Mounting instruction
0006241
31 August 2017
Mounting of liquid drain system in R717 HPC 104-108 and HPX 704-708 compressors
The compressor must be evacuated before mounting the liquid drain system.
Fig. 1: Remove the old suction filter end cover (without sight glass) and the old suction filter (without “gutter”).
Fig. 2: Place the new suction filter with the “gutter” downwards.
Fig. 3: Place the new suction filter end covers (with sight glass) with the drain hole pointing downwards.
Suction filter end cover
“Gutter”
Drain hole
Page 2 of 7
Johnson Controls Denmark ApS
Christian X's Vej 201 ∙ 8270 Højbjerg ∙ Denmark
Phone +45 87 36 70 00 ∙ Fax +45 87 36 70 05 ∙ www.sabroe.com
CVR No 19 05 61 71
Fig. 4: Mount the outside pipes according to compressor size.
HPC 104/
HPX 704
HPC 106/
HPX 706
HPC 108/
HPX 708
Page 3 of 7
Johnson Controls Denmark ApS
Christian X's Vej 201 ∙ 8270 Højbjerg ∙ Denmark
Phone +45 87 36 70 00 ∙ Fax +45 87 36 70 05 ∙ www.sabroe.com
CVR No 19 05 61 71
Fig. 5: Remove the left side cover (seen from the oil pump end).
Fig. 6: Remove the old pressure pipe (the pipe must be cut before removal).
Left side cover
Oil pressure pipe
Page 4 of 7
Johnson Controls Denmark ApS
Christian X's Vej 201 ∙ 8270 Højbjerg ∙ Denmark
Phone +45 87 36 70 00 ∙ Fax +45 87 36 70 05 ∙ www.sabroe.com
CVR No 19 05 61 71
Fig. 7: Fit the heat exchanger into the compressor according to the picture. The heat exchanger should replace the oil pressure pipe.
Fig. 8: Fittings in the oil pump end.
Page 5 of 7
Johnson Controls Denmark ApS
Christian X's Vej 201 ∙ 8270 Højbjerg ∙ Denmark
Phone +45 87 36 70 00 ∙ Fax +45 87 36 70 05 ∙ www.sabroe.com
CVR No 19 05 61 71
Fig. 9: Fitting in the drive end.
Fig. 10: The internal pipework for the oil pump end is similar to the picture for all compressor sizes.
Page 6 of 7
Johnson Controls Denmark ApS
Christian X's Vej 201 ∙ 8270 Højbjerg ∙ Denmark
Phone +45 87 36 70 00 ∙ Fax +45 87 36 70 05 ∙ www.sabroe.com
CVR No 19 05 61 71
Fig. 11: The same as Fig. 7 but seen from another angle. It should not be necessary to remove both side covers (only 1 cover gasket is
provided).
HPC 104/
HPX 704
HPC 106/
HPX 706
Page 7 of 7
Johnson Controls Denmark ApS
Christian X's Vej 201 ∙ 8270 Højbjerg ∙ Denmark
Phone +45 87 36 70 00 ∙ Fax +45 87 36 70 05 ∙ www.sabroe.com
CVR No 19 05 61 71
Fig. 12: Mount the pipes for the shaft seal end according to the pictures.
Change the side cover gasket and remount the side cover.
Fig. 13: Mount the painted oil cooler pipe - remember to put an isolation tube on it before mounting.
Erhardt Nielsen
Manager, Compressor Development
Engineering, Sabroe Products
Industrial Refrigeration Europe
Tel: +45 87 36 77 20
Mob: +45 29 22 77 20
Internet: http://www.johnsoncontrols.dk/
HPC 108/
HPX 708
Oil cooler pipe
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7

Sabroe Mounting of liquid drain system in R717 HPC 104-108 and HPX 704-708 compressors Installation guide

Type
Installation guide

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI