Installation and maintenance instructions
FläktGroup DC_9346GB 20180326_R0 Specifications are subject to alteration without notice
MOTOR CABLE
Motor and speed controller is delivered with 3,5 m long motor cable. If it
should be replaced with longer one or disconnected at the other end.
Following rules should be meet and considered:
• Motor cable should be shielded type.
• Shield should be grounded 360° at both ends of cable.
• Motor cable should be no longer than 20 meters.
• Motor is connected to star inside the motor.
• Phase wires are connected to terminals U1, V1, W1.
• Terminal connectors are not needed.
CONTROL CABLE
Control cable should be shielded. Keep control cable distance min 200
mm from mains and motor cable.
CONTROL SIGNALS
Fan is started with potential free switch connected be-
tween terminals 12 and 18. The circuit voltage is 24 VDC. AUTO mode
should be selected from operation panel.
Speed reference can be given from with 0…10 V signal connected in
terminals 53(+) and 55(-).
Alarm signal is available in relay1 (terminals 01, 02 and 03).
Running indication is available in relay 2 (terminals 04, 05 and 06).
SINGLE SPEED OPERATION:
Set constant speed reference (rpm) in parameter 411. Only external start
signal is needed.
MODBUS RTU:
Speed controller can be controlled via Modbus RTU. RS-485 cable is
connected to the terminals 68 (P), 69 (N) and 61 (COM). If speed controller
is last unit in line, it should be terminated by setting switch S801 in ON
position. Modbus operation is described in speed controller operation
instructions.
PARAMETERS
Speed controller parameters are set at the factory pro-viding for optimal
performance of fan and motor.
This includes motor parameters, ramp times, starting and stopping
methods and speed limitations. Changing of these parameters may result
in unstable operation or motor won’t start. Original parameter values can
be downloaded from operation panel in case of losing them.
SUPPLY CABLE
Mount mains supply to terminals L1, L2 and L3 and ground wires to earth
terminal and tighten.
SHORT CIRCUIT PROTECTION:
The speed controller must be protected against short-circuit to avoid
electrical or fire hazard. The fuses mentioned below are recommended
to use to protect service personnel and equipment in case of an internal
failure in the speed controller. Speed controller provides full short circuit
protection in case of a short circuit on the motor output.
OVER CURRENT PROTECTION:
Provide overload protection to avoid fire hazard due to overheating of
the cables in the installation. The speed controller is equipped with an
internal over-current protection that can be used for upstream overload
protection. See par. 4-18 Current Limit. Moreover, fuses or circuit breakers
can be used to provide the over-current protection in the installation.
Over-current protection must always be carried out according to national
regulations.
LEAKAGE CURRENT (>3,5MA)
EN/IEC61800-5-1 (Power Drive System Product Stand-ard) requires
special care if the leakage current exceeds 3,5 mA. Earth grounding
must be reinforced in one of the following ways:
• Earth ground wire of at least 10 mm
2
• Two separate earth ground wires both complying
with the dimensioning rules
ISOLATION SWITCH
All speed controllers may be used with an isolated input source as well
as with ground reference power lines.
RECOMMENDED PRE-FUSES
Power 0,75 1,5 2,2 3 4 5,5 7,5 11 15
3x380-
400V
UL (A) 10 10 15 15 15 25 25 50 50
IEC (A)
type gG 10 10 16 16 16 25 25 50 50