Fulton Boiler Works.*Electric Thermal Fluid Heaters Manual* Version 06 2011
Page 20
d) Typical Fulton Thermal Piping Schematic
e) Alignment
1. Proper alignment directly affects bearing, coupling, and seal life
expectancy. The pump is properly aligned before it leaves the factory.
Because the system expands in operation, the pump must be realigned
when the system is at operating temperature.
2. The coupling alignment of the pump and driver must be carefully
checked for angular and axial alignment. Check the pump
manufacturer’s instructions for these specifications. The use of a dial
indicator to check the axial and angular alignment is recommended.
20
23
1. Thermal Fluid Heater
2. Thermal Fluid Circulating Pump
3. Safety Relief Valve
4. Thermometer
5. Pressure Gauge
6. Thermal Fluid Heated Equipment
7. Bypass Valve to maintain full flow to heater
8. Expansion Joints as required
9. Anchor and Pipe Guides as required
10. Expansion Tank
11. Vent Piping should be full size of expansion tank vent
12. Deaerator Tank
13. Deaerator Tank inlet must be highest point of piping
14. Thermal Buffer Tank
15. Catch Tank for drain of pressure relief valve, cold seal,
expansion tank, and vent. Locate in safe area.
16. Gate Valve
17. Strainer
18. DN20 System Fill Connection
19. Flexible Connection as necessary
20. Isolating Valve as necessary
21. Manual Low Level Test Line
22. Manual High Level Test Line
23. Buffer Drain
Full pump design flow must be maintained at all
times through the main piping loop. Low flow will
seriously damage the heater.
Note: Manifold configuration for illustration only.
See drawing appropriate to particular model.