Mounting instruction 28 August 2023
008298 (updated in 2023)
Mounting of cooling water hoses on CMO, HPO and TCMO
Use this Mounting instruction for the following sets of cooling water hoses:
Compressor type Set no.
CMO/HPO 24/34 3185.1113
CMO/HPO 26/36 3185.1114
CMO/TCMO/HPO 28/38 3185.1115
TCMO/HPO side covers only 3185.1116
When the compressor unit has been connected to the refrigeration plant, the cooling water hoses are mounted on
the compressor and connected to the water supply system.
The cooling water hoses form part of a set, which includes the following parts (depending on compressor type):
Necessary number of complete hoses as stated in the following tables for each compressor type. The types
of hoses are shown in Fig. 1.
Necessary fittings for connecting the cooling water hoses as illustrated in the Fittings tables.
Threaded nipples for connecting the hoses to the water supply system.
Hose types
Fig. 1
Mounting the cooling water system
Before mounting the hoses, we recommend checking that all parts are included according to the specification in this
Mounting instruction.
D
E
L
F
A
B
C
L
Page 2 of 5
Johnson Controls Denmark ApS
Christian X's Vej 201 ∙ 8270 Højbjerg ∙ Denmark
Phone +45 87 36 70 00 ∙ www.sabroe.com
CVR No 19 05 61 71
Mount the threaded nipples in the top and side covers first. The threaded nipples are fitted without gaskets
as they seal against the cover by means of the sealing edge Aas illustrated in Fig. 2.
Threaded nipple
Fig. 2
Tighten the threaded nipples to a torque of 80 Nm using a JW26 spanner
Mount the cooling water hoses and fittings as shown in the following drawings.
Before assembling the parts, apply a thin layer of grease to the cone, O-ring and thread, which facilitates
the mounting and makes it easier to disassemble the parts if necessary.
Tighten the union nut manually, and then tighten it 1/4 to 1/2 turn using a JW24 spanner.
Make sure the rubber hoses do not touch the compressor covers or discharge pipes. If necessary, it is rec-
ommended to secure the hoses by means of plastic strips.
Mount the inlet and discharge nipples, which have outside ISO 7/1 - R1/2" thread, and connect the hoses
to the water supply system.
When connecting the hoses to the water supply system, be aware of the stream direction of the water as
shown in the drawings.
See the section Water-cooling of the reciprocating compressor in the compressor manual to find information about
water consumption, pressure loss, operating limits and regulation of the water cooling system.
A
Page 3 of 5
Johnson Controls Denmark ApS
Christian X's Vej 201 ∙ 8270 Højbjerg ∙ Denmark
Phone +45 87 36 70 00 ∙ www.sabroe.com
CVR No 19 05 61 71
Cooling of top and side covers, T/CMO and HPO
Fig. 3
1
2
3
4
5
Inlet
Outlet
1
2
34
5
Inlet
Outlet
6
1
2
3
4
5
Inlet
Outlet
6
4
Page 4 of 5
Johnson Controls Denmark ApS
Christian X's Vej 201 ∙ 8270 Højbjerg ∙ Denmark
Phone +45 87 36 70 00 ∙ www.sabroe.com
CVR No 19 05 61 71
CMO/HPO 24/34
31.851.113
CMO/HPO 26/36
31.851.114
CMO/HPO 28/38
31.851.115
Pos. no. Quantity Hose
type
L
(mm) Pos. no. Quantity Hose
type
L
(mm) Pos. no. Quantity Hose
type
L
(mm)
1 1 C 940 1 1 C 870 1 1 C 820
2 1 C 130 2 1 C 145 2 1 C 145
3 1 E 280 3 1 E 215 3 2 D,40* 100
4 1 C 440 4 1 E 250 4 1 E 150
5 1 A 530 5 1 C 255 5 1 C 145
6 1 A 455 6 1 A 670
*Angle direction of hose fitting.
Fittings Strips
Part no. 1349.264 1349.261 1349.262 1349.263 1349.259 1349.265 1554.062
24/34 0 1 1 5 1 2 4
26/36 0 1 1 7 1 2 6
28/38 0 1 1 9 1 2 6
Table 1: Number of fittings - top and side covers.
Page 5 of 5
Johnson Controls Denmark ApS
Christian X's Vej 201 ∙ 8270 Højbjerg ∙ Denmark
Phone +45 87 36 70 00 ∙ www.sabroe.com
CVR No 19 05 61 71
Cooling of side covers only - T/CMO and HPO
Fig. 4
T/CMO and HPO
3185–1116
Pos. no. Hose type L (mm)
1 C 500
2 D,90 440
Fittings Strips
Part no. 1349.264 1349.261 1349.262 1349.263 1349.259 1349.265 1554.062
24/34 0 0 0 2 0 2 4
26/36 0 0 0 2 0 2 4
28/38 0 0 0 2 0 2 4
Table 2: Fittings
1
2
Inlet
Outlet