.4 Balancing of
the main air volumes
9
VIEWA402
Why should you balance the system?
To achieve the best possible performance, it is
vital to balance the main air volumes. A balance
should be found between the main air volumes
in the house (this will contribute to protecting
the house against fungus and dry rot).
Setting up with low outdoor temperatures
If the outdoor temperature is below -3°C, the
system should not be balanced/commisioned as
the system will go into frost protection mode. A
flashing icon will show this on the display.
Note! If forced to balance a unit at outdoor air
temperatures below -3°C, remove power from
the ventilation unit for 20 seconds. The system can
then be balanced for up to 1½ hours, after which
the frost protection mode will again become
active (if conditions apply).
How to balance the main air volume -
Danfoss supplied the complete duct system
1. Remove front panel from unit (you do not need
tools, simply pull lightly at handles).
2. See the drawing of the duct system included.
Here you will find suggested pre-setting values
for all air valves. Close valves completely, and
turn them full turns towards ”open (number of
turns as indicated on the duct system drawing).
If dampers are included in the system, open
these completely before set-up is commenced.
3. Mount measuring tubes between the unit’s
measuring spigots on the exhaust side (see
illustration above) and differential pressure
gauge.
4. Find the required flow on the system diagram
(blue sticker) with the corresponding differential
pressure value. This is the pressure the measur-
ing equipment must show to ensure that the
flow is = as required. If the pressure is too low,
adjust the fan step upwards until you reach the
required pressure. Now move the measuring
tubes over onto the opposite measuring points
and use the same procedure to set up the sup-
ply air. All that remains is a quick fine-tuning
of the room air volumes as the presettings
are usually close to the required flow. See also
page 20 for further details about set-up.
Setting up a system that is operational, but
has not yet been adjusted
Press Air Dial for 5 seconds. The hidden Service
menu appears. In the Service menu, press ”set
basic step to activate the special commissioning
mode (where all outside influences are blocked
– the installer controls the exhaust and supply
air fans completely with 1-100% fan speed). The
Service menu remains visible for one hour and
then disappears.
How to balance the main air volume in a duct
system provided by a different supplier:
1. Remove front panel from unit (you do not need
tools - simply pull firmly on handles). When
setting up systems for which Danfoss has not
dimensioned the duct system, set the supply
and exhaust valves in accordance with the
instructions of the project manager.
2. Mount measuring tubes between the unit’s
measuring spigots on the exhaust side (see illus-
tration above) and differential pressure gauge.
3. Find the required flow on the system diagram
(blue sticker) with the corresponding differ-
ential pressure value. This is the pressure the
measuring equipment must show to ensure
that the flow is = as required. If the pressure is
too low, adjust the fan step upwards until you
reach the required pressure. Now move the
measuring tubes over onto the opposite meas-
uring points and use the same procedure to set
up the supply air. All that remains is to set up
the room air volumes.
After the main air volumes have been adjusted, the
set-up of individual valves needs to be carried out.
In most cases, this will entail minor changes to the
chosen basic steps, but this can be done in the room
by adjusting the valves.
How to measure
supply
How to measure
exhaust
Instructions Technical data
3.1 Dimensions - w
1
unit
Weight of unit: 31 kg
430 (incl. wall bracket)
530
Ø125
Supply
Ø125
Outdoor air
Ø125
Extract
Ø125
Exhaust
1000 (1042 incl. connectors)
95 170
Service side Service side
170
110
120
70
Top view Top view
Front view
1 2
3 4
Filter reset button
Isometric drawing
(frontpanel removed)
Optional supply air connector located on bottom of w1. To
use, remove top supply air connector by loosening screws,
remove lid from the bottom connector, and use this to seal
of the normal supply air connector. Then fit the supply air
connector on bottom.
