LQEK Electric air heater - Installation instruction
4
FläktGroup DC_9147GB 20180329_R0
Specifications are subject to alteration without notice
NEMKO
SEMKO, BS
GT 1 GT 2
C
1
120 90
C
PE
2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
1,5 1,5 3 6 12
18 19 20
32
GT 1 GT 2
C
21
120 90
C
PE
3 4 5 76 8 9 10 11 12 13 14 15 16 17 18 19
20 21 22
WIRING DIAGRAM
(DIAGRAMMATIC ARRANGEMENT)
The air heater is wired according to the examples above. Thermo-
stats GT1 and GT2 are wired to terminal block 1 through 4 or 1 through
6, and the elements on terminal blocks number 5 or 7 and upward.
The lowest output stages are always energized first and subsequent
stages are energized as the need for increased output arises. Star or
delta-wiring and limitations of the elements are specified below. Par-
ticulars of the division of outputs across the elements are tabulated on
pages 2 and 3.
REMOTE ALARM INDICATION
The automatic control equipment of the heater can be provided with
remote alarm indication from overheating thermostat GT1. When the
unit is in operation, auxiliary relay HR1 is energized. When thermostat
GT1 opens the circuit, auxiliary relay HR1 will be de-energized and an
alarm will be initiated.
OPERATION
1. The system can be started either manually by means of switch S1
or automatically by means of time switch GX1. The fan will be start-
ed and the air heater will be switched in sequentially by the step-
ping switch.
2. If the temperature in the heater should exceed the value preset
on limiting thermostat GT2, the air heater will be tripped. It will be
switched back on again automatically when the temperature has
dropped to below the thermostat setting. If a fault on the equipment
should cause the temperature to rise beyond the value at which
overheating thermostat GT1 trips, the fan and air heater will both be
tripped. GT1 must then be reset manually after the fault has been
cleared.
3. To prevent cold air from being supplied to the premises in the event
of a fault on the air heater or its control equipment, a thermostat
should be installed on the supply air side to stop the unit after a de-
lay of about 10 minutes after starting of the system if the tempera-
ture should drop below the preset value (about +10 °C).
Element group
Element group max. kW Ext. fuse
A
Wire crosssection1)
mm2
Terminal blocks
mm2 (min)
c = 1
230 V supply
c = 2
400 V-415 V supply
Max. 1,99 kW Max. 3,5 kW 10 1.5 (1,5) 4
Max. 3,9 kW Max. 6,9 kW 10 1.5 (1,5) 4
Max. 6,3 kW Max. 11,0 kW 16 2.5 (1,5) 4
Max. 8,0 kW Max. 13,8 kW 20 4.0 (2,5) 6
Max. 10 kW Max. 17,3 kW 25 6.0 (4) 16
Max. 14 kW Max. 24,2 kW 35 10 (6) 16
Max. 20 kW Max. 34,6 kW 50 16 (10) 35
Max. 32 kW Max. 55,3 kW 80 25 (16) 35
Max. 40 kW –100 35 (25) 50
1) Choose wiring having sufficient cross-section so that it will not be overloaded by the output of the element groups.
If necessary, wiring having the cross-section specified between brackets may be used inside the air heater.
The correction factor 0.86 has been used for selecting the fuse.