FläktGroup DC_10421GB 20200128_R0 Specifications are subject to alteration without notice
FREQUENCY INVERTER
The shielded cable must be led either through an EMC approved cable
gland in the casing of the frequency inverter or through a cap intended for
this purpose.
The shielded cable must not be connected to an earth screw.
The shield must be in 360º
contact with
the casing
Shield
Insulating tape
NOTE!
PARAMETERS
Speed controller parameters are set at the factory pro-viding for
optimal performance of fan and motor. This includes motor para-
meters, ramp times, starting and stopping methods and speed
limitations.
Changing of these parameters may result in unstable
operation or motor won’t start.
GENERAL
• Admissible environmental temperature: from -15 °C up to
+40 °C, with altitudes 1000 m above sea level
• Mounting: IM B3, B5
• Drive operating voltage: 400 VAC
• Insulation class: "F"; temperature rise to class B
(TEFC execution)
• IP55 degree of protection for the whole range
• Reduced dimensions
• Rare earth permanent magnets
NOTE!
The frequency converter have been optimized for the
duty point. The power could thus be lower than the
motors rated power.
PM-MOTOR
INSTALLATION
A continuous, shielded 4-wire cable designed for EMC installation to
motor drives should be installed between the motor and the frequency
inverter. The optical density of the cable shield shall be at least 80 %, e.g.
NCY or Olflex Classic. The shield must be in 360 º contact with the casing
both in the motor and in the frequency inverter in order to achieve maxi-
mal surface contact. It is not advisable to install a safety isolating switch
or junction boxes between the frequency inverter and the motor.