Supply
(Located
at bottom)
115
92
92
Filter,
supply air
Filter,
extract air
Differential
pressure for
extract air
Differential
pressure for
supply air
Flow chart
(for set-up)
Differential
pressure for
extract air
Differential
pressure
for supply air
10
VIEWA402
Instructions Technical data
3.2 Dimensions - w
2
unit
11
VIEWA402
1 2
3 4
Weight of unit: 45 kg
580 (incl. wall bracket)
590
Ø160
Supply
Ø160
Outdoor air
Ø160
Extract
Ø160
Exhaust
1050 (1094 incl. connectors)
110 185 185
126
143
120
Top view Top view
Front view
Filter reset button
Isometric drawing
(frontpanel removed)
Filter,
supply air
Filter,
extract air
Differential
pressure for
extract air
Differential
pressure for
supply air
Flow chart
(for set-up)
Differential
pressure for
extract air
Differential
pressure for
supply air
1180
600
550
15
528
780
160
Ø250
318
440
Instructions Technical data
1180
600
580
32515
177
450
Ø160
550
Extract air
Exhaust airSupply air
Outdoor air
Exhaust
Outdoor air
Extract air
Supply air
Outdoor air
Exhaust
Differential pressure
for extract air
Differential pressure
for extract air
Differential pressure
for supply air
Differential pressure
for supply air
Filter reset button
Filter, supply air
Filter, exhaust air
Flow chart
(for balancing)
Weight of unit: 52 kg
Exhaust air
Outdoor air
Front view
Front view (without front panel)
Right view
Condensate drain
connection (on back)
Condensate drain
connection (on back)
3.3 Dimensions - a
2
unit
3.4 Dimensions - a
3
unit
3.5 Details - front panel removed
Weight of unit: 67 kg
12
VIEWA402
50
60
70
80
90
100
110
120
130
140
150
160
170
180
190
200
25 50 75 100 125 150 175 200 225 250 275 300
P ext. [Pa]
[m
3
/h]
SFP 1200
Flow properties / Strömungsverhältnisse / Luftdata
60 100 140 180 220 260 300
[m3/h]
Dry efficiency / WRG trocken / Tør virkningsgrad
89
91
87
85
83
81
Eta T [%] acc. EN 308 / Laut EN 308 / Jf. EN 308
Flow Pext. SFP P
1
tot.
[m3/h] [Pa] [J/m3] [W]
100 35 720 20
100 55 792 22
140 60 951 37
140 70 1029 40
180 70 1080 54
180 100 1300 65
Typical operation / Typische Arbeitspunkte
Typiske driftspunkter
63
22
20
(1) L
w
(A)
(2) L
w
(A)
(3) L
p
(A) Unit / Gerät / Anlæg til rum: 50
125
37
36
250
46
44
500
46
46
1000
43
43
2000
37
37
4000
25
26
Hz
dB(A)
dB(A)
dB(A)
63
34
31
(4) L
w
(A)
(5) L
w
(A)
(6) L
p
(A) Unit / Gerät / Anlæg til rum: 55
125
43
42
250
50
47
500
51
50
1000
48
48
2000
42
42
4000
31
31
Hz
dB(A)
dB(A)
dB(A)
(1) Exhaust / Abluft / Udsugning @ 140 m3/h
(2) Supply / Zuluft / Indblæsning @ 140 m3/h
(3) Hard room / Harter raum / hårdt rum @ 140 m3/h
(4) Exhaust / Abluft / Udsugning @ 180 m3/h
(5) Supply / Zuluft / Indblæsning @ 180 m3/h
(6) Hard room / Harter raum / hårdt rum @ 180 m3/h
Danfoss Air w
1
By condensation up to 95%
Bei Kondensation bis zu 95%
Ved kondensering op til 95%
100%
84%
35%
SFP 1000
66%
50
60
70
80
90
100
110
120
130
140
150
160
170
180
190
200
25 50 75 100 125 150 175 200 225 250 275 300
P ext. [Pa]
[m
3
/h]
100%
67%
45%
82%
SFP 1200
SFP 1000
SFP 800
Flow properties / Strömungsverhältnisse / Luftdata
60 100 140 180 220 260 300
[m3/h]
Dry efficiency / WRG trocken / Tør virkningsgrad
88
89
87
86
85
84
Eta T [%] acc. EN 308 / Laut EN 308 / Jf. EN 308
Flow Pext. SFP P
1
tot.
[m3/h] [Pa] [J/m3] [W]
160 50 720 32
220 70 867 53
220 100 1047 64
260 70 997 72
260 100 1163 84
300 90 1200 100
Typical operation / Typische Arbeitspunkte
Typiske driftspunkter
By condensation up to 95%
Bei Kondensation bis zu 95%
Ved kondensering op til 95%
63
30
25
(1) L
w
(A)
(2) L
w
(A)
(3) L
p
(A) Unit / Gerät / Anlæg til rum: 60
125
41
42
250
47
52
500
48
50
1000
46
48
2000
42
44
4000
32
34
Hz
dB(A)
dB(A)
dB(A)
63
33
28
(4) L
w
(A)
(5) L
w
(A)
(6) L
p
(A) Unit / Gerät / Anlæg til rum: 63
125
46
46
250
57
55
500
57
54
1000
55
52
2000
51
48
4000
43
40
Hz
dB(A)
dB(A)
dB(A)
(1) Exhaust / Abluft / Udsugning @ 220 m3/h
(2) Supply / Zuluft / Indblæsning @ 220 m3/h
(3) Hard room / Harter raum / hårdt rum @ 220 m3/h
(4) Exhaust / Abluft / Udsugning @ 260 m3/h
(5) Supply / Zuluft / Indblæsning @ 260 m3/h
(6) Hard room / Harter raum / hårdt rum @ 260 m3/h
Danfoss Air w
2
Instructions Technical data
3.6 Technical data - w
1
unit
3.7 Technical data - w
2
unit
13
VIEWA402
50
60
70
80
90
100
110
120
130
140
150
160
170
180
190
200
25 50 75 100 125 150 175 200 225 250 275 300
P ext. [Pa]
[m
3
/h]
100%
67%
45%
82%
SFP 1200
SFP 1000
SFP 800
Flow properties / Strömungsverhältnisse / Luftdata
60 100 140 180 220 260 300
[m3/h]
Dry efficiency / WRG trocken / Tør virkningsgrad
89
91
87
85
83
81
Eta T [%] acc. EN 308 / Laut EN 308 / Jf. EN 308
Flow Pext. SFP P
1
tot.
[m3/h] [Pa] [J/m3] [W]
160 50 684 30
220 70 824 50
220 100 995 61
260 70 947 68
260 100 1105 80
300 90 1140 95
Typical operation / Typische Arbeitspunkte
Typiske driftspunkter
By condensation up to 95%
Bei Kondensation bis zu 95%
Ved kondensering op til 95%
63
31
32
(1) L
w
(A)
(2) L
w
(A)
(3) L
p
(A) Unit / Gerät / Anlæg til rum: 51
125
41
43
250
47
50
500
46
47
1000
41
42
2000
39
40
4000
29
29
Hz
dB(A)
dB(A)
dB(A)
63
32
28
(4) L
w
(A)
(5) L
w
(A)
(6) L
p
(A) Unit / Gerät / Anlæg til rum: 54
125
44
44
250
49
51
500
49
48
1000
45
45
2000
43
42
4000
33
32
Hz
dB(A)
dB(A)
dB(A)
(1) Exhaust / Abluft / Udsugning @ 220 m3/h
(2) Supply / Zuluft / Indblæsning @ 220 m3/h
(3) Hard room / Harter raum / hårdt rum @ 220 m3/h
(4) Exhaust / Abluft / Udsugning @ 260 m3/h
(5) Supply / Zuluft / Indblæsning @ 260 m3/h
(6) Hard room / Harter raum / hårdt rum @ 260 m3/h
Danfoss Air a
2
50
60
70
80
90
100
110
120
130
140
150
160
170
180
190
200
50 100 150 200 250 300 350 400 450 500 550 600
P ext. [Pa]
[m
3
/h]
SFP 1200
Flow properties / Strömungsverhältnisse / Luftdata
200 250 300 350 400 450 500
[m3/h]
Dry efficiency / WRG trocken / Tør virkningsgrad
89
91
87
85
83
81
Eta T [%] acc. EN 308 / Laut EN 308 / Jf. EN 308
Flow Pext. SFP P
1
tot.
[m3/h] [Pa] [J/m3] [W]
200 70 900 50
350 70 802 78
450 70 832 104
450 100 1080 135
Typical operation / Typische Arbeitspunkte
Typiske driftspunkter
By condensation up to 95%
Bei Kondensation bis zu 95%
Ved kondensering op til 95%
63
35
35
(1) L
w
(A)
(2) L
w
(A)
(3) L
p
(A) Unit / Gerät / Anlæg til rum: 57
125
44
45
250
51
56
500
48
49
1000
48
47
2000
44
44
4000
31
31
Hz
dB(A)
dB(A)
dB(A)
63
39
39
(4) L
w
(A)
(5) L
w
(A)
(6) L
p
(A) Unit / Gerät / Anlæg til rum: 61
125
47
48
250
61
62
500
55
55
1000
53
52
2000
48
50
4000
37
37
Hz
dB(A)
dB(A)
dB(A)
(1) Exhaust / Abluft / Udsugning @ 350 m3/h
(2) Supply / Zuluft / Indblæsning @ 350 m3/h
(3) Hard room / Harter raum / hårdt rum @ 350 m3/h
(4) Exhaust / Abluft / Udsugning @ 450 m3/h
(5) Supply / Zuluft / Indblæsning @ 450 m3/h
(6) Hard room / Harter raum / hårdt rum @ 450 m3/h
Danfoss Air a
3
100%
SFP 1000
55%
79%
SFP 800
Instructions Technical data
3.8 Technical data - a
2
unit
3.9 Technical data - a
3
unit
14
VIEWA402
Instructions Menu
The Service menu is activated by pressing the Air
Dial button for 5 seconds.
In the Service menu the installer can set
individual functions to which it is not desirable
that the end user has access.
If the installer is dealing with a system where for
some reason there is a need to reset the system,
it should be done as follows:
1. If the system has already been balanced, the
basic steps used must be noted on a piece of
paper for later use. This is done by going into
the following menu item and reading the fan
steps for both the supply and exhaust fans:
Service > Info > basic steps
2. Remove the batteries from the Air Dial and
insert them again. While the last battery is
inserted, hold down the button - continue to
hold down the button until you hear a beep
from the Air Dial. The Air Dial is now ready in
start-up mode.
3. Remove the supply or communication cable
connecting the unit to the communication
module - hold down the button on the
communication module while you reconnect
the cable. Continue to hold down the button
on the communication module for 5 seconds
until only the green LED is flashing.
4. The system has now been reset to its factory
settings and can be registered as described in
Chapter 3.
If you noted the system’s basic steps in Point 1
above, these are the values that you should use
when the Air Dial asks for the required basic step
during the registration procedure.
Service
Back
Info
As normal, but fan steps are displayed without being rounded o
Set filter timer
Set filter period
Set language
Select required language on Air Dial
Set basic step
Set-up mode, installer controls both fans 0-100%
Link test
Used to test the wireless connection
4.1 Service menu
4.2 System reset
15
VIEWA402
Instructions Valve installation
Start by deciding on the location of the valves,
using the enclosed technical drawing as a
guideline. If the drawing indicates a valve which
is in the path of electrical wiring, water ducts or
wooden joists, for example, the fittings can of
course be moved so that installation is not made
unduly difficult.
Guidelines for valve locations:
Air diffusion
Try to avoid placing air diffusion valves above
places where people may be located for long pe-
riods such as above sofas, beds, dining table, etc.
If the house has a wood-burning stove, it is best
to position the air diffusion valve nearby.
Extraction
Designed to remove moist ”contaminated” air
and should therefore be positioned as close as
possible to the source, i.e. above washbasins, in
shower cabinets, etc.
Use a cup drill/hollow drill to drill the holes for
the valves. Use the following drill sizes: For valves
that are 100 mm in diameter (both diffusion and
extraction) use a hollow drill with a diameter of
108 mm. For valves that are 125 mm in diameter
(both air diffusion and extraction) use a hollow
drill with a diameter of 133 mm.
NOTE:
• Avoiddamagingthedampcourseunneces-
sarily and always remember to repair it with
weatherproof tape from the ceiling side after-
wards.
• Thesizeandshapeofthevalvesvariesdepend-
ing on the air direction and volume.
Supply air valve
Extract air valve
5.1 Location of valves
5.2 Drilling holes in the
ceiling
16
VIEWA402
Instructions Valve installation
Fix the bayonet socket that will hold the valve to
the ceiling. If it is a gypsum ceiling, we recom-
mend putting a wooden plate on the back for
the screws to bite into. If the duct needs to pass
through insulation, we recommend measuring
the insulation section and installing a duct sec-
tion along a suitable length of the bayonet socket
(VGU or VGM). Use an NPU connection nipple to
connect the VGM and the duct section.
200
200
200
200
200
200
5.3 Installing the valves
17
VIEWA402
Instructions Installing the duct system
Use a hacksaw or angle grinder to adjust the
ducts. We recommend filing down or cutting off
any sharp edges on the duct in order to avoid
damage to the rubber seals on the fitting parts.
NOTE:
• Alwaysuseappropriateprotectiveequipment
(i.e. protective goggles, ear defenders, etc.)
Pic. 1
To get the best out of the system and to achieve
optimum operational efficiency, you should
install the duct system as compactly as the build-
ing construction will allow. In practice, this means
that you should keep your duct sections as short
as possible and use as few bends as possible in
order to achieve the lowest possible loss of pres-
sure in the system. If the ducts are located on the
loft floor, they can be secured using duct clips.
Duct clips can also be used if the duct system is
suspended from the roof, using
UV fixing hangers, if required (Picture 1).
NOTE:
• Itisimportantthattheductsdonotrestonthe
valves or hang in the roof terminals.
• Werecommendpositioningtheductsinthe
insulation, in order to minimise heat loss as far
as possible. See the section on insulation.
• Itisimportanttoplaceasoftmaterialbetween
the duct and the rafters/duct clip in order to
avoid any vibration noise.
• Alwaysavoidinstallingdamagedproducts,
such as dented ducts, as this may reduce the
performance of the system and can result in
leaks.
Example
duct installations…
6.1 In general
6.2 Adaptation of ducts
18
VIEWA402
Instructions Installing the duct system
Push connectors into the duct up to the stop stick;
turning them slightly will make assembly easier.
Fix the connectors to the duct using self-tapping
screws or pop rivets. Screws/pop rivets should be
evenly distributed around the circumference. Fix
screws/pop rivets so that the safe rubber strips
are not damaged, i.e. 10 cm from the stop stick
line at the end of the duct.
In the event of incorrect assembly, screw/pop
rivet holes should be sealed up.
We recommend adhering to the following mini-
mum number and dimensions for steel screws/
pressure-resistant pop rivets:
Ød Min. Ød mm Number
63-125 3.2 2
140-250 3.2 3
The ducts supplied are 3 metres long as standard.
If you want to connect two ducts together, use
an NPU nipple with a rubber strip.
Stopsick
Ø 100
Ø 125
Ø 100
Ø 100
Ø 125
Ø 125
Ø 125 RCFU
NPUSR SR
Ø 125Ø 125 RCFURCFU
TCPU
TCPU
Ø 100
Ø 125
Ø 100
Ø 100
Ø 125
Ø 125
Ø 125 RCFU
NPUSR SR
Ø 125Ø 125 RCFURCFU
TCPU
TCPU
Reductions
If you want to reduce a branch, you can use a
T-section, where the branch on the T-section has
smaller dimensions. If you want to reduce the
main duct, you will need to use an RCFU reduction.
Ø 100
Ø 125
Ø 100
Ø 100
Ø 125
Ø 125
Ø 125 RCFU
NPUSR SR
Ø 125Ø 125 RCFURCFU
TCPU
TCPU
Example
Ø 100
Ø 125
Ø 100
Ø 100
Ø 125
Ø 125
Ø 125 RCFU
NPUSR SR
Ø 125Ø 125 RCFURCFU
TCPU
TCPU
Example
Crossing ducts
If two ducts need to cross, we recommend
installing the duct that runs along the beam
underneath the duct crossing it. This is the best
way to reduce heat loss.
30˚
30˚
30˚
To get your duct down into the insulation as
quickly as possible, we recommend the solution
illustrated.
30˚
70
600
1200
Connection to unit viewed from the side
.
30˚
SLU
SR
SR
BU
70
600
1200
Connection to unit viewed from above.
Connection between ducts and unit
It is important that all 4 flanges are connected
to the ducts with a flexible connection, so that
potential vibrations are not transferred from the
unit to the ducts system.
Avoid bending the flex pipe as this will add to
an increased pressure loss in the system. When
mounting, the flex pipe should be stretched as
far as possible – without deforming the pipe.
It is recommended to use an insulated flex pipe
type THISOL.
Mount hose clamps around the outer layer of
plastic in order to ensure air tightness.
6.3 Connecting the
duct system
19
VIEWA402
Instructions Installing the duct system
It is important that you insulate the duct system
correctly in order to avoid heat loss. Where the
design allows, the ducts can be run in/under the
insulation without any problems and this will
save some of the costs of insulation.
NOTE:
• Itisimportantthatbothsupplyandextractare
covered by at least 100 mm of insulation
and that the insulation is fixed tightly around
the duct.
• Thefreshairintakeandexhaustmustalways
have at least 30 mm of insulation to protect
against condensation. Where there is a pre-
heating surface or a geothermal surface, the
insulation of the fresh air intake should be at
least 100 mm.
• 50mmofinsulationwillbeadequateforsound
dampers, as they already have
50 mm of insulation.
In order to minimise heat loss from the duct sys-
tem in the ceiling, both the supply and discharge
ducts should be insulated using at least 100 mm
of insulation.
If you use insulation option A, we recommend
using two layers of 50 mm paper or foil covered
lamella mat mounted with staggered joints.
You should also note that if you use steel wire to
tie on the insulation, you must not tighten the
steel wire so much that it deforms or breaks up
the insulation.
Insulation of ducts, Option A
Insulation of ducts, Option B
Incorrect insulation of ducts
Note!
The above should be considered recom-
mended values only and you must always
abide by any country-specific regulations.
6.4 Insulating the
duct system
20
VIEWA402
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24

Danfoss air units and duct systems Installation guide

Type
Installation guide

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI