Danfoss Air Units Installation guide

Type
Installation guide
MAKING MODERN LIVING POSSIBLE
Installation Guide
Danfoss Air Units
www.heating.danfoss.com
Danfoss A/S is not liable or bound by warranty if these
instructions are not adhered to during installation or service.
The English language is used for the original instructions.
Other languages are a translation of the original instructions.
(Directive 2006/42/EC)
© 2014 Copyright Danfoss A/S
Installation Guide
Installationsvejledning
Installationshandbuch
Instrukcja montażu
GB .
DK .
DE .
PL .
Table of Contents
1 Safety Note .................................................................... 2
2 Before Start .................................................................... 2
3 Installation of Air Units ............................................................ 3
4 Installation of CCM Module and Air Dial ................................................. 4
4.1 Electrical connections .......................................................... 4
4.2 Wireless connection ........................................................... 4
4.3 Air Dial .................................................................... 4
4.4 Mounting and removing CCM module and Air Dial ........................................ 5
5 Connecting to Danfoss Link™ CC ...................................................... 5
5.1 Connecting the Air Unit to Danfoss Link™ CC, physical installation .............................. 5
5.2 Connecting the Air Unit to Danfoss Link™ CC, wireless inclusion ............................... 6
5.3 Performing a network test after adding a new device ...................................... 6
5.4 Setting basic steps in the Danfoss Link™ CC ............................................ 7
6 Balancing of the Main Air Volume ..................................................... 7
7 Service Menu ................................................................... 8
8 Technical Specifications ............................................................ 9
8.1 a² Unit .................................................................... 9
8.2 a³ Unit .................................................................... 11
8.3 w¹ Unit .................................................................... 13
8.4 w² Unit .................................................................... 15
9 Troubleshooting ................................................................. 16
1 Safety Note
This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of
experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person respon-
sible for their safety.
Children should be supervised to ensure that they do not play with the appliance.
Apart from the replacement of air filters and exterior cleaning of the system, any kind of maintenance will require the use of trained
personnel.
2 Before Start
Check the Danfoss Air Unit packing list to ensure that the shipment is complete.
If a complete Danfoss Air Solution is ordered, a packing list for the Air Flex duct system is included.
Inspect to ensure that no parts or components have been damaged.
Standard delivery includes:
Danfoss Air Unit
Wall bracket (if w-model)
CCM
Cabels
Optional deliveries:
Air Dial
Danfoss Link
TM
CC
Installation Guide Danfoss Air Units
VIEWB302 Danfoss Heating Solutions
2
3 Installation of Air Units
Attic Units a² and a³
1. Pull out the spigots
1
. Never lift the unit into the spigots, as it can damage the unit.*
2. Turn the spigots around and mount them using the included tapping screws (for power drill,
use lowest torque setting).
3. Make a platform
2
for the unit of 16 mm plywood or MDF sheet around 50 mm wall batts.
4. Allow for 60 cm free space in front of unit, to assure service access.
5. Make sure the unit is mounted with a minor backward fall.
6. A siphon
5
must always be installed with the unit (to be ordered separately).
7. Mount the siphon on the joist
4
below the unit or in the room below the attic.
8. Connect the siphon to a drain
6
.
9. The condensate line
3
must be insulated where risk of freezing occurs.
10. Connect the hose to the unit outlet condensate spigot. Lead the connected pipe to the out-
let, allowing for a gradient of min. 1 cm/metre.
11. Remove the front panel and foam front, fill the condensate tray, check the outlet and reas-
semble the front.
* If the unit is lifted into the spigots, it might cause leakage between the steel cabinet and the polystyr-
ene core. The leakage can be fixed from the inside of the unit by sealing the spigots with an acrylic-
based sealant.
1
2
3
4
5
6
1
1 cm
Wall Units w¹ and w²
1. Place the mounting bracket
1
on the wall in desired position (75 mm from bracket bottom to
unit top), mark up and drill holes. Use screws suitable for the wall surface (not included).
2. Make sure that the bracket is mounted absolutely horizontal.
3. Hang the unit onto the bracket.
4. Attach the self-adhesive rubber separators
2
to the lower rear back plate.
5. Allow for 60 cm free space in front of unit, to assure service access.
6. A siphon
3
must always be installed with the unit (to be ordered separately).
7. Mount the siphon on the wall below the unit.
8. Connect the siphon to the drain
5
at the unit bottom.
9. The condensate line
4
must be insulated where risk of freezing occurs.
10. Connect the hose to the unit outlet condensate spigot. Lead the connected pipe to the out-
let, allowing for a gradient of min. 1 cm/metre.
11. Remove the front panel and foam front, fill the condensate tray, check the outlet and reas-
semble the front.
75 mm
1
2
3
4
5
6
Wall Unit w¹
In order to comply with safety standards and avoid the risk of malfunction, the supplied protec-
tion shield must be mounted on top of the w¹-unit covering the connector plate.
Installation Guide Danfoss Air Units
Danfoss Heating Solutions VIEWB302
3
GB .
4 Installation of CCM Module and Air Dial
4.1 Electrical connections
1. Connect power cable
4
to Air unit
3
.
2. Plug in communication cable
2
between CCM module
1
and Air unit.
3. Check the signal. If it is too weak, the CCM module should be placed elsewhere, e.g. on the
same floor as as the Air Dial (see Air Dial Link Test).
4. If possible, place the CCM module close to an ethernet connection for future connection to
PC.
5. If accessories (electrical preheating, electrical afterheating, water heating surface or geo-
thermal surface) are present, the pin on terminals 5 and 6 must be removed (also see the
instructions included with the accessories).
1
2
3
4
5
6
1
2
3
4
Communication cable connections:
1. White/Orange, 2. Orange, 3. Black, 4. White/Blue, 5. Blue, 6. Black
Note! The communication cable can be extended up to 200 m. Use shielded cable , 22 or 24 AWG with 2 x twisted pair.
4.2 Wireless connection
When powering up the CCM module a green LED will flash slowly, indicating the CCM module
has yet to be connected to the Air Dial.
To connect the Air Dial, insert the batteries. The Air Dial starts in installation mode and automat-
ically guides through the set-up.
1. Set language.
2. Create network (press button on CCM module and then press Air Dial).
3. Set basic step (setting up the main air volume).
4. Finish.
Green LED lights continuously Connected established
Red LED flashes slowly 5 times Connection attempt failed, see Troubleshooting.
Tab. 2: LED blink patterns on the CCM
4.3
Air Dial
The Air Dial has an integrated temperature sensor. To ensure best possible performance,
place the Air Dial according to following guidelines:
Place the Air Dial 80-150 cm above floor level.
Place the Air Dial free of curtains etc.
Place the Air Dial where the temperature is representative.
!
Do not place the Air Dial in bathrooms.
Do not place the Air Dial in direct sunlight.
Do not place the Air Dial onto outer wall.
Do not place the Air Dial directly above heat source.
Installation Guide Danfoss Air Units
VIEWB302 Danfoss Heating Solutions
4
Air Dial Link Test
Before mounting the Air Dial permanently, perform a link test to ensure that transmission conditions are sufficient for the required loca-
tion:
1. Press the Air Dial button for 5 seconds to access the Service Menu (The Service Menu remains visible for one hour).
2. Select the Link Test function.
3. The function shows if the transmission conditions are sufficient or not.
4. If the link test fails, see Troubleshooting.
4.4 Mounting and removing CCM module and Air Dial
CCM module
Mounting:
1. Place the CCM on the wall
bracket.
2. Press downwards to click the
CCM into place.
2
1
Removing:
1. Press in the two latches on the
side.
2. Pull the CCM upwards.
Air Dial
Mounting:
1. Place the Air Dial on the wall
bracket.
2. Press downwards to click the
Air Dial into place.
1
2
Removing:
1. Lift the Air Dial.
2. Pull the Air Dial away.
1
2
5 Connecting to Danfoss Link™ CC
5.1 Connecting the Air Unit to Danfoss Link™ CC, physical installation
1. Connect power cable
4
to Air unit
3
.
2. Plug in communication cable
2
between CCM module
1
and Air unit.
3. If possible, place the CCM module close to an ethernet connection for future connection to
PC.
4. If accessories (electrical preheating, electrical afterheating, water heating surface or geo-
thermal surface) are present, the pin on terminals 5 and 6 must be removed (also see the
instructions included with the accessories).
5. The Air Unit is now ready to be added to the Danfoss Link™ CC.
1
2
3
4
5
6
1
2
3
4
Communication cable connections:
1. White/Orange, 2. Orange, 3. Black, 4. White/Blue, 5. Blue, 6. Black
Note! The communication cable can be extended up to 200 m. Use shielded cable , 22 or 24 AWG with 2 x twisted pair.
Installation Guide Danfoss Air Units
Danfoss Heating Solutions VIEWB302
5
GB .
5.2 Connecting the Air Unit to Danfoss Link™ CC, wireless inclusion
Remove the front cover of the Danfoss Link™ CC by gently pulling it off, pull near the
edges of the cover.
Press the SETUP pin for 3 seconds to enter the service area.
Note!
The Air Unit must be added to the network as a service device. For further instructions on the network inclusion, see the installation guide
supplied with the Danfoss Link™ CC.
Add any dedicated repeater units (CF-RU) BEFORE adding the Air Unit to the wireless network.
?
1
Service Options
Rooms and Devices
es
?
2
Rooms and Devices
Add Service Devices
ices
?
3
Add Service Device
Begin Registration
ion
Click here on the CCM for adding the Air
Unit
Note! During installation, the distance between the Danfoss Link™ CC and the CCM must not exceed 1.5m.
Green LED flashes slowly
CCM module has not yet been connected to the Danfoss Link™ CC
Green LED lights continuously CCM module is now connected to the Danfoss Link™ CC
Red LED flashes slowly 5 times Connection attempt failed
Tab. 2: LED blink patterns on the CCM
5.3
Performing a network test after adding a new device
After finishing installation, perform a network test, to ensure that communication between added devices and the Danfoss Link™ CC is
stable.
Note! Do not perform the network test before the Danfoss Link™ CC is mounted in its final position.
?
1
Service Options
Status and Diagnostics
tics
?
2
Status and Diagnostics
Network
?
3
Wireless Network Status
Start Network Test
est
At the end of the network test the Danfoss Link™ CC awaits for all battery operated devices to wake up and report. Follow the instruc-
tions given on the screen. If the network test is running smoothly, there will be no need for further interaction. If the network test is
performing slow, the Danfoss Link™ CC guides through troubleshooting and gives usefull tips for speeding up the process.
Installation Guide
Danfoss Air Units
VIEWB302 Danfoss Heating Solutions
6
5.4 Setting basic steps in the Danfoss Link™ CC
Now the Air Unit has been added to the wireless system, and is ready for balancing of the air flow. If the Air Unit has just been added to
the system, the screen will prompt for setting the basic extract and supply air step.
If the system was started earlier/by others, enter the basic settings through the Service Menu by pressing the Air Dial button for 5 sec-
onds. Go through the following steps.
?
1
Service Options
Rooms and Devices
es
?
2
Rooms and Devices
Manage Devices
es
?
3
Manage Devices
Congure device
?
4
Select Device
Air unit
?
5
Congure Device
System settings
?
6
System settings
Set basic steps
6 Balancing of the Main Air Volume
To achieve the best possible performance, it is vital to balance the main air volumes (balancing
will also help protecting the house against fungus and dry rot). The system should not be bal-
anced/commisioned at outdoor temperatures below -3°C, as the system will go into frost pro-
tection mode (indicated by a flashing icon on the display. If necessary to perform balancing at
outdoor air temperatures below -3°C, remove power for 20 seconds to de-activate frost protec-
tion for 90 minutes.
Note! Close all doors and turn off the cooker hood.
1. Remove the front panel from unit by pulling the handles.
2. See the drawing of the duct system, where suggested pre-setting values for all air valves
are stated. Close the valves completely, and turn them full turns towards open (number of
turns as indicated on the duct system drawing). When setting up the systems for which
Danfoss has not dimensioned the duct system, set the supply and extract valves in accord-
ance with the instructions of the project manager.
3. If dampers are included in the system, open these completely.
4. Mount measuring tubes between the unit’s measuring points on the extract side and dif-
ferential pressure gauge.
5. Find the required flow on the system diagram (sticker on front cover) with the correspond-
ing differential pressure value. If the pressure is too low, adjust the fan step upwards until
you reach the required pressure.
6. Move the measuring tubes to the measuring points on the supply side and use the same
procedure to set the supply air.
7. After the main air volumes have been adjusted, the set-up of individual valves needs to be
carried out. In most cases, this will entail minor changes to the chosen basic steps, but this
can be done in the room by adjusting the valves, or by using the Air Dial to fine tune basic
steps.
Measuring the extract
Measuring the supply
Adjusting an operational system
1. Press Air Dial for 5 seconds to get access to the Service menu.
2. Press ”set basic step” to activate the special commissioning mode (where all outside influ-
ences are blocked - the installer controls the extract and supply air fans completely with
1-100% fan speed). The Service menu remains visible for one hour and then disappears.
Installation Guide Danfoss Air Units
Danfoss Heating Solutions VIEWB302
7
GB .
7 Service Menu
Press Air Dial for 5 seconds to access the Service Menu to change basic settings like language,
filter timer, basic steps etc.
System Reset
1. If the system has already been balanced, make a note of the basic fan steps for later use.
The values are found in the Service Menu: Service > Info > Basic Steps.
2. Remove and re-insert the Air Dial batteries while pressing the button until a beep is heard.
The Air Dial is now in start-up mode.
3. Remove the supply or communication cable.
4. While re-connecting the cable, press the CCM module button until only the green LED is
flashing.
5. The system is now reset to factory settings.
Service
Back
Info
Set filter timer
Set language
Set basic step
Link test
Accessories
Installation Guide Danfoss Air Units
VIEWB302 Danfoss Heating Solutions
8
8 Technical Specifications
8.1 a² Unit
Dimensions
450
325
177
160
1263
1180
600
1
2
3
4
580
450
325
177
1
Outdoor air
2
Exhaust air
3
Extract air
4
Supply air
Weight of unit: 52 kg
Front view (without front panel)
1
2
3
4
5
6
6
5
1
Filter, extract air
2
Filter, supply air
3
Flow chart (for balancing)
4
Filter reset button
5
Differential pressure for extract air
6
Differential pressure for supply air
Capacity Temperature ratio
Pressure [Pa] η [%]
100%
85%
1000 J/m³
70%
58%
46%
33%
21%
350
300
250
200
150
100
50
0
0 50 100 150 200 250 300 350 400 450
*0.45 W/m³/h
Flow [m³/h]
83%
84%
85%
86%
87%
88%
89%
90%
91%
92%
93%
94%
0 50 100 150 200 250 300
Flow [m³/h]
* 0.45 W/m³/h = "Passiv Haus" requirements.
Flow [m³/h] Pext. [Pa] SFP [J/m³] P
1
tot. [W]
160 50 615 27
220 70 728 44
220 100 854 52
260 70 783 57
260 100 894 65
300 90 936 78
Tab. 3: Capacity for the a² unit
Extract air Fresh air
t = 21 °C RH = 36% t = -3 °C RH = 80% with condensation and 5% imbalance
t = 25 °C RH < 27% t = 5 °C as acc. to EN308
Tab. 4: Temperature ratio for the a² unit
Installation Guide
Danfoss Air Units
Danfoss Heating Solutions VIEWB302
9
GB .
Flow
m³/h
Pres-
sure Pa
Measured
at
Frequency band [Hz], sound power Lw (A) [dB(A)] Sound pressure
Lp(A) (standard*
room) [dB(A)]
63 125 250 500 1000 2000 4000 8000
162 70
Supply air
duct
23 34 40 36 29 25 17 18
Extract air
duct
23 33 39 37 29 24 18 18
Cabinet 40
162 100
Supply air
duct
25 35 43 38 31 28 18 18
Extract air
duct
25 36 42 39 30 25 17 18
Cabinet 41
216 70
Supply air
duct
26 36 44 39 33 30 19 18
Extract air
duct
28 36 43 41 34 29 18 18
Cabinet 45
216 100
Supply air
duct
26 37 44 40 34 31 19 18
Extract air
duct
27 37 45 42 35 30 19 18
Cabinet 46
250 100
Supply air
duct
28 39 46 42 37 33 21 18
Extract air
duct
30 39 48 45 38 33 20 18
Cabinet 49
* Values for sound pressure calculated for a standard room with A = 10 m², H = 2.4m and mean absorption 0.2.
Tab. 5: Sound data for the a² unit
Installation Guide
Danfoss Air Units
VIEWB302 Danfoss Heating Solutions
10
8.2 a³ Unit
Dimensions
250
440
160
528
318
1180
1342
600
1
2
3
4
780
440
160
528
318
1
Outdoor air
2
Exhaust air
3
Extract air
4
Supply air
Weight of unit: 67 kg
Front view (without front panel)
1
2
3
4
5
6
6
5
1
Filter, extract air
2
Filter, supply air
3
Flow chart (for balancing)
4
Filter reset button
5
Differential pressure for extract air
6
Differential pressure for supply air
Capacity Temperature ratio
Pressure [Pa] η [%]
40%
56%
82%
100%
1000 J/m³
300
250
200
150
100
50
0
0 50 100 150 200 250 300 350 400 450 500 550 600
*0.45 W/m³/h
Flow [m³/h]
80%
81%
82%
83%
84%
85%
86%
87%
88%
89%
90%
0 50 100 150 200 250 300 350 400 450 500
Flow [m³/h]
* 0.45 W/m³/h = "Passiv Haus" requirements.
Flow [m³/h] Pext. [Pa] SFP [J/m³] P
1
tot. [W]
200 70 787 44
350 70 835 81
450 70 973 122
350 100 1000 97
Tab. 6: Capacity for the a³ unit
Extract air Fresh air
t = 21 °C RH = 36% t = -3 °C RH = 80% with condensation and 5% imbalance
t = 25 °C RH < 27% t = 5 °C as acc. to EN308
Tab. 7: Temperature ratio for the a³ unit
Installation Guide
Danfoss Air Units
Danfoss Heating Solutions VIEWB302
11
GB .
Flow
m³/h
Pres-
sure Pa
Measured
at
Frequency band [Hz], sound power Lw (A) [dB(A)] Sound pressure
Lp(A) (standard*
room) [dB(A)]
63 125 250 500 1000 2000 4000 8000
350 70
Supply air
duct
35 45 56 49 47 44 31 16
Extract air
duct
35 44 54 48 48 44 31 19
Cabinet 57
450 100
Supply air
duct
39 48 62 55 52 50 37 22
Extract air
duct
39 47 61 55 53 48 37 20
Cabinet 61
* Values for sound pressure calculated for a standard room with A = 10 m², H = 2.4m and mean absorption 0.2.
Tab. 8: Sound data for the a³ unit
Installation Guide
Danfoss Air Units
VIEWB302 Danfoss Heating Solutions
12
8.3 w¹ Unit
530
1005
108
287
438
125
161
254
296
125
430
224
160
1
2
3
4
5
6
7
89
98
10
1
Supply air
2
Extract air
3
Exhaust air
4
Outdoor air
5
Condensate drain
6
Filter, extract air
7
Filter, supply air
8
Differential pressure for extract air
9
Differential pressure for supply air
10
Filter reset button
Weight of unit: 32 kg
Capacity Temperature ratio
Pressure [Pa] η [%]
85%
70%
58%
46%
33%
21%
*0.45 W/m³/h
1000 J/m³
350
300
250
200
150
100
50
0
0 50 100 150 200 250 300
100%
Flow [m³/h]
84%
85%
86%
87%
88%
89%
90%
91%
92%
93%
0 50 100 150 200 250
Flow [m³/h]
* 0.45 W/m³/h = "Passiv Haus" requirements.
Flow [m³/h] Pext. [Pa] SFP [J/m³] P
1
tot. [W]
100 35 588 16
100 55 682 19
140 60 710 28
140 70 759 30
180 70 798 40
180 100 945 47
Tab. 9: Capacity for the w¹ unit
Extract air Fresh air
t = 21 °C RH = 52% t = 5 °C RH = 80% with condensation and 5% imbalance
t = 25 °C RH < 27% t = 5 °C as acc. to EN308
Tab. 10: Temperature ratio for the w¹ unit
Installation Guide
Danfoss Air Units
Danfoss Heating Solutions VIEWB302
13
GB .
Flow
m³/h
Pres-
sure Pa
Measured
at
Frequency band [Hz], sound power Lw (A) [dB(A)] Sound pressure
Lp(A) (standard*
room) [dB(A)]
63 125 250 500 1000 2000 4000 8000
126 70
Supply air
duct
20 30 41 42 38 30 19 18
Extract air
duct
18 30 41 41 30 26 18 18
Cabinet 47
126 100
Supply air
duct
22 32 46 45 39 32 21 18
Extract air
duct
22 33 43 42 32 27 19 18
Cabinet 50
162 70
Supply air
duct
23 31 43 46 41 33 22 18
Extract air
duct
26 31 42 43 33 29 21 18
Cabinet 53
162 100
Supply air
duct
28 33 44 48 43 35 23 18
Extract air
duct
29 34 44 51 37 31 23 18
Cabinet 55
216 70
Supply air
duct
28 33 44 54 46 37 28 18
Extract air
duct
27 33 43 52 39 33 27 18
Cabinet 57
216 100
Supply air
duct
28 35 45 55 46 38 29 18
Extract air
duct
32 34 44 52 40 34 28 18
Cabinet 56
* Values for sound pressure calculated for a standard room with A = 10 m², H = 2.4m and mean absorption 0.2.
Tab. 11: Sound data for the w¹ unit
Installation Guide
Danfoss Air Units
VIEWB302 Danfoss Heating Solutions
14
8.4 w² Unit
590
1055
580
126
270
389
110
295
480
1
2
3
4
5
6
7
8
9
98
10
1
Supply air
2
Extract air
3
Exhaust air
4
Outdoor air
5
Condensate drain
6
Filter, extract air
7
Filter, supply air
8
Differential pressure for extract air
9
Differential pressure for supply air
10
Filter reset button
Weight of unit: 45 kg
Capacity Temperature ratio
Pressure [Pa] η [%]
100%
85%
70%
58%
46%
33%
21%
300
250
200
150
100
50
0
*0.45 W/m³/h
1000 J/m³
0 50 100 150 200 250 300 350 400
Flow [m³/h]
83%
84%
85%
86%
87%
88%
89%
90%
91%
92%
93%
94%
0 50 100 150 200 250 300
Flow [m³/h]
* 0.45 W/m³/h = "Passiv Haus" requirements.
Flow [m³/h] Pext. [Pa] SFP [J/m³] P
1
tot. [W]
160 50 700 31
220 70 832 51
220 100 963 59
260 70 892 64
260 100 996 72
280 90 1000 78
Tab. 12: Capacity for the w² unit
Extract air Fresh air
t = 21 °C RH = 36% t = -3 °C RH = 80% with condensation and 5% imbalance
t = 25 °C RH < 27% t = 5 °C as acc. to EN308
Tab. 13: Temperature ratio for the w² unit
Installation Guide
Danfoss Air Units
Danfoss Heating Solutions VIEWB302
15
GB .
Flow
m³/h
Pres-
sure Pa
Measured
at
Frequency band [Hz], sound power Lw (A) [dB(A)] Sound pressure
Lp(A) (standard*
room) [dB(A)]
63 125 250 500 1000 2000 4000 8000
126 50
Supply air
duct
20 30 34 36 23 19 17 18
Extract air
duct
16 31 37 36 29 21 17 18
Cabinet 39
162 70
Supply air
duct
23 33 35 40 32 24 18 18
Extract air
duct
20 33 44 39 34 26 18 18
Cabinet 44
162 100
Supply air
duct
25 36 42 42 34 28 18 18
Extract air
duct
21 33 43 41 35 28 18 18
Cabinet 46
216 70
Supply air
duct
25 34 42 42 35 28 19 18
Extract air
duct
22 34 44 43 37 31 20 18
Cabinet 47
216 100
Supply air
duct
26 36 43 44 36 30 20 18
Extract air
duct
23 34 45 44 33 32 20 18
Cabinet 49
250 100
Supply air
duct
27 36 45 45 38 31 21 18
Extract air
duct
24 37 47 45 40 34 22 18
Cabinet 53
* Values for sound pressure calculated for a standard room with A = 10 m², H = 2.4m and mean absorption 0.2.
Tab. 14: Sound data for the w² unit
9 Troubleshooting
Error Cause Solution
Alarm: Filter error Air filters are dirty. Exchange air filters and reset alarm.
Alarm: Battery low Battery voltage in Air Dial is too low. Replace batteries (4 x AAA) in Air Dial.
Installation Guide Danfoss Air Units
VIEWB302 Danfoss Heating Solutions
16
Error Cause Solution
Alarm: No connection to CCM/link test
failed
Communication between Air Dial and CCM
module has failed, typically caused by an ob-
stacle between Air Dial and CCM module, e.g.
steel piping, other steel objects, insulation ma-
terial clad with aluminum foil, etc. Another
cause can be other wireless appliances that
does not conform to wireless standards (radio
noise).
If an obstacle has been identified, move
it. If this is not possible, move CCM
module to a better location with a free
‘line of sight’.
If the error occurs due to other wireless
appliances in the house, try switching
these off one by one, to identify the
faulty device.
If none of the above helps, contact Dan-
foss.
Alarm: No connection via modbus/link test
failed
Cable between CCM module and unit is un-
plugged or defective.
Check cable and reconnect if necessary.
If cable is connected, but error still oc-
curs - contact Danfoss.
Alarm: Room air too cold Central heating system is not supplying heat.
Room temperature is dropping, so the unit
turn off to reduce involuntary heat loss. Alarm
active if Air Dial measures a room temperature
below +10 °C.
Check if heating system is functional. If
the problem can not be solved, contact
plumber/Danfoss.
When error has been remedied, shut
down and restart ventilation system to
resume normal operation. Power can be
disconnected by pulling power cable
from system.
Alarm: Fire One of four temperature sensors in Danfoss Air
Unit or temperature sensor in Air Dial remote
control has detected a temperature higher
than +70 °C. The Air Unit turns off until all sen-
sors indicate below +70 °C.
Examine all rooms, leave the house.
When error has been remedied, shut
down and restart ventilation system to
resume normal operation. Power can be
disconnected by pulling power cable
from system.
Alarm: Sensor error Temperature sensor in Danfoss Air unit or Air
Dial is defective.
Contact Danfoss.
System continues to run, but with limi-
ted functionality.
Abnormally large negative pressure inside
the house, doors binding
Discharge air flow is larger than supply air flow.
Either balancing was not carried out correctly
during set-up of the system or the Air Unit is in
extreme defrost conditions (can occur at out-
door temperatures below -12 °C).
Imbalance of flow should be 4-10% in
favour of extract air, but if problems
with doors binding is permanent, con-
tact Danfoss.
If problems only arises during extreme
winter condition, it is due to the inte-
grated defrost function that reduces the
supply air (hence not a defect, but an
expected, and very rare occurrence).
Condensation in window frames Air exchange is too low. Condensation occurs
when humidity is high and surface tempera-
tures are low, typically in bathrooms or utility
rooms, where clothes are drip drying (some
condensation in bathrooms following a shower
is normal, but should disappear within half an
hour).
Increase fan step Manual mode or
change to Demand mode or Pro-
gramme mode.
Set Autoboost - on.
House temperatures are too high House thermostats are set too high. Turn down thermostats.
Bypass is disabled on ventilation system. Bypass is disabled on ventilation system. Enable Bypass in Main menu Bypass
Auto bypass.
Noise from Air Unit a-type unit: vibration noise may occur if unit is
mounted directly onto joists. Unit should be
mounted on a suitable platform.
Check that unit is mounted on platform,
according to installation manual.
w-type unit: vibration noise may occur if rub-
ber spacers are not fitted between unit and
wall and/or if silicone strip is not fitted onto
wall bracket.
Check that rubber spacers and silicone
strip are fitted, according to installation
manual.
Defective fan bearings will produce a ‘grinding
noise’.
If fan ball bearing is suspected to be de-
fective, contact Danfoss.
Installation Guide Danfoss Air Units
Danfoss Heating Solutions VIEWB302
17
GB .
Error Cause Solution
Noise from Air valves Air flow is too high. Noise is not a problem in a correctly
sized and commissioned system. How-
ever, if air valves are closed (e.g. during
cleaning), a hissing noise may occur.
Pressure is too high over valve.
No silencer is fitted to main duct.
Frost icon in display
The system is in defrost mode, because low
outdoor temperatures entail a risk of ice form-
ing in the heat exchanger.
This is not an error, but a standard
mode. The function stops automatically
when the outdoor temperature rises.
Installation Guide Danfoss Air Units
VIEWB302 Danfoss Heating Solutions
18
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72

Danfoss Air Units Installation guide

Type
Installation guide

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI