ACT PRO 1010 - DIAGRAM Wiring Instruction

Type
Wiring Instruction

This manual is also suitable for

ACTpro 1010
Reader (Exit)
Wire both readers in parallel but leave
the SENSE line on the Exit reader unconnected.
Controller
SENSE
CLOCK
DATA
+5v
0v
RED
GREEN
Card/Prox Reader
White
Green
Blue
Red
Black
Brown
Yellow
Orange
SENSE
CLOCK
DATA
+5V
0V
RED
GREEN
Not Connected
Wiring for Clock and Data
The +5V reader supply on ACT controllers is normally rated
at 100mA. Typically this is sufficient to power 2 ACT readers.
Note however that readers from other manufacturers may need
to be powered separately if their current requirements exceed
this or if they require 12V.
The standard wiring colours for
ACTpro 1010 reader is shown above.
Readers should be a maximum of 30m
from the controller when powered
from +5V and a maximum of 100m
when powered from +12V.
Unit C1, South City Business Centre, Tallaght, Dublin 24, Ireland.
Telephone: 353 1 466 2570. Telefax: 353 1 452 0427. E-mail: [email protected] Web: www.accesscontrol.ie
ACTpro 1010 Wiring for Entry / Exit
ACTpro 1010
Reader (Entry)
The ACTpro 1010 is configured to read ISO Track 2 of magnetic stripe card media.
Reader Specification
Voltage: 5-12V DC
Current: 15 mA standby, 20 mA maximum
Operating Temperature: -10 degrees C to +55 degrees C
Media: ISO standard high or low coercivity magnetic card
Speed: 12.7-172 cm/s
Head Life >1,000,000 passes
Cable: 3m x 8-core screened
Reader Distance: Max 30m from controller powered with 5V DC
Max 100m from controller powered with 12V DC
18-0004 Issue 4
  • Page 1 1