Fulton FT-C User manual

Type
User manual

Below you will find brief information for FT-C FT-0080-C, FT-C FT-0120-C, FT-C FT-0160-C, FT-C FT-0240-C, FT-C FT-0320-C, FT-C FT-0400-C, FT-C FT-0600-C, FT-C FT-0800-C, FT-C FT-1000-C, FT-C FT-1400-C. The Fulton FT-C Thermal Fluid Heaters are vertical, helical coil, self-venting designs with operating temperatures up to 345 °C. They feature a 4-pass combustion design, pre-heater jacket for thermal efficiency, and are constructed of carbon steel. The heaters are designed to be safe and efficient for various industrial applications, with detailed installation, operation, and maintenance guidelines provided.

Below you will find brief information for FT-C FT-0080-C, FT-C FT-0120-C, FT-C FT-0160-C, FT-C FT-0240-C, FT-C FT-0320-C, FT-C FT-0400-C, FT-C FT-0600-C, FT-C FT-0800-C, FT-C FT-1000-C, FT-C FT-1400-C. The Fulton FT-C Thermal Fluid Heaters are vertical, helical coil, self-venting designs with operating temperatures up to 345 °C. They feature a 4-pass combustion design, pre-heater jacket for thermal efficiency, and are constructed of carbon steel. The heaters are designed to be safe and efficient for various industrial applications, with detailed installation, operation, and maintenance guidelines provided.

This manual must be available to the operator at all times. FTC-IOMM-2015-2
INSTALLATION, OPERATION AND MAINTENANCE MANUAL
FT-C
Fuel Fired Thermal Fluid Heater
FTC-IOMM-2015-2
Fulton Ltd
Page II
TABLE OF CONTENTS
SECTION 1 - INTRODUCTION
1.1 General 1
1.2 Technical Data 1
SECTION 2 - INSTALLATION
2.1 General 3
2.2 Transport 3
2.3 Siting 4
2.4 Gas Supply 5
2.5 Oil Supply 7
2.6 Minimum Clearance For Coil Removal 8
2.7 System Connections 8
2.7.1 Drain/Fill Connection 8
2.7.2 Heater Connections 8
2.7.3 Electrical Connections 9
2.7.3.1 Voltage and Frequency 9
2.8 Pipework Systems 9
2.9 Combination Expansion/Deaerator/Thermal Buffer Tank 10
2.9.1 Expansion Section 10
2.9.2 Deaerator Section 10
2.9.3 Thermal Buffer Section 10
2.9.4 Sizing the Tank for the System 11
2.9.5 Location 11
2.9.6 Pressurised Systems 12
2.9.7 Connections 13
2.10 Oil and Gas Circulating Pump 14
2.10.1 Location 14
2.10.2 Connections and Piping 14
2.10.3 Alignment 15
2.10.4 Lubrication 15
2.10.5 Seals 15
2.10.6 Air Cooling 15
2.10.7 Water Cooling 16
2.11 Catch Tank 16
2.12 Gauges 17
2.13 Valves 17
2.14 Piping 18
2.15 Gasket Installation Instructions 20
2.16 Testing 21
2.17 Insulation 21
2.18 Thermal Fluids 22
2.18.1 Thermal Fluids at Elevated Temperatures 22
2.18.2 Selecting a Thermal Fluid 22
2.18.3 Routine Analysis of Heat Transfer Fluid 24
2.18.4 Thermal Fluid Breakdown 24
2.19 Multi-Skid System 25
SECTION 3 - OPERATION
3.1 General 27
3.2 Start-Up Preparation and Installation Review 27
3.3 Filling the System 28
3.3.1 Filling Procedure 29
3.4 For Systems Equipped With Inert Blanket 30
3.5 Circulating Pump 30
3.5.1 Mechanical/Air Cooled Seal 31
3.6 Initial Start-up 32
3.6.1 Start-up Service 32
3.6.2 Cold Circulation 32
3.6.3 Filtering the System 33
3.6.4 System Boil-out 34
3.6.5 Procedure for First Shutdown 35
3.6.6 Sequence of Operation 36
3.6.7 Dual Fuel Burner - Changing Fuel 39
3.6.8 Gas Fired Modulating Burner 40
3.6.9 Setting Main Burner Ignition 41
3.6.10 Setting Main Run Ignition 42
3.6.11 Setting Low Fire 42
3.6.12 Setting the Complete Range 43
3.6.13 Changing Set Point on the AZL 44
3.6.14 For Manual Operation 44
3.7 Required Pressure Drop Across The Heater 44
3.8 Required Flow Through the Heater 44
3.9 Operating Control 45
3.9.1 Liquid Level Switch-When Combination Tank is Supplied 46
3.9.2 Air Safety Switch 46
3.9.3 Blower Motor Starter 47
3.9.4 Differential Pressure Switch 47
3.9.5 Pump Motor Starter 47
3.9.6 High and Low Fluid Pressure Switches 48
3.9.7 Gas Pressure Switch 48
3.9.8 Operating Temperature Control 49
3.9.9 High Limit Temperature Control 50
3.9.10 Pressure Gauges 50
3.9.11 Operating Limit Controller 50
3.9.12 On/Off Controls 51
3.9.13 Flow Proving Device 51
3.9.14 Test of Ignition Safety System Shut-off 51
3.9.15 Cycle Testing 51
3.10 Daily Start-up 52
3.11 Daily Shutdown 52
FTC-IOMM-2015-2
Fulton Ltd
Page III
TABLE OF CONTENTS
SECTION 4 - MAINTENANCE
4.1 Required Maintenance at First Shutdown 53
4.2 Maintenance Procedures 53
4.2.1 Lubrication 53
4.2.2 Soot Cleaning 54
4.3 Schedule of Operator Test and Checks 54
4.3.1 Daily 54
4.3.2 Weekly-in addition 55
4.3.3 Monthly-in addition 55
4.3.4 Six Monthly-in addition 56
4.3.5 Annually-in addition 56
4.4 Safety Check Procedures 56
4.4.1 Temperature Limit(s) 56
4.4.2 Air Switch 57
4.4.2.1 Air Filter Box Switch 57
4.4.3 Liquid Level Switch 57
4.4.4 Differential Pressure Switch 57
4.4.5 Low Inlet Pressure Switch 57
4.4.6 High Outlet Pressure Switch 57
4.4.7 High/Low Gas Pressure Switch 58
4.5 Troubleshooting: 59
4.5.1 Troubleshooting-Flow Circuit/Circulating Pump(s) 59
4.5.2 Troubleshooting-Tripped High Outlet Pressure Switch 62
4.5.3 Troubleshooting-Differential Pressure Switch Break 63
4.5.4 Troubleshooting-Call for Heat 64
4.5.5 Troubleshooting-Safety Interlock 65
4.13 Maintenance Log 66
APPENDIX A - TI SHEETS
FTC-IOMM-2015-2
Fulton Ltd
Page IV
WARNINGS
Prior to shipment, the following tests are made to assure
the customer the highest standards of manufacturing:
a) Material inspections
b) Manufacturing process inspections
c) ASME welding inspection
d) ASME hydrostatic test inspection
e) Electrical components inspection
f) Operating test
g) Final engineering inspection
h) Crating inspection
Rigging your heater into position should be handled
by a competent rigger experienced in handling heavy
equipment.
The customer should examine the heater for any
damage, especially the refractories.
It is the responsibility of the installer to ensure
all parts supplied with the heater are tted in a
correct and safe manner.
WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance.
Do not touch any electrical switch; do not use any
phone in your building.
Immediately call your gas supplier from a
neighbour's phone. Follow the gas supplier’s
instructions.
If you cannot reach your gas supplier, call the re
department.
For your safety!
The following WARNINGS, CAUTIONS and NOTES appear in various sections of this manual.
WARNINGS must be observed to prevent serious
injury or death to personnel.
CAUTIONS must be observed to prevent damage
or destruction of equipment or loss of operating
effectiveness.
Notes: must be observed for essential and
effective operating procedures, conditions and as
a statement to be highlighted.
It is the responsibility and duty of all personnel involved
in the operation and maintenance of this equipment
to fully understand the WARNINGS, CAUTIONS and
NOTES by which hazards are to be eliminated or
reduced.
Personnel must become familiar with all aspects
of safety and equipment prior to operation or
maintenance of the equipment.
CAUTION
In case of emergency
This heater has been designed and constructed to meet all of the essential requirements of the applicable
European Directives and subject to proper maintenance should not give occasion to any hazardous conditions.
If such a condition should occur during commissioning or during subsequent operation of this product,
whatever the cause, then the fuel supply to the boiler should be isolated immediately, until the fault has been
investigated by a competent person and rectied.
!
WARNING
Thermal Fluid Heaters are a potential hazard, possibly fatal if not properly maintained.
CAUTION
It is vitally important that the instructions given in this manual are strictly adhered to. Failure to carry
out the routine maintenance checks could result in a drastic reduction in the life expectancy of the
system and increase the possibility of re, explosion, property damage, personal injury or loss of life.
!
!
FTC-IOMM-2015-2
Fulton Ltd
Page V
WARNINGS
SAFETY
The instructions provided for the operation and maintenance
of the heater MUST be observed. Failure to do so could
result in damage to the heater and serious personal injury.
WARNING
Do not try to do repairs or any other maintenance work
you do not understand. Obtain a service manual from
Fulton Ltd or call a Fulton service engineer.
It is the responsibility of the installer to ensure all parts
supplied with the boiler are tted in a correct and safe
manner.
Understand the electrical circuit before connecting
or disconnecting an electrical component. A wrong
connection can cause injury and or damage.
A defective heater can injure you or others. Do not
operate
a heater which is defective or has missing parts. Make
sure that all maintenance procedures are completed
before using the heater.
LIFTING EQUIPMENT
Make sure that lifting equipment complies with all local
regulations and is suitable for the job. You can be injured
if you use faulty lifting equipment. Make sure the lifting
equipment is in good condition.
Operating the heater beyond its design limits can
damage the heater, it can also be dangerous.
Do not operate the boiler outside its limits.
Do not try to upgrade the heater performance by
unapproved modications.
Non-approved modications can cause injury and
damage. Contact your Fulton dealer before modifying
the boiler.
Only qualied persons should be allowed to operate and
maintain the heater and its equipment.
DANGER FROM HOT SURFACES
Thermal Fluid Heaters have high temperature surfaces,
that if touched may cause serious burns. Only competent
and qualied personnel should work on or in the locality
of a thermal uid heater and ancillary equipment. Always
ensure the working area and oor are clear of potential
hazards, work slowly and methodically.
Do not store or use gasoline or other ammable vapours
and liquids in the vicinity of this or any other appliances.
Note: Max. room temperature not to exceed 38 °C.
Note: In no case should any part of the drive side of the
pump be insulated.
Note: Max. operating temperature for air cooled pumps
varies by manufacturer. Consult instruction manual to
verify.
Note: If the tank is located outdoors nitrogen is required.
High temperature thermal uid, steam and combustible
vapours may be vented through the DA vent connection.
!
CAUTION
Obey all laws and local regulations which affect you and
your heater.
During operation, any leaks are usually detected by a
small amount of vapour. Leaks should be attended to as
soon as possible because under certain circumstances,
such as saturated insulation, thermal uid can ignite
when exposed to air and heat.
Note: Fulton Ltd cannot be held responsible in the
case of accident or damage resulting from the use of
inadequate uid.
Note: Unless specially ltered, compressed air will
introduce moisture into the system. Dry air or Nitrogen is
recommended.
Note: Some plastics can be dissolved by thermal uid.
Note: Do not use system circulating pump for system
lling. A pump that has been used for water or for
a different thermal uid should not be used prior to
extensive cleaning. Thermal uid can be damaged by
contact with moisture or other uids.
Use extreme caution opening plug when system
temperature is elevated.
Wear eye and hand protection.
Back the plug out slowly to the last two or three threads.
Allow any pressure under the plug to bleed slowly to
prevent a spray of hot oil.
Note: Flash steam may be generated at any point up to
the operating temperature. Watch for gauge uctuations.
Note: All of the above maintenance procedures should
be completed by trained personnel. Appropriate training
and instructions are available from the Fulton Service
Department.
!
WARNING
Once the system has been lled, any modication to the
tank or connected piping requires purging of the work
area to prevent ignition of potentially ammable vapours.
Consult factory prior to beginning work. Consult the
MSDS (material data safety sheet) for your thermal uid
for ammability limits.
Note: Unless the system is pressurised, the inlet to
the deaerator section of the combination tank must be
higher than or equal to the highest point in the system
to prevent pockets of air from collecting in the system
piping.
Pressurising a drum to force uid into the system is not
recommended. The drum can easily explode, creating a
hazard to personnel and equipment.
Note: Tanks are non-code as a standard. Non-code
tanks cannot be pressurised over 0.5 barg. Tanks built to
BS EN13445:2009 are available upon request.
Note: Do not run the pump before lling it with uid.
!
FTC-IOMM-2015-2
Fulton Ltd
Page VI
Figure. 1 - General Arrangement: Skid Mounted FT-C Thermal Fluids System
FT-C vertical
thermal uid
heater
Electrical panel
box containing all
operating safety
controls
FT-L combination
expansion/
dearaetor/thermal
buffer tank
Thermal uid
circulating pump
FTC-IOMM-2015-2
Fulton Ltd
Page 1
INTRODUCTION - 1
SECTION 1 - INTRODUCTION
1.1 GENERAL
The Fulton FT-C is a vertical thermal uid heater with a range of 11 models. The Fulton FT-C
Thermal Fluid Heater offers a compact fuel red 4-pass heater design capable of operating
temperatures up to 345 °C.
The heater is of a vertical, helical coil self venting design, and the pressure vessel coil
construction is carbon steel ASME SA106B, Schedule 40 or equal. The design pressure is 13.8
barg standard at 370 °C. The heater will be per ASME Code Section I stamped at 10.34 barg
maximum working pressure, trimmed at 6.9 barg unless otherwise specied. Test pressure will
be per ASME Code Section I. Minimal refractory lining will be supplied in the heater combustion
chamber to avoid thermal inertia and overheating of the thermal uid should a pump or power
failure occur.
The shell, coil and burner are encased in a pre-heater jacket. This jacket is a welded steel
construction with an integral oor plate and bolted top cover to facilitate coil removal, access
panels for air chamber inspection and has an aluminium inner air bafe. This pre-heater removes
the need for insulation of the heater and simultaneously boosts thermal efciency by preheating
incoming combustion air.
1.2 TECHNICAL DATA
For a full specication refer to Appendix A - TI-123-FT-C Dimensions & Specication.
FTC-IOMM-2015-2
Fulton Ltd
Page 2
Figure. 2 - FT-C Component View
Note: Thermal uid heater is of four-pass combustion design.
First pass (radiant): combustion air enters burner fan and travels upward between inner and outer jacket
before it enters top-mounted burner.
Second pass (convection): Gases travel back across the inner row of coils.
Third pass (convection): Gases continue back down between inner and outer coil.
Fourth pass: Upward between the outer coil and inner jacket to the ue outlet.
A - Fluid Outlet
B - Top Mounted Burner
C - Fluid Inlet
D - Control Panel
E - Fan Inlet
FTC-IOMM-2015-2
Fulton Ltd
Page 3
INSTALLATION - 2
2.1 GENERAL
The installation of a FT-C thermal uid heater should be carried out by competent personnel in
accordance with all relevant safety regulations. It is the responsibility of the installer to ensure that
these regulations are complied with.
a) All components exposed to thermal uid ow including pipe, valves, and screens must not
be made out of copper, copper alloys, aluminium, or cast iron. Cast iron is porous to thermal
uids, and copper and aluminium act as catalysts in the degradation of some thermal uids.
Carbon or stainless steel, or ductile iron are recommended.
b) For standard applications, all components must be rated to 350 °C unless otherwise specied.
c) All pipework, valves and user equipment must be suited to the maximum operating pressure
of the heater. The maximum pressure stamped on the heater nameplate is typically 10.34 barg
(150 psig).
d) If an isolating valve is completely closed, the pressure in the system will rise to the deadhead
pressure of the pump. Suitably sized pipe will enable the system to withstand the total head
generated by the circulating pump, should this occur. In applications where it is desirable
to design to pressures lower than 6.9 barg (100 psig), an alternative safeguard is to install
appropriately sized safety valves.
e) Where secondary circulating pumps are installed, the system must be suitable for the
aggregate head, against a closed valve, of both pumps.
f) During construction of the installation, ensure that no dirt, water, or residue from welding is left
in the system.
2.2 TRANSPORT
All Fulton Coil Design Heaters are shipped vertically and all units are crated for forklift transport.
Once unpacked, all units with the exception of free-standing Models FT-0080-C, FT-0120-C,
FT-0160-C, and FT-0240-C can be transported with a forklift.
These four models can only be lifted for unloading and moving by means of lifting lugs at the
top of the heaters. If means of lifting are not available then rollers should be placed beneath the
frame of the heater and it should be guided to the position of where it is to be installed. Under no
circumstances should weight be allowed to bear on the jacket, control panel or fan housing of any
Fulton Thermal Fluid Heater.
All stand alone heaters can be moved via a crane utilizing lifting lugs on top of the heater. The
FT-0320-C and larger stand alone heaters can also be moved using a fork lift. All skidded units
can be moved with forklifts.
SECTION 2 - INSTALLATION
FTC-IOMM-2015-2
Fulton Ltd
Page 4
INSTALLATION - 2
2.3 SITING
Reference should be made to Appendix A - TI-123-FT-C Dimensions & Specication to
ascertain the relevant dimensions and weights.
a) Authorities with jurisdiction over any national or local codes which might be applicable to
thermal uid applications should be consulted before installations are made.
b) The heater should be located as close as possible to the place where the heat will be used in
order to keep pipework costs to a minimum.
c) A level, hard, non-combustible surface is required as a suitable base for mounting the unit. It is
suggested that a 100 mm curb be installed completely around the unit. In the event of a large
spill, this will help contain the uid.
d) Approximations for the oor loading of each heater can be calculated using the weights given
in Appendix A - TI-123-FT-C Dimensions & Specication. Check building specications for
permissible oor loading.
e) The heater should be placed in a suitable heater house or well ventilated separate room
through which personnel do not normally pass. This is not essential, but the layout should
eliminate trafc in potentially hazardous areas. For instance, the service engineer or the
operator should not have to pass exposed and hot pipework to make adjustments to the
heater controls.
f) Ventilation must be sufcient to maintain a building temperature of 38 °C or less and the panel
box temperature must not exceed 52 °C. Natural ventilation should be provided by means of
grilles at oor and ceiling level.
g) To burn fuel properly, the burner must have an adequate supply of air.
See Technical Information sheet for the heater for minimum make up air required and the
recommended area of opening for each heater.
If positive forced ventilation is adopted, you must ensure that there will be no appreciable
pressure variation in the heater room.
FTC-IOMM-2015-2
Fulton Ltd
Page 5
INSTALLATION - 2
Adhere to the following for gas supply installation:
1. Install gas piping in accordance with all applicable codes.
2. Ensure pipe and ttings used are new and free of dirt or other deposits.
3. Ensure piping is of the proper size for adequate gas supply to the gas head assembly. Consult
your gas company for specic recommendations.
4. When making gas piping joints, use a sealing compound resistant to the action of liqueed
petroleum gases. Do not use Teon tape on gas line heads.
5. Ensure no piping stresses are transmitted to the equipment. The equipment shall not be used
as a pipe anchor.
6. Ensure all vent connections on diaphragms, gas valves, pressure regulators, and pressure
switches (gas-red units) are vented per local code.
7. During any pressure testing of the system at pressures in excess of 34 mbar (0.5psi),
disconnect the heater at the heater manual shut-off valve (located at the end of the supplied
gas train) from the gas supply piping system.
8. Ensure the supply pressure is regulated by a non-stacking, tight, shut-off regulator.
9. Arrange gas piping so that it does not interfere with any cover or burner, inhibit service or
maintenance, or prevent access between unit and walls or another unit. The burner assembly
and gas controls terminate at a manual stop valve to which the gas supply should be
connected. Piping must be sized for a gas ow consistent with the required kW input. Large
pressure drops must be avoided. Fulton recommends that the supply piping between the
pressure regulator and the inlet to the heater be kept to a minimum. The minimum required
gas pressure at the stop valve varies with the model of heater. The requirements for natural
gas-red coil design models are as follows:
Models FT-0080-C to FT-0400-C 34 mbar (0.5 psi)
Models FT-0600-C to FT-0800-C 149 mbar (2.2psi)
Models FT-1000-C to FT-1400-C 299 mbar (4.3psi)
Note: Low emissions burners for all models require 345 mbar (5psi).
Note: Even when the unit is shut down, the gas supply pressure must never exceed these values.
Note: When operating, the supply pressure must not drop below these limits: Not less than 27 mbar where 34
mbar is required. Not less than 125 mbar where 149 mbar is required. Not less than 249 mbar where 299 mbar is
required.
10. After gas piping is completed and before wiring installation is started, carefully check all piping
connections (factory and eld) for gas leaks. Use a soap and water solution.
2.4 GAS SUPPLY
FTC-IOMM-2015-2
Fulton Ltd
Page 6
INSTALLATION - 2
Main gas valve
assembly
Main gas line
isolating valve
Pilot line
ball valve Pilot line
governor Pilot line
gas valves
Gas valve
Gas
governor
Gas
actuator
Figure. 3 - Gas Valve (non modulating burner)
Figure. 4 - Gas Valve (fully modulating burner)
FTC-IOMM-2015-2
Fulton Ltd
Page 7
INSTALLATION - 2
2.5 OIL SUPPLY
Burner is suitable for Class D fuel oil. If required to run on kerosene contact Fulton for
replacement components and commissioning
Adhere to the following for installation:
1. Fuel pipes must be of approved materials and of a diameter suitable for the quantity of oil
being delivered to the burner and the static head available.
Make fuel connection in accordance with the details on the enclosed fuel pump cut sheet.
2. Ensure fuel oil piping is in accordance with local/national requirements.
In addition, if a two pipe system is employed, a check valve must be tted into the return pipe.
Figure. 5 - Typical No.2 Oil Fired Fuel Train
FTC-IOMM-2015-2
Fulton Ltd
Page 8
INSTALLATION - 2
2.6 MINIMUM CLEARANCE FOR COIL REMOVAL
a) All heaters will also require a minimum clearance overhead for coil removal. In cases where
the available height is insufcient, a roof or ceiling trap might be considered.
b) Pipes should not be run within 250 mm of any control cabinets or combustible material.
c) Failure to provide suitable and safe access at the time of commissioning may cause delays, as
our service engineers are instructed not to commence commissioning if hazardous conditions
exist.
For more information see Appendix A - TI-123-FT-C Dimensions & Specication.
2.7 SYSTEM CONNECTIONS
If screwed connections have to be made, e.g. to items of control equipment, then a thread sealant
suitable for use with uids at elevated temperature must be used. Teon tape, standard pipe dope
or hemp and paste are not acceptable. Screw threads must be carefully and accurately cut. If
possible new tools should be used. Threaded connections larger than DN25 are not to be used. It
is recommended that class 8.8 or better tensile steel bolts be used for all anged joints.
2.7.1 DRAIN/FILL CONNECTION
The system is usually lled from the
lowest point, with the aid of a pump.
On skid mounted systems a drain and
ll connection is provided in the inlet
piping to the pump.
Note: The system pump is not to be used to ll the
system.
2.7.2 HEATER CONNECTIONS
a) The outlet of the pump should connect directly to the inlet of the heater via an isolating valve
and pump exible connector.
b) The heater outlet should be piped directly to the system, via an isolating valve.
c) A safety relief valve may be shipped in the parts box accompanying the electric heater, and
must be installed in the outlet manifold. On all units, the outlet of the safety relief valve must
be piped to a catch tank. The discharge ow must not be restricted, i.e. no valve should
be installed, there should be no reduction in pipe size, and the minimum number of bends
possible. The weight of the piping must be properly supported in order to prevent damage to
the safety valve. If the valve body becomes warped, leakage may result.
Figure. 6 - Drain and Fill Connection
FTC-IOMM-2015-2
Fulton Ltd
Page 9
INSTALLATION - 2
a) A wall mounted fused disconnect sized for the unit must be provided and tted by the
client/contractor if a disconnect is not supplied on the panel.
b) Fuses must be sized according to motor name plates and local electrical codes.
c) Heaters and single skid systems are shipped completely pre-wired. The liquid level switch on
the expansion tank, when supplied, will be shipped in the parts box and must be installed on
site. Multiple skid systems may require wiring between the skids.
d) If the unit is not skid-mounted at the factory, the client/contractor is required to wire the
circulating pump starter.
e) When using a SCR, a Shunt Trip Breaker is required to be installed by the customer. It will be
used to remove power to the panel in the event of an over temperature/pressure condition.
The Shunt Trip Coil needs to be wired to the boiler electrical panel as indicated on the
electrical drawing.
Note: If the circulating pump motor is not supplied by Fulton Ltd, the motor starter will not be supplied.
2.7.3 ELECTRICAL CONNECTIONS
Normal supply will be 400 volts, 3
phase, 50 Hz, AC unless otherwise
specied.
Make sure the information on the
electrical drawing corresponds to the
voltage and frequency specic to the
heater. Check the supply voltage and
make sure that there is no over or
under voltage exceeding 10% of the
nominal value.
2.7.3.1 VOLTAGE AND FREQUENCY
2.8 PIPEWORK SYSTEMS
Certain properties of thermal uid including low surface tension, make it necessary to pay
particular attention to contain the uid. Good pipework system design, welded construction,
proper anging, gaskets, and other appropriate means of eliminating potential leakage must be
employed.
Figure. 7 - Thermal Fluid Heater Nameplate
FTC-IOMM-2015-2
Fulton Ltd
Page 10
INSTALLATION - 2
2.9 COMBINATION EXPANSION/DEAERATOR/THERMAL BUFFER TANK
Figure. 8 - Combination Expansion/Deaerator/Thermal Buffer Tank
Please see Appendix A - FT-L Dimensions & Specication.
Fulton Ltd's efcient design combines the operation of the expansion, deaerator and thermal
buffer tanks. Installation is simplied by virtue of this arrangement.
The tank will be constructed of carbon steel. It is supplied with expansion section liquid level
switch and PN16 anged connections.
The tank may be built to BS EN 13445: 2009 upon request. Non-coded tanks should not be
pressurised above 0.5 barg.
The expansion section is vital to the thermal uid system. From ambient to operating temperature,
the thermal uid in the system will typically expand in the range of 25%-50%, and a vessel
capable of handling this expansion is mandatory. The customer should conrm the expansion rate
of the chosen uid and system volume.
At start up the primary purpose of the deaerator section is to remove all volatiles from the system
to avoid pump cavitation. The deaerator section also allows oxygen to be vented from the system
on a continuous basis during operation to avoid oxidation of the thermal uid, and removes other
volatile particles generated by the uid itself during system operation. This section of the tank
should be insulated.
2.9.1 EXPANSION SECTION
2.9.2 DEAERATOR SECTION
Expansion
Volume
Vent for piping
to Safe Catchment
Expansion
Tank
Hot Fluid
Medium Fluid
Cool Fluid
Gases (Steam)
Thermal
Buffer Section
Drain
Fluid Out
Liquid
Level
Switch
Fluid In
Dearator
Section
Section
FTC-IOMM-2015-2
Fulton Ltd
Page 11
INSTALLATION - 2
Combination tank capacity is the total volume of the tank. It is necessary to have some air space
available at the top of the tank to avoid spillage or overow. At initial ll (for system volume
calculations) the deaerator and thermal buffer sections must be lled completely and the
expansion section must be lled to a level of 100 mm to “make” the liquid level switch.
The volume between the initial ll level and the safe “full” level is the amount available for
expansion. That volume is used to decide which tank is suitable for the system expansion.
Sizing Example
A system contains 660 litres (including the heater, but not the tank). You select the FT-200-L, so
you add 95 litres to 660. You must look up the expansion rate for the thermal uid (assume it is
25%). 755 litres x 1.25 = 945 litres. 945-755 = 190 litres expansion. The FT-200-L has only 75
litres available for expansion, so the correct selection is the FT-500-L.
2.9.5 LOCATION
a) The combination tank must be installed in accordance with Fulton Ltd’s specications.
b) Unless the system is pressurised, the inlet to the deaerator section must be higher than or
equal to the highest point in the system to prevent pockets of air from collecting in system
piping.
c) The head required at the circulation pump suction inlet must also be taken into account
to avoid the possibility of pump cavitation. In systems operating close to maximum uid
temperature, the tank must be elevated if possible above the highest point in the system to
prevent pump cavitation by increasing the static head. An inert pressurising blanket may be
considered as an alternative. See Section 2.9.6 - Pressurised Systems.
d) Supports for tank mounting should be provided by the client/contractor. These should be
suited for supporting the tank by the side rails. The eyelets tted to the tank are for lifting only.
A system of interconnecting pipework in the thermal buffer tank section prevents the movement
of any oil that has not cooled sufciently into the expansion section. This avoids contact of very
high thermal uid temperature with oxygen contained in the atmosphere, which causes uid
breakdown. DO NOT insulate this section.
2.9.3 THERMAL BUFFER SECTION
2.9.4 SIZING THE TANK FOR THE SYSTEM
FTC-IOMM-2015-2
Fulton Ltd
Page 12
INSTALLATION - 2
Figure. 9 - Liquid Level Switch
Nitrogen pressurisation may be used to advantage where the total system content is very large or
in a system operating near or above the vapour pressure of the uid employed or if the inlet of the
DA tank is not the highest point in the piping system.
In conjunction with this system, an automatic venting device must be tted to the system
expansion tank. Consult Fulton Ltd for further details.
The location for the liquid level switch is a connection on the same end of the tank as the inlet.
The liquid level switch is supplied and shipped with the unit and must be installed by the customer
and then wired to the control panel.
Note: If the tank is located outdoors nitrogen pressurisation is required.
Liquid Level
Switch
2.9.6 PRESSURISED SYSTEMS
FTC-IOMM-2015-2
Fulton Ltd
Page 13
INSTALLATION - 2
2.9.7 CONNECTIONS
a) The vent connection must be made in a manner that will prevent penetration of water or
foreign bodies into the tank. This connection must always terminate in a safe, well ventilated
area and has to be free of obstruction, open to atmosphere and arranged in such a manner
that in the event of discharge from the system, thermal uid could drain into a catch tank
without danger to personnel or property.
Note: Non-code tanks cannot be pressurised over 0.5 barg.
WARNING
High temperature thermal uid, steam and combustible vapours may be vented through this connection.
!
b) The vent run should be the same size as the tank outlet. It should run pitch down from the
outlet of the tank to the catch tank.
c) If nitrogen is used on the system, the vent can be reduced to DN50 and should be piped with a
positive closing valve at the catch tank.
d) The connection between the tank outlet and the horizontal pump inlet run should be as close
to a vertical drop as possible. It should not contain an excessive number of bends of length of
pipe. These faults could encourage pump cavitation.
e) As noted, the inlet to the combination tank must be higher than or equal to the highest point in
the system or a pressurised system must be used.
f) The liquid level switch supplied and shipped with the unit must be installed and wired to the
control panel by the customer.
g) The high and low level test connections are DN15. The low level is situated lower than the
high level. The high level rises up from the bottom of the tank and ends 100 mm below the top;
the low level rises 50 mm from the bottom of the tank.
h) Both the high and low level connections should be piped to a safe catchment. Valves should
be installed in these lines at the catch tank.
Installation of the valves should be accomplished in such a manner that any ow will be visible
when the valves are open.
Flow from the high level test connection indicates when a tank is too full; no ow from the low
level test connection indicates too little uid in the tank.
i) There is a drain on the bottom of the thermal buffer section for the purpose of draining the tank
when necessary. This should be piped with a valve in the line to a safe catchment. The valve
specications outlined above apply to this valve as well.
j) An inspection opening is located at the highest point on the tank. Access to this port is
recommended but not required.
k) Refer to the maintenance schedule for recommendations on draining the thermal buffer
section. For positioning of all connections on the tank, see Figure. 8.
WARNING
Once the system has been lled, any modication to the tank or connected piping requires purging of the work
area to prevent ignition of potentially ammable vapours. Consult factory prior to beginning work. Consult the
MSDS for your thermal uid for ammability limits.
!
FTC-IOMM-2015-2
Fulton Ltd
Page 14
INSTALLATION - 2
2.10 OIL AND GAS CIRCULATING PUMP
Installing the pump in accordance
with the manufacturer’s specications
and these instructions will prolong
the life of the pump and contribute
signicantly to the successful operation
of your Fulton heater system. The
pump manufacturer’s installation and
operation instructions will be provided
with the pump (with skid-mounted
systems it will be provided within the
same folder as all OEM literature).
Figure. 10 - Oil and Gas Circulating Pump
2.10.1 LOCATION
The pump should be located adjacent to the heater. Its base must be rm, level (preferably
concrete) and free from vibration.
2.10.2 CONNECTIONS AND PIPING
a) The pump should be routed as per the manufacturer’s requirements. It should be equipped
with exible connections at the suction and discharge sides. The primary function of these
connections is to prevent stresses due to pipe expansion from being placed on the pump and
to isolate pump vibrations from the pipework and the heater. They also allow for expansion
and deection of the pipework. These connections should be rated for high temperature since
they are considered part of the piping system.
b) The suction pipework must be directly connected to the deaerator section of the combination
tank via a vertical run with as few elbows as possible and should contain the strainer and an
isolating valve. The discharge pipework must be connected directly to the heater inlet and
should contain an isolating valve. See that pipework connections match up accurately with
pump anges. Refer to the pump manufacturer’s recommendations for the specic pump inlet
piping requirements.
Typically these requirements are that:
i. It be a straight run of pipe.
ii. The straight run from the pump inlet to the rst tting, valve or ex connector be a minimum
of 6-10 pipe diameters in length.
iii. The pipe used should be the same size as the inlet of the pump.
c) The piping in the immediate vicinity of the pump must not be supported by the pump. The
pump is not designed to bear the weight of the piping and weight on any part of the pump will
throw it out of alignment.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80

Fulton FT-C User manual

Type
User manual

Below you will find brief information for FT-C FT-0080-C, FT-C FT-0120-C, FT-C FT-0160-C, FT-C FT-0240-C, FT-C FT-0320-C, FT-C FT-0400-C, FT-C FT-0600-C, FT-C FT-0800-C, FT-C FT-1000-C, FT-C FT-1400-C. The Fulton FT-C Thermal Fluid Heaters are vertical, helical coil, self-venting designs with operating temperatures up to 345 °C. They feature a 4-pass combustion design, pre-heater jacket for thermal efficiency, and are constructed of carbon steel. The heaters are designed to be safe and efficient for various industrial applications, with detailed installation, operation, and maintenance guidelines provided.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI