Installation and maintenance instructions
4
FläktGroup DC_10395GB 20210503_R1 Specifications are subject to alteration without notice
TEMPERATURE CORRECTION
The flow scale on the indicating instrument and the flow formula
above apply to air with a temperature of +20 °C. For other tempera-
tures, the flow must be corrected using the following formula:
where q = the actual flow through the fan, q20 = the flow reading and
t = the current temperature in °C.
MAINTENANCE
The fan must be inspected and cleaned every 6/12th month. The
length of the interval has been determined on the basis of approx.
2000 hours of operation during a 12-month period and for a normal
comfort installation.
In environments where the dust content is high in the supply and/
or extract air, the air handling unit will have to be inspected and clea-
ned more often.
The fan is accessible through the inspection door and cleaned with
the fan in place.
CLEANING
Both the supply air and the extract air fan should be inspected and
cleaned whenever the need arises. Dust tends to collect mainly on
the inner side of the fan blades.
The best way to clean the fan impeller is by using a vacuum
cleaner equipped with a soft nozzle. Be careful to remove all the
impurities from the fan blades so that the fan will not come out of
balance.
After adjusting or cleaning the fan, check that it runs free of
vibration.
TO REMOVE THE FAN FROM THE AIR HANDLING
UNIT CASING, ASYNCHRONOUS AND PM-MOTORS
The fan can be withdrawn from the casing in the following way:
1. Remove the frame of the inspection door including the door
and the fixed panel by removing the bolts beneath the cover
plenums.
2. Disconnect the motor cable/control cable to the frequency
inverter and pull the cables through the rotor wall/filter wall.
3. If a pressure suppressor and steel spring anti-vibration
mountings are fitted: Remove the nuts to the fan beams in
the floor at both ends.
4. If steel spring anti-vibration mountings are fitted:
Remove the bolts that hold the fan connection against
the fan outlet.
NB!
In the case of air handling units supplied with a
control system, the pressure tappings in the end
connection panels of the unit are not connected to
the airflow sensor of the fan.
If you still want to read the manometer pres-
sure with an external manometer, you can
connect the tubes from the airflow sensor of
the fan across T-nipples to the pressure tappings
in the end connection panel of the air handling
unit.
If this external means of measuring flow will not
be permanent, the tubes must be restored to their
original condition.
Warning!
In order to prevent personal injury and damage
to machinery, the safety isolating switch must be
switched off and the safety fuses of the fan must
be removed before beginning work on
the fan.
If two fans are installed in the fan section, the k-value is applicable to
the total airflow generated by both fans
q = q20 , m3/s
(273 + t)
293
Size EQLA-aaa-b
k-factor
Fan size
L=1 L=2
008-2, 009-2 48,0 42,4 028
008-3, 009-3 48,0 34,0 031
011-2, 014-2 37,89 25,7 035
011-3, 014-3, 018-2, 020-2 23,38 20,0 040
018-3, 020-3, 023-2 18,27 16,4 045
023-3, 027-2 14,29 12,9 050
027-3, 032-2, 036-2, 041-2 11,69 10,1 056
032-3, 036-3, 041-3, 045-2, 047-2, 050-2 9,45 8,57 063
045-3, 047-3, 050-3, 054-2, 056-2, 063-2,
072-2
6,79 6,79 071
054-3, 056-3, 063-3, 068-2, 072-3, 079-2 5,37 5,37 080
068-3, 079-3, 090-2 4,24 4,24 090
090-3 3,43 3,43 100