Fulton VMP-W Operating instructions

Type
Operating instructions

This manual is also suitable for

INSTALLATION AND
OPERATION MANUAL
Vertical Multi-Port
Hot Water Boilers
Model VMP-W
40 -150 HP
Serial/ National
Board Number
Model
Fulton Order
Sold To
Job Name
Date
VMPW-IOM-2012-1001
Questions? Call (315) 298-5121, or visit us online at www.fulton.com
VMPW-IOM-2012-1001 TABLE OF CONTENTS
0-1
Introduction 1-1
Overview .............................................................................................................. 1-2
Warnings & Cautions ............................................................................................ 1-2
Disclaimers and Local Codes ................................................................................ 1-2
Installation 2-1
Placement & Rigging ........................................................................................... 2-2
Clearances & Serviceability .................................................................................. 2-4
Environment, Ventilation and Combustion Air Requirements ............................ 2-4
Utilities ................................................................................................................. 2-6
THE GAS SUPPLY ..........................................................................................................................26
THE OIL SUPPLY ...........................................................................................................................27
Electrical Supply ................................................................................................... 2-8
Water Supply ........................................................................................................ 2-8
INSTALL WATER PIPING ...............................................................................................................28
Water Chemistry Requirements ........................................................................... 2-9
PREVENT OXYGEN CONTAMINATION ........................................................................................210
ELIMINATE SYSTEM AIR ............................................................................................................210
Piping Speci cations ..........................................................................................2-11
Insulation ........................................................................................................... 2-12
System Interfaces ............................................................................................... 2-12
FILL CONNECTION ......................................................................................................................212
Assembly of Multi-Skid Systems ........................................................................2-12
Stack and Flue ....................................................................................................2-13
EXHAUST SIDE WALL VENTING ................................................................................................215
Testing ................................................................................................................ 2-16
Operation 3-1
Start-Up Preparation & Installation Review ........................................................ 3-2
Start-Up Service ................................................................................................... 3-3
Initial Start-Up ..................................................................................................... 3-4
COMBUSTION ...............................................................................................................................34
Flame Programmers ............................................................................................ 3-5
Operating Controls ............................................................................................... 3-5
WATER RELIEF VALVE ...................................................................................................................35
WATER OUTLET VALVE .................................................................................................................35
TEMPERATURE CONTROL ...........................................................................................................35
OPERATING TEMPERATURE AQUASTAT ......................................................................................35
HIGH LIMIT AQUASTAT/HIGH TEMPERATURE LIMIT ..................................................................36
AIR SAFETY SWITCH ....................................................................................................................36
PROBE TYPE LOW WATER CUTOFF .............................................................................................36
Optional Circulating Pump Switch ....................................................................... 3-6
Cycle Testing ......................................................................................................... 3-6
Before Leaving the Installation ............................................................................ 3-6
Maintenance 4-1
Daily Maintenance Schedule ................................................................................ 4-2
Weekly Maintenance Schedule ............................................................................ 4-2
Monthly Maintenance Schedule .......................................................................... 4-2
Recommended Semi-Annual Maintenance Schedule ......................................... 4-3
Recommended Annual Maintenance Schedule .................................................. 4-5
Procedure for Primary Air Adjustment/Inspection .............................................. 4-6
Procedure for Secondary Air Adjustment/Inspection .......................................... 4-6
Procedure for Flame Scanner Adjustment ........................................................... 4-7
GAS UNIT ......................................................................................................................................47
OIL UNIT ......................................................................................................................................47
Procedure for Removing/Cleaning the Burner .................................................... 4-8
Procedure for Soot Cleaning................................................................................. 4-8
After All Repairs or Maintenance ......................................................................... 4-9
Troubleshooting ................................................................................................... 4-9
Warranty & Parts 5-1
Standard Warranty for Fulton Boilers................................................................... 5-3
Parts ..................................................................................................................... 5-4
© The Fulton Companies 2012
TABLE OF CONTENTS VMPW-IOM-2012-1001
0-2
Questions? Call (315) 298-5121, or visit us online at www.fulton.com 1-1
INTRODUCTION
INTRODUCTION 1
INSTALLATION 2
OPERATION 3
MAINTENANCE 4
WARRANTY & PARTS 5
© The Fulton Companies 2012
1-2
INTRODUCTION VMPW-IOM-2012-1001 SECTION 1
Overview
Prior to shipment, the following inspections and tests are
made to ensure the highest standards of manufacturing for
our customers:
§Material inspections
§Manufacturing process inspections
§American Society of Mechanical Engineers (ASME)
welding inspection
§ASME hydrostatic test inspection
§Electrical components inspection
§Operating test
§Final engineering inspection
§Crating inspection
This manual is provided as a guide to the correct operation
and maintenance of your Fulton equipment, and should be
read in its entirety and be made permanently available to the
sta responsible for the operation of the boiler. It should not,
however, be considered as a complete code of practice, nor
should it replace existing codes or standards which may be
applicable. Fulton reserves the right to change any part of
this installation, operation and maintenance manual.
Installation, start-up, and maintenance of this equipment
can be hazardous and requires trained, quali ed installers
and service personnel. Trained personnel are responsible
for the installation, operation, and maintenance of this
product, and for the safety assurance of installation,
operation, and maintenance processes. Do not install,
operate, service or repair any component of this
equipment unless you are quali ed and fully understand
all requirements and procedures. Trained personnel
refers to those who have completed Fulton Service School
training speci c to this product.
When working on this equipment, observe all warnings,
cautions, and notes in literature, on stickers and labels, and
any additional safety precautions that apply. Follow all safety
codes and wear appropriate safety protection. Follow all
jurisdictional codes and consult any jursidictional authorities
prior to installation.
Warnings & Cautions
WARNINGS and CAUTIONS appear in various chapters of this
manual. It is critical that all personnel read and adhere to all
information contained in WARNINGS and CAUTIONS.
§WARNINGS must be observed to prevent serious injury
or death to personnel.
§CAUTIONS must be observed to prevent damage
or destruction of equipment or loss of operating
e ectiveness.
All Warnings and Cautions are for reference and guidance
purposes, and do not substitute for required professional
training, conduct, and strict adherence to applicable
jurisdictional/professional codes or regulations.
Disclaimers and Local Codes
Installation of the equipment shall conform to all the
requirements or all national, state and local codes established
by the authorities having jurisdiction or, in the absence
of such requirements, in the US to the National Fuel Gas
Code ANSI Z2231/NFPA 54 latest edition, and the speci c
instructions in this manual. Authorities having jurisdiction
should be consulted prior to installation.
When required by local codes, the installation must conform
to the American Society of Mechanical Engineers Safety Code
for Controls and Safety Devices for Automatically Fired Boilers
(ASME CSD-1).
Questions? Call (315) 298-5121, or visit us online at www.fulton.com 2-1
INSTALLATION
INTRODUCTION 1
INSTALLATION 2
OPERATION 3
MAINTENANCE 4
WARRANTY & PARTS 5
© The Fulton Companies 2012
INSTALLATION VMPW-IOM-2012-1001 SECTION 2
2-2
! WARNING
All information in this manual is for
reference and guidance purposes,
and does not substitute for required
professional training, conduct,
and strict adherence to applicable
jurisdictional/professional codes and
regulations.
Crystalline silica may be present
in components of this equipment.
Exposure to crystalline silica may
pose signi cant health hazards,
including but not limited to eye and
respiratory system damage. Per
the Centers for Disease Control and
Prevention (CDC) and Occupational
Safety and Health Administration
(OSHA), appropriate Personal
Protective Equipment must be worn
to minimize exposure to hazardous
substances. Refer to most current
guidelines o ered by the CDC and
OSHA for more information, including
Personal Protective Equipment
recommendations.
This boiler is certi ed for indoor
installation only.
A competent rigger experienced in
handling heavy equipment should
handle rigging your equipment into
position.
The equipment must be installed on a
non-combustible surface.
Do not store or use gasoline or other
ammable vapors and liquids or
corrosive materials in the vicinity of
this or any other appliances.
4 CAUTION
Do not allow weight to bear on
equipment components to prevent
damage.
Placement & Rigging
Proper placement of your Fulton Product (see Figure 1, and Tables 1 and 2) is
essential. Attention paid to the following points will save a great deal of di culty
in the future. Correct placement is the rst step to trouble-free installation,
operation and maintenance.
Adhere to the following for equipment placement and rigging:
1. Consult authorities with jurisdiction over any national or local codes
(including but not limited to National Fire Protection Agency (NFPA),
American National Standards Institute (ANSI), Underwriters Laboratories
(UL), SCA, and ASME, which might be applicable to boiler applications
before beginning.
2. Make appropriate determinations for placement, based on the following:
§Check building speci cations and Table 2 for unit weights.
§Ensure the equipment is to be placed on a non-combustible level base
with adequate clearances from combustible materials. See Clearances &
Serviceability section.
§Locate boiler as close as possible to the place where the heat will be used
in order to keep pipe work costs to a minimum.
§Ensure that there is adequate clearance around the unit to provide
access for operators and maintenance personnel to all parts of the
equipment. Ensure also that clearance provides for component removal for
maintenance. See Clearances & Serviceability section. The equipment
should be placed in a suitable boiler house or well ventilated separate
room through which personnel do not normally pass. The layout should
eliminate tra c in potentially hazardous areas. For instance, the service
engineer or the operator should not have to pass exposed, hot pipe work
to make adjustments to the boiler controls.
§Ensure the equipment is to be placed in such a way that the electrical
components are protected from exposure to water or excessive humidity.
§Ensure the boiler is located a safe distance from the fuel oil tank (if
applicable).
3. Determine rigging procedure, based on the following:
§Units are shipped and crated for forklift transport. Once uncrated, all units
can be transported with a forklift and/or lifting lugs at the top of the boiler.
All skidded units can be moved with forklifts.
§If means of lifting are not available, place rollers beneath the frame of the
equipment for guidance to the position of where it is to be installed.
§Under no circumstances allow weight to bear on the jacket, control panel,
burner, fuel train or fan housing of any Fulton boiler.
§Tagged support legs on boiler are for shipping purposes only. These must be
removed at time of installation, and may not be used to mount or anchor
boilers.
Questions? Call (315) 298-5121, or visit us online at www.fulton.com
SECTION 2 VMPW-IOM-2012-1001 INSTALLATION
2-3
TABLE 1 DIMENSIONS REFER TO FIGURE 1
Model VMP-W 40 50 60 80 100 130 150
Unit Size BHP 40 50 60 80 100 130 150
A. Boiler Diameter
IN
MM
49
1245
55
1397
55
1397
63
1600
69
1753
76.5
1943
76.5
1943
(B) Boiler Height
IN
MM
84
2133
91
2312
97
2464
100
2540
100
2540
115
2921
115
2921
(C) Boiler Depth
IN
MM
90
2286
100
2540
100
2540
114
2896
119
3022
128
3251
130
3302
(D) Boiler Height With Trim
IN
MM
107
2718
113
2870
119
3023
125
3175
125
3175
149
3785
149
3785
(E) Overall Boiler Width
IN
MM
56
1422
62
1575
62
1575
68
1727
74
1880
84.5
2146
84.5
2146
(F) Flue Outlet Diameter
IN
MM
12
305
12
305
12
305
14
356
14
356
14
356
14
356
(G) To Center of Flue Outlet
IN
MM
79
2006
83
2108
89
2261
95
2413
95
2413
107
2718
107
2718
(H) Return Water Inlet Height
IN
MM
20.3
516
20.3
516
20.3
516
20.3
516
20.3
516
23.6
599
23.6
599
(J) Water Outlet
IN
MM
73.8
1870
77.8
1980
83.8
2130
89.8
2280
89.8
2280
101.1
2570
101.1
2570
(K) Min. Clearance to Ceiling for Burner Removal
IN
MM
123
3124
135
3429
144
3658
147
3734
147
3734
155
3937
155
3937
All data is approximate. Fulton reserves the right to change data without prior notice.
FIGURE 1 MODEL VMPW DIMENSIONS/SPECIFICATIONS REFER TO TABLES 1 AND 2
F
E
C
G
K
DB
J
A
H
H.H.
© The Fulton Companies 2012
INSTALLATION VMPW-IOM-2012-1001 SECTION 2
2-4
NOTE: ´When calculating ventilation requirements, heat losses from the Fulton
equipment (and other equipment) should be considered.
Clearances & Serviceability
Adhere to the following for equipment clearances and serviceability:
1. Ensure appropriate front, back, sides and top clearances are met. This
will allow access around the equipment to facilitate maintenance and a
safe work environment, and ensure technicians will commission the unit.
Technicians will not commence commissioning if hazardous conditions
exist.
2. Place boiler with clearances to unprotected combustible materials,
including plaster or combustible supports, not less than the following:
§Heater Front: 36 in. (914 mm)
§Heater Sides and Rear: 18 in. (457 mm)
§Heater top: 24 in. (610 mm)
§Allow for additional minimum clearances for personnel access and burner
removal, as necessary.
§Verify that all clearances are acceptable with the local ordinances.
Environment, Ventilation and Combustion Air
Requirements
It is critical to provide free access of air to the boiler. To burn fuel properly, it
requires one square inch opening for every 3,000 BTU input of fuel (6.4 cm2 for
every 756 kCal).
Adhere to the following to meet ventilation and combustion air requirements:
1. Install two fresh air openings, one at a low level, 24” (610 mm) from the
oor, and one at a higher level on the equipment room wall. This will
provide a ow of air to exhaust the hot air from the equipment room.
2. Ensure the equipment room air supply openings are kept clear at all times.
! WARNING
All information in this manual is for
reference and guidance purposes,
and does not substitute for required
professional training, conduct, and strict
adherence to applicable jurisdictional/
professional codes and regulations.
Failure to provide required and safe
access to the equipment could impede
commissioning and maintenance.
Service technicians are instructed not to
commence commissioning if hazardous
conditions exist.
Failure to provide proper minimum
clearances between equipment and
combustible materials may result in re.
The installation of an exhaust fan in the
boiler room is not recommended. An
exhaust fan or similar equipment can
create a downdraft in the stack or restrict
the burner’s air supply and result in poor
combustion. It is essential only fresh
air be allowed to enter the combustion
air system. Foreign substances such as
combustible volatiles and lint may create
hazardous conditions.
Ensure all labels on the boiler are legible.
All connections and safety devices, both
mechanical and electrical, must be kept
clean, with ease of access for inspection,
use and maintenance.
Questions? Call (315) 298-5121, or visit us online at www.fulton.com
SECTION 2 VMPW-IOM-2012-1001 INSTALLATION
2-5
TABLE 2  SPECIFICATIONS REFER TO FIGURE 1
Model VMP-W 40 50 60 80 100 130 150
Boiler Connec ons
Safety Valve Outlet
IN
MM
1.5
38.1
1.5
38.1
1.5
38.1
2
50.8
2
50.8
2
50.8
2
50.8
Safety Valve Inlet
IN
MM
1.25
31.8
1.25
31.8
1.25
31.8
1.5
38.1
1.5
38.1
1.5
38.1
1.5
38.1
Natural Gas Connec on
IN
MM
1.5
38
1.5
38
2
51
2
51
2
51
2.5
63
2.5
63
Water Supply & Return Connec ons*
IN
MM
4
102
4
102
4
102
4
102
4
102
4
102
4
102
Ra ngs (sea level to 3000  /914 m) Output
1000 BTU/HR
1000 KCAL/HR
1356
342
1693
427
2033
512
2710
683
3387
853
4405
1110
5081
1280
Water Content
GAL
Liters
210
795
290
1098
315
1192
440
1665
602
2278
920
3482
920
3482
Model VMP-W STANDARD MOTOR
Light Oil Connec on
IN
MM
.25
6
.25
6
.25
6
.25
6
.25
6
.375
9.5
.375
9.5
Burner Motor
HP
Wa! s
1.5
1119
1.5
1119
1.5
1119
3
2237
3
2237
10
7460
10
7460
Approximate Weights
Shipping Weight
LB
KG
5775
2620
6575
2980
7370
3340
8000
3636
9500
4318
12,350
5601
12,500
5675
Opera ng Weight
LB
KG
7526
3414
8994
4080
9997
4535
11670
5294
14520
6587
20023
9083
20172
9150
Approximate Fuel Consump on at Rated Capacity+
Natural Gas
FT3
M3
1595
45
1992
56
2392
68
3188
90
3985
113
5182
147
5978
169
LP Gas
FT3
M3
638
18
797
23
957
27
1275
36
1594
45
2080
59
2381
68
Light Oil
GPH
LPH
11
41.6
14
53
17
64.3
23
87
28
106
37
140
42
159
Min. Gas Pressure Required; In. W.C. 7 7 7 9 9 40 40
Max Gas Pressure Required (Standard Gas Train) In. W.C. 13 13 13 27 27 10 psig 10 psig
Electric Power Requirements/Amps for Burner Motor
208V 50/60 CY 3 Phase (Gas/Oil) 6.6/7.5 6.6/7.5 6.6/7.5 10.6 10.6 30.8 30.8
230V 50/60 CY 3 Phase (Gas/Oil) 6.0/6.8 6.0/6.8 6.0/6.8 9.6 9.6 28 28
460V 50/60 CY 3 Phase (Gas/Oil) 3.0/3.4 3.0/3.4 3.0/3.4 4.8 4.8 14 14
* 150 pound fl anged.
CONTINUED ON NEXT PAGE
© The Fulton Companies 2012
INSTALLATION VMPW-IOM-2012-1001 SECTION 2
2-6
3. See Table 3 for minimum make up air openings required
for each model.
TABLE 3 MINIMUM MAKE UP AIR OPENING REQUIREMENTS
Model Fresh Air Opening FT2 (M2)
40 1 (.09)
50 1 (.09)
60 1.5 (.14)
80 4 (.37)
100 4 (.37)
130 5 (.46)
150 7.5 (.69)
4. If positive forced ventilation is adopted, ensure that
there will be no appreciable pressure variation in the
equipment room.
5. Avoid ventilation which creates a negative pressure
in the building as it will seriously a ect combustion
and proper operation of the burner. Please note that
exhaust fans or similar equipment can create a down
draft in the chimney or starve the burner’s air supply.
Either case may result in poor combustion or nuisance
failures. A properly designed make-up air system in the
equipment room will preclude these possibilities and is
required to maintain proper combustion.
6. Eliminate potential for high risk situations for particulate
matter to be in the combustion air supply (e.g., as a
result of construction and maintenance activities).
Utilities
¡The Gas Supply
Adhere to the following for gas supply installation:
1. Install gas piping in accordance with all applicable
codes.
2. Ensure pipe and ttings used are new and free of dirt or
other deposits.
3. Ensure piping is of the proper size for adequate gas
supply to the gas head assembly. Consult your gas
company for speci c recommendations.
4. When making gas piping joints, use a sealing
compound resistant to the action of lique ed
petroleum gases. Do not use Te on tape on gas line
heads.
Model VMP-W Low Emissions (LE) MOTOR
Model VMP-WModel 40 50 60 80 100 130 150
Model VMP-W 40 50 60 80 100 130 150
Burner Motor **
HP
Wa! s
5
3730
5
3730
5
3730
5
3730
5
3730
Consult
Factory
Consult
Factory
Approximate Weights
Shipping Weight
LB
KG
6575
2982
7373
3345
8170
3706
8800
3992
10300
4672
12800
5806
12800
5806
Opera" ng Weight
LB
KG
8659
3928
9684
4393
10671
4840
12051
5466
14700
6668
20585
9337
20585
9337
Approximate Fuel Consump! on at Rated Capacity+
Natural Gas
FT3
M3
1595
45
1992
56
2392
68
3188
90
3985
113
5182
147
5978
169
Required Gas Pressure (IN. W.C./PSIG)
Minimum/Maximum 30/10 30/10 40/10 40/10 40/10 60/10 60/10
208V, 60 CY, 3 Phase 16.7 16.7 16.7 16.7 24.2 Consult Factory
230V 60 CY 3 Phase 15.2 15.2 15.2 15.2 22 Consult Factory
460V 60 CY 3 Phase 7.6 7.6 7.6 7.6 11 Consult Factory
Specifi ca" ons and dimensions are approximate. We reserve the right to change data without prior no" ca" on.
Design condi" ons based on 160 F return and 180 F supply.
+ Consump" on based on natural gas 1000 Btu/$ 3.
** Sub 20 ppm; for lower requirements, consult factory.
Questions? Call (315) 298-5121, or visit us online at www.fulton.com
SECTION 2 VMPW-IOM-2012-1001 INSTALLATION
2-7
5. Ensure no piping stresses are transmitted to the equipment. The
equipment shall not be used as a pipe anchor.
6. Ensure all vent connections on diaphragms, gas valves, pressure
regulators, and pressure switches (gas- red units) are vented per local
code.
7. On gas- red units with NFPA 85 valve trains, ensure the vent valve is
piped to atmosphere per local code.
8. During any pressure testing of the system at pressures in excess of 1/2
psig (14 inch W.C.), isolate the boiler with the manual shuto valve
(located at the end of the supplied gas train) from the gas supply
piping system.
9. Ensure the supply pressure is regulated by a non-stacking, tight, shut-
o regulator.
10. Arrange gas piping so that it does not interfere with any cover or
burner, inhibit service or maintenance, or prevent access between
unit and walls or another unit.
11. After gas piping is completed and before wiring installation is started,
carefully check all piping connections, (factory and eld), for gas
leaks. Use an appropriate leak test solution.
¡The Oil Supply
Adhere to the following for installation:
1. Fuel pipes must be of approved materials and of a diameter suitable
for the quantity of oil being delivered to the burner. Vacuum must
not exceed 10 in. (254 mm) of mercury at the pump inlet. Maximum
inlet pressure to oil pump is 3 PSIG.
2. Make fuel connection in accordance with the details on the enclosed
fuel pump cut sheet.
3. Ensure fuel oil piping is in accordance with local/national
requirements.
4. Meet the maximum pressure allowed at the fuel oil pump inlet per
the National Fire Protection Association (NFPA).
5. Oil pumps are of a two-line design system, requiring a return line and
a supply line. The oil pump is factory set per Test Fire Sheet. Do not
alter the setting without consulting the factory.
6. A stop valve, a check valve, and an oil lter must be installed on the
oil supply line.
7. Ensure there are no loose ttings. Loose ttings in the fuel oil line will
permit air to enter the fuel line and cause improper ring.
! WARNING
A quali ed installer, service agency or the
gas supplier must perform installation and
service on the fuel delivery system.
Do not use matches, candles, ame or
other sources of ignition to check for gas
leaks.
What to do if you smell gas:
Do not try to light the appliance.
Do not touch any electrical switch.
Do not use any phone in the building.
Leave building and contact gas supplier
from neighbor’s phone. If you cannot
reach gas supplier, phone the re
department.
When making gas piping joints, maintain
proper ventilation to reduce breathing
hazards.
An exhaust fan may draw products of
combustion into the work environment
creating a possible hazard to personnel.
4 CAUTION
It is essential that only fresh air be allowed
to enter the combustion air system. Foreign
substances, such as combustible volatiles
and lint in the combustion system can create
hazardous conditions. If foreign substances
can enter the air stream, the combustion air
inlet must be piped to an outside location.
Failure to do so will void the warranty.
To avoid failures due to poor combustion,
ensure make-up air system is properly
designed.
© The Fulton Companies 2012
INSTALLATION VMPW-IOM-2012-1001 SECTION 2
2-8
Electrical Supply
Adhere to the following for electrical supply installation:
1. Locate electrical schematic diagram, a copy of which is inside of the panel
box.
2. Ensure the information on the electrical drawing corresponds to your
voltage and frequency. Check the supply voltage and make sure that there
is no over- or under-voltage exceeding 10% of the nominal value.
3. Install a separate fuse switch for the contactor and a separate fuse switch
for the circulating pump. If pump motor is 3/4 HP or larger, install an
across-the-line starting switch ahead of the circulating pump motor.
4. Install wiring and ground in equipment in accordance with authority
having jurisdiction or in absence of such requirements the National
Electrical Code, ANSI/NFPA.
5. Provide a fused disconnect sized for the unit. Size fuses according to motor
name plates and local electrical codes.
6. Connect power to the terminal strip as supplied on the inside of the panel
box.
Water Supply
¡Install Water Piping
All water supplies contain some solids, dissolved gases or dissolved minerals.
These may cause corrosion, deposition and/or fouling of equipment. To prevent
these contaminants from impacting boiler performance, valve operation and
general pipe longevity, each location must be analyzed and treated accordingly.
Adhere to the following for water piping installation:
1. Isolation valves and unions are recommended on both water connections
for ease of service.
2. Install piping so that the boiler is not supporting any additional piping.
3. Install manual purging valves in all loops and zones. Install a pressure-
reducing (automatic  ll) valve in the cold water  ll line to the boiler system.
Check that the proposed operation of zone valves, zone circulator(s) and
diverting valves will not isolate air separator(s) and/ or expansion tank(s)
from the boiler. Clearance from hot water pipes to combustibles must be at
least 6 inches (152 mm).
4. Pipe the water supply line to the lower opening on the back of the boiler.
Water stop valve should be in line between the boiler and the  rst piece
of equipment. Hot water outlet should be piped to process/equipment
requiring hot water. Water makeup supply should be installed. Hot water
inlet should be piped to the make-up water supply.
! WARNING
All information in this manual is for
reference and guidance purposes,
and does not substitute for required
professional training, conduct, and strict
adherence to applicable jurisdictional/
professional codes and regulations.
4 CAUTION
Loose ttings in the fuel oil line will permit
air to enter the fuel line and cause improper
ring.
Questions? Call (315) 298-5121, or visit us online at www.fulton.com
SECTION 2 VMPW-IOM-2012-1001 INSTALLATION
2-9
5. Pipe the water safety valve carry piping from the outlet of the valve to a
safe blow-o point.
NOTE: ´Do not alter water temperature/pressure gauge assembly in any way.
6. Drain valve is connected to the lowest opening at bottom rear of boiler.
Carry piping from the outlet of the valve to safe drain point. Provision
should be made for easy access to drain valve of boiler.
NOTE: ´The water connection on the top of the boiler is the outlet connection. The
water connection on the rear of the boiler is the inlet connection.
7. Install ltration to remove particulates if appropriate.
8. Install bypass chemical feeder for corrosion inhibitor maintenance if
appropriate.
9. Install corrosion coupon holder to assess corrosion inhibitor performance if
appropriate.
NOTE: ´The boiler is provided with a drain valve connection and a drain valve.
10. Heating system:
»An automatic pressure activated water make up valve with back
ow preventer. It must be set to maintain required Net Positive
Suction Head (NPSH) for re-circulating pumps, a positive system
pressure at the highest point of at least 5-10 PSIG, and make up
water valve should be designed to add water to the system at the
outlet of the boiler and should not be fed directly into the boiler.
»Air removal equipment, including an air separator and automatic
breather valves, along with a functioning expansion tank . Each
must be designed to system speci cations.
11. When used in conjunction with a refrigeration system, install the boiler
so that the chilled medium is piped in parallel with the boiler with
appropriate valves to prevent the chilled medium from entering the
boiler. If the boilers are connected to heating coils (located in air handling
units where they may be exposed to refrigerated air circulation) such
boiler piping systems must be equipped with  ow control valves or other
automatic means to prevent gravity circulation of the boiler water during
the cooling cycle.
Water Chemistry Requirements
System water chemistry requirements are as follows:
§pH: Range of 8.5 - 10.5
§Oxygen: Less than 250 ppb (operating condition)
§Total Iron/Copper: Less than 5 ppm
! WARNING
All information in this manual is for
reference and guidance purposes,
and does not substitute for required
professional training, conduct, and strict
adherence to applicable jurisdictional/
professional codes and regulations.
© The Fulton Companies 2012
INSTALLATION VMPW-IOM-2012-1001 SECTION 2
2-10
§Corrosion Inhibitor: Capable of maintaining iron corrosion rates <2
mpy. Due to changing environmental restrictions a non-heavy metal
ALL ORGANIC inhibitor is recommended which is designed for multi
metal systems including ferrous metals and yellow metals such as
copper and brass.
§Chloride: Less than 250 ppm
Adhere to the following:
1. Refer to your water conditioning or chemical treatment supplier for
analysis and recommendations for proper system conditions.
2. Follow a program with appropriate monitoring and maintenance of
system water conditions as provided by your water conditioning or
chemical treatment supplier.
3. Operate the boiler in a closed-loop system using water or water/glycol
(not requiring a make-up water supply). A large amount of improperly
treated make-up water can cause premature failure of the heat
exchanger resulting from scale build up. Scale build up will reduce the
e ciency and useful life of the boiler and is not covered under warranty.
¡Prevent Oxygen Contamination
There are several ways to prevent boiler water oxygen contamination:
§Minimize system leaks to minimize make up water requirement
§Do not use open tanks or ttings
§Do not use oxygen permeable materials anywhere in the water
system
§Repair leaks in the system quickly
§Eliminate ttings wherever possible
§Use air elimination devices in system piping
¡Eliminate System Air
NOTE: ´There are no built-in boiler air eliminating features.
Adhere to the following for air elimination:
1. The installation of an air separator and air eliminator (air vent) is required.
2. To prevent scale corrosion in boiler and associated piping, make up
water must be kept to a minimum. This is best achieved by ensuring
immediate repair of all leaks and that system pressure is maintained.
3. If a sealed diaphragm-type expansion tank is used, install an air
eliminator in the hot water piping at the air separator.
4. If an air cushion type expansion tank is used, pipe tank directly into
! WARNING
All information in this manual is for
reference and guidance purposes,
and does not substitute for required
professional training, conduct, and strict
adherence to applicable jurisdictional/
professional codes and regulations.
4 CAUTION
A large amount of improperly treated make-
up water can cause premature failure of the
heat exchanger resulting from scale build
up. Scale build up will reduce the e ciency
and useful life of the boiler and is not
covered under warranty.
Questions? Call (315) 298-5121, or visit us online at www.fulton.com
SECTION 2 VMPW-IOM-2012-1001 INSTALLATION
2-11
boiler supply.
5. On multi-zoned systems (or a system with both space and domestic water
heating), air elimination must be provided either in the common piping or
on every loop.
6. When the boiler is installed at a higher level than baseboard radiation (if
used), air elimination must be provided directly above the unit.
Piping Speci cations
For piping, the basic considerations are: the design temperature, the pressure
retained by the pipe, the uid in the pipe, the load resulting from thermal
expansion or contraction, impact or shock loads imparted such as water hammer,
external loads, wind loads and vibration from equipment.
Adhere to the following for piping installation:
1. Ensure the arrangement of the piping and its appurtenances takes into
consideration the location of other structures and equipment adjacent to
the piping, which may result in freezing interference and/or damage as a
result of expansion, contraction, vibration, or other movements.
2. Consider the appropriate location and orientation of valves necessary
for safe operation and isolation of the piping. Valves are used in piping
systems to stop and start the ow of uids, to regulate ow, to prevent the
back  ow, and to relieve excessive pressure build up in the piping.
3. Ensure all piping and piping components are suitable for the design
temperatures, pressure and uid used in the system.
4. Ensure all pipework is constructed from seamless mild steel pipe, Schedule
40 or Schedule 80 as required by code and/or application; or copper if
system parameters allow.
5. During construction of the installation, ensure that no dirt, water, or
residue from welding is left in the system.
6. Provide expansion joints or properly designed and sited loops to
accommodate thermal expansion. Thermal expansion should be calculated
using the maximum possible utilization  uid temperature, regardless of
whether the pipe considered is in the feed or return circuit. Steel pipe will
expand approximately 1 “ per 100 over a 10F temperature rise (1 mm
per meter over 100 C rise).
7. Provide supports and anchors for all pipes where necessary to prevent
undue stresses from being placed on items of equipment, including
pumps, valves, and the boiler. Supports and anchors which will not
interfere with thermal expansion should be chosen.
8. Cut screw threads carefully and accurately. If possible, new tools should be
used. It is recommended that GR5 or higher tensile steel bolts be used for
all anged joints.
9. Use gaskets to make all  anged connections. Gasketing material must be
! WARNING
All information in this manual is for
reference and guidance purposes,
and does not substitute for required
professional training, conduct, and strict
adherence to applicable jurisdictional/
professional codes and regulations.
The vent line connection on the gas
pressure regulator must be piped to
outdoor air by the installer in accordance
with National Fuel Gas Code, ANSI Z223-
1-1991 or latest addenda. In Canada, gas
installations must be in accordance with
the current CAN/CGA B149.1 and 2 and/or
local codes.
4 CAUTION
Some soap used for leak testing is
corrosive to certain types of metals. Use
an appropriate leak test solution. Clean all
piping thoroughly after completing the leak
check.
© The Fulton Companies 2012
INSTALLATION VMPW-IOM-2012-1001 SECTION 2
2-12
suitable for use with the pressure, temperatures and  uids in the system.
Ensure that all bolts are tightened evenly and to the torque recommended
values provided by the gasket manufacturer.
10. Install high point bleeds at all high points in the system piping. 1/2 x 12
nipples welded in the top of the piping with ball valves and plugs attached
are to be used.
11. Install all pipes with a pitch to facilitate draining and venting.
Insulation
After the appropriate system tests have been satisfactorily completed (see
Testing section of this manual), all hot pipework and vessels must be adequately
insulated with material suited to the temperature and application to prevent
both heat loss and personnel injury. For inspection and maintenance purposes,
leave pumps,  anges, valves and  ttings uninsulated but suitably shielded for
safety. Removable insulation may also be used over these components.
System Interfaces
Proper selection and installation of the components in the system will ensure
proper and safe operation of the boiler. Consult Fulton representative or contact
Fulton at (315) 298-5121.
¡Fill Connection
The system is usually lled from the lowest point, with the aid of a pump. On skid-
mounted units, a ll connection is provided in the inlet piping to the pump.
Pressure Gauges
The range in which readings are expected to fall should comprise mid-scale
on the pressure gauge chosen. Pressure gauges must be able to withstand
overpressure equal to the rating of the safety relief valves, normally 100 psig.
NOTE: ´The Water temperature pressure gauge should not be altered in any way.
Assembly of Multi-Skid Systems
Adhere to the following for multi-skid engineered systems:
1. Refer to the Fulton mechanical/electrical drawings during assembly.
2. Ensure that equipment orientation allows for operation interface and
maintenance.
3. Align the skids as shown on the drawings ensuring that skid fasteners (skid
joint angles) are matched. The skid joint angles are a matched set and the
edges of the fasteners should be exactly aligned.
! WARNING
All information in this manual is for
reference and guidance purposes,
and does not substitute for required
professional training, conduct,
and strict adherence to applicable
jurisdictional/professional codes and
regulations.
Hot pipework and vessels must be
adequately insulated with material
suited to the temperature and
application to prevent both heat loss
and personnel injury.
Questions? Call (315) 298-5121, or visit us online at www.fulton.com
SECTION 2 VMPW-IOM-2012-1001 INSTALLATION
2-13
! WARNING
All information in this manual is for
reference and guidance purposes,
and does not substitute for required
professional training, conduct,
and strict adherence to applicable
jurisdictional/professional codes and
regulations.
Assure all electrical connections are
powered down prior to attempting
replacement or service of electrical
components or connections of the
equipment.
Cements for plastic pipe should
be kept away from all sources of
ignition. Proper ventilation should
be maintained to reduce the hazard
and to minimize breathing of cement
vapors.
No shuto of any kind may be
placed between the safety relief
valve and the equipment, or in the
discharge pipe between such valve
and the atmosphere. Doing so may
cause accidental explosion from
overpressure.
Discharge from safety relief valve
must be con gured so that there
is no danger of scalding personnel
or causing equipment damage.
Provisions must be made to properly
drain safety relief valve discharge
piping.
For reasons of safety, the hot exhaust
gas duct and chimney must be
insulated or shielded within the
locality of the heater in compliance
with local codes and regulations.
4 CAUTION
The stack arrangement and draft
conditions should be in accordance
with the information in this manual for
proper performance of the equipment.
NOTE: ´Do not bolt the skids to the housekeeping pad/ oor until all of the piping
has been reassembled and tightened.
4. Ensure the skids are level and at before fastening the skids together with
the supplied bolts. The skids should be leveled front to back, side to side
and corner to corner. Failure to properly level the skids will result in piping
misalignment. A level or laser level should be used to verify skid alignment
(when a standard level is used, the length should be appropriate for the
skid). If assembling multi-component support stands, attach sections
using the supplied bolts through the tank frame mounting plates. These
should be hand tight until all of the piping is assembled. Note: skids are
leveled at the factory using a laser level.
5. Connect the piping between the skids by matching the union connections
and/or ange stamps and tightening. Refer to the mechanical drawing
as necessary to con rm location of spool pieces etc. as the ange stamps
are shown on the drawing in hexagonal callouts. The  ange stamps
should matched and aligned (the  ange stamps should be directly across
from one another. Rotating a ange will result in piping misalignment).
Bolts should be hand tight until all of the piping is assembled. Refer to
the appropriate instructions to tighten the anges to the required torque
speci cations. Support pipe runs as required.
6. Ensure that a low point drain is installed in the piping.
7. Connect the conduit runs between the skids and tighten conduit
connectors.
8. Locate the supplied wiring for the equipment and pull wiring through
the appropriate conduit runs. Electrical wires are labeled for easy landing.
Connect all wiring per the Fulton supplied electrical drawings.
9. If a header is supplied, mount the header as shown in the mechanical
drawing.
NOTE: ´For piping supplied in sections, make up and connect hand tight until all
sections are in place to ensure sections align properly. Sections are match marked
for reassembly.
10. Tighten all connections.
11. Pneumatically test the piping (at 15 psig maximum) prior to lling the
systems.
12. Check bolts and connections for tightness after the  rst heat up cycle.
Retorquing may be required.
Stack and Flue
An appropriately sized stack should be connected to the ue gas outlet at the
boiler. The proper ue size and draft control is most important for proper burner
operation. See Table 4.
Stack and chimney must be constructed from material that is rated for 1000 F
© The Fulton Companies 2012
INSTALLATION VMPW-IOM-2012-1001 SECTION 2
2-14
operating temperature. Check all local codes for requirements.
The ue must be as large or larger than the outlet on the vessel. Avoid ue
piping and elbows by placing the equipment as close as possible to the chimney.
TABLE 4  MINIMUM FLUE SIZES
Model Minimum Flue Size
inches (mm)
40 12 (305)
50 12 (305)
60 12 (305)
80 14 (356)
100 14 (356)
130 14 (356)
150 16 (406)
Adhere to the following for stack and ue installation (see Figure 2):
1. Ensure the stack rises continuously to the connection at the chimney and
contains no more than two bends at 45 degree angles or less. If required,
as a result of space limitations, one 90 degree elbow (or tee) can be tted
at the back of the vessel.
2. Ensure 2 feet (0.6 m) of straight, horizontal ue before any change in
direction,  tting or draft regulator. This is to prevent potential pilot or
main  ame failures due to back pressure build up during ignition. Any
alternative stack arrangement must supply negative 0.02 to 0.04”wc.
3. Ensure the run in the total distance of stack ducting, as measured in a
straight line from the outlet of the boiler to the outlet of the stack, does
not exceed 25% of the rise. With the exception of the duct run previously
described, horizontal sections of ducting must be avoided and should not
exceed 4 feet (1.2 m) total. See Figure 2.
4. Ensure the stack, chimney, and any components associated with the stack,
such as heat reclaimers or assist fans, are constructed from material that is
rated for a 1000 F (538 C) operating temperature.
5. Ensure the stack and chimney material complies with all applicable codes.
6. Make adequate provisions for the support of the weight of the chimney
and stack to avoid having a load imparted to the outlet connection of the
equipment.
7. Ensure the draft, when ring, is negative and constant. A reading of -0.02
to -0.04”wc (-0.508 to -1.016 mm) when the unit and stack are cold usually
indicates su cient draft. When the unit is running and the stack is hot, the
draft should read -0.04 to -0.08 “wc (-1.016 to -1.524 mm) negative.
8. The installation of a draft regulator by the client/contractor is
recommended at all installations. This will help to maintain the required
draft. The placement of the draft regulator should be as shown in Figure 3.
Insulate the section of the chimney duct within the building.
! WARNING
All information in this manual is for
reference and guidance purposes,
and does not substitute for required
professional training, conduct,
and strict adherence to applicable
jurisdictional/professional codes and
regulations.
Non-Fulton product information is for
reference purposes only. No Fulton
document may substitute for full
review of documentation available
from the component manufacturer.
4 CAUTION
Boilers damaged due to adverse water
conditions are not covered by warranty.
The weight of all piping must be
properly supported. Failure to support
piping may result in equipment
damage and/or system leakage.
Piping must take into consideration
potential for freezing interference and/
or damage as a result of expansion,
contraction, vibration, or other
movements.
Dirt, water, and/or other debris in the
piping system after welding may result
in equipment failure.
To maintain a reasonable
temperature in the equipment area
and ensure safety to personnel, the
section of the chimney duct within
the building should be insulated.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52

Fulton VMP-W Operating instructions

Type
Operating instructions
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI