FläktGroup Smoke Master SMHA Hatch Installation guide

Type
Installation guide
INSTALLATION, OPERATION AND MAINTENANCE
Smoke Master
SMHA HATCH
Smoke Master SMHA HATCH - Installation, operation and maintenance
2
FläktGroup DC_10507GB 20210129_R0 All rights reserved.
CONTENTS
Important information ............................................................................. 2
Safety notes ............................................................................................... 2
Technical description ............................................................................. 3
Fan and motor range ...............................................................................4
Dimensions and weights ........................................................................ 5
Transport ...................................................................................................... 6
Installation ...................................................................................................7
Commissioning .......................................................................................... 9
Maintenance .............................................................................................. 10
Faults .......................................................................................................... 12
Spare parts ................................................................................................ 12
Product code ............................................................................................. 12
Declaration of conformity .................................................................... 13
IMPORTANT INFORMATION
FläktGroup HT-fans comply with the requirements for EN 12101-3
standard and health and safety of the EC Machinery Directive.
All fans leave the factory after being subjected to testing.
These instructions are intended for use by professional service staff.
The installation, commissioning and operation of the fans must be
carried out by professional staff, who are familiar with the safety
regulations.
Tools and protective equipment necessary for preventing accidents
from occurring while installing and operating the fan must be used/
worn in accordance with the local safety regulations.
All personnel involved with the product must carefully study
this operating manual and diligently comply with all orders and
instructions.
FläktGroup does not accept responsibility for any damage that can be
attributed to nonobservance of these instructions.
The warranty issued by the manufacturer will be forfeited if any
changes to the product are made without the manufacturer’s consent.
SAFETY NOTES
This symbol is designed to point out all safety and danger related
information regarding danger on the operating personnels lives and
health.
Smoke Master SMHA HATCH - Installation, operation and maintenance
3
FläktGroup DC_10507GB 20210129_R0 All rights reserved.
TECHNICAL DESCRIPTION
Between the hatch and casing is sealing material. Both hatch
and casing have isolation material between metal sheets.
Specification
The equipment is an axial fan with casing designed for use as an
exhaust fan in high temperature emergency conditions. The product
is not allowed to be used in normal ventilation. The fan is driven by an
enclosure electric motor classified to F400(120) in accordance with
EN1201-3. The hatch and fan are integrated to be one certified unit.
Hatch is opened by 2 electrical motors, which are dimensioned to
cover both snow and wind load. The fan itself should be started 30
seconds after the hatch motors have been started.
The door is also equipped with a mechanical cable opening mecha-
nism. The mechanism is intended for situations where it is desired to
open the door without electricity.
1. Opening hatch
2. JMHT fan and fire rated motor
3. Safety mesh
4. Mechanical cable opening mechanism
5. Linear motor
6. Limit switch
7. Safety switches
3
2
1
4
5
6
7
Product SMHA, galvanised steel, insulated casing
Fan type JMHT axial fan
Smoke extraction class 400°C 2h
Approval body EUROFINS EXPERT SERVICES OY
Certificate 0809-CPR-19001010
CE marking EN12101-3 ; 2015
Motors Fan motor F400 (120) rated
3x400VAC, 50 Hz class H / F
Linear motors 2 pcs 1x230 VAC, 50 Hz
Installation method Free / duct
Exhaust UPWARDS/DOWNWARD
Installation Outside on the roof or car park deck
Smoke Master SMHA HATCH - Installation, operation and maintenance
4
FläktGroup DC_10507GB 20210129_R0 All rights reserved.
FAN AND MOTOR RANGE
The product can also be dimensioned with the Fan Selector, taking into account different installation cases in the same way.
Product code Fan Rotation speed
(rpm)
Power
(kW)
Power con-
sumption (A)
Starting
current (A)
Voltage
(V)
Frequency
(Hz)
SMHA-040-009 JMHT40/16/2/5 2735 0,9 2,0 9,8 400 50
SMHA-040-017 JMHT40/16/2/5 2730 1,7 3,6 18,3 400 50
SMHA-050-017 JMHT50/20/2/3 2730 1,7 3,6 18,3 400 50
SMHA-050-048 JMHT50/20/2/6 2835 4,8 9,3 50,1 400 50
SMHA-080-036 JMHT80/20/4/6 1400 3,6 7,3 40,1 400 50
SMHA-080-048 JMH T80/25/4/6 1410 4,8 9,7 49,4 400 50
SMHA-080-066 JMHT80/25/4/6 1450 6,6 12,5 76,3 400 50
SMHA-080-090 JMHT80/25/4/9 1440 9,0 1 7, 1 100,9 400 50
SMHA-100-066 JMHT100/31/4/6 1450 6,6 12,5 76,3 400 50
SMHA-100-110 JMHT100/31/4/6 1445 11,0 19,9 133,3 400 50
SMHA-100-180 JMHT100/31/4/9 1455 18,0 34,2 1 7 7,9 400 50
SMHA-125-180 JMHT125/50/4/6 1455 18,0 34,2 1 7 7,9 400 50
SMHA-125-270 JMHT125/50/4/6 1455 27,0 50,6 275 400 50
Smoke Master SMHA HATCH - Installation, operation and maintenance
5
FläktGroup DC_10507GB 20210129_R0 All rights reserved.
DIMENSIONS AND WEIGHTS
Size A
(mm)
B
(mm)
C
(mm)
D
(mm)
E
(mm)
F
(mm)
G
(mm)
H
(mm)
I
(mm)
J
(mm)
K
(mm)
L
(mm)
M
(mm)
Weight
* (kg)
040 1065 1165 1010 400 800 900 980 1080 1245 1135 1935 900 375 180
050 1065 1165 1010 500 800 900 980 1080 1245 1135 1935 900 375 200
080 1265 1365 1010 800 1000 1100 1180 1280 1445 1335 2135 900 375 330
100 1465 1565 1010 1000 1200 1300 1380 1480 1645 1535 2335 900 375 520
125 1715 1815 1210 1250 1450 1550 1630 1730 1895 1785 2785 1100 575 936
* maximum weight at the highest motor rating
E (internal)
G
20
A B 90°
J
K
M
L
D
I
C
F (internal)
H
Diameter
of fan
Smoke Master SMHA HATCH - Installation, operation and maintenance
6
FläktGroup DC_10507GB 20210129_R0 All rights reserved.
TRANSPORT INSPECTION
Check the fan immediately after you receive it and make sure that it
has not been damaged during transport. If you discover any damage,
get in touch with the transportation company without delay.
Check the information on the fan rating plate.
Proper procedures must be followed when transporting the
product.
Faulty conditions in transporting may result in serious damage on
the product.
TRANSPORT SAFETY
The transport material is to be selected according to the
packaging and the weight of the product.
Loading must be carried out as instructed.
INTERMEDIATE STORAGE
If the fan is to be stored before or in between uses, the following
needs to be taken in account:
Original packaging is to be used.
If the storage conditