The external surface of the motor should be kept clean and the
ventilation inlets should not be blocked.
Intermittent and abnormal noise and vibrations are not accept-
able and the motor should be shut off. The bearing temperature
shall not exceed 95 °C.
INSTALLATION OF SEPARATELY SUPPLIED
FREQUENCY INVERTER
CAPACITIES IN EXCESS OF 22 KW
If the capacity exceeds 22 kW, a symmetrically shielded cable
with concentric or in some other way symmetrically designed
protective earth conductor should be used. For recommenda-
tions governing these installations we refer to the installation
instructions for the frequency inverter.
INPUT POWER {MAINS) CABLE, FUSES AND CIRCUIT
BREAKERS
A four conductor cable (three phases and earth/protective
earth) is recommended for the input power cabling. Shielding is
not necessary. Dimension the cables and fuses in accordance
with the input current. Always pay attention to local codes when
sizing the cables and fuses.
The input power connectors are at the bottom of the drive. lnput
power cable routing must be done so that the distance from the
sides of the drive is at least 20 cm to avoid excessive radiation
to the input power cable. In the case of shielded cable, twist the
cable shield wires together into a bundle (pigtail) not longer than
five times its width and connect to the PE terminal of the drive (or
PE terminal of input filter, if present).
GENERAL
FläktGroup Standard Three phase asynchronous motor can be
delivered in different models (manufacturers).
Regardless of the models the delivered motor always fulfils
the specification given from the product selection software ACON.
The motor and fan are balanced from factory.
The motor is designed for continuous operation in ambient
temperature 40 °C and altitudes below 1000 meters. The casing
of the motor can be hot when touching during normal service
even after shut off.
INSTALLATION
The motor shall be earthed according to valid regulations.
Voltage tolerance is +/- 10 %. When the phase-sequence is
L1, L2, L3 the direction of rotation is clockwise viewed from the
driving end. The direction of rotation will be reversed if
the phase-sequence is altered.
The connecting terminal block is equipped with metric knock-
outs. Not used holes must be sealed. The cable gland must have
same IP-class as the terminal block and fit the cable diameter.
Generally, a thermal and short circuit protection device should
be mounted in the motors power supply. If the motor is equipped
with a thermistor it should be used.
The instruction for connection of the thermistor is in the terminal
block.
Warning!
If the frequency inverter is not installed
correctly, this may damage the motor bearings.
FläktGroup’s policy stipulates that we agree
to accept guarantee liability only if the motor
and frequency inverter have been supplied
and installed by us.
Guarantee liability will not be accepted by
FläktGroup if the motor has been connected/
wired to a frequency inverter by another fitter,
i.e. one who is not employed by or commis-
sioned by FläktGroup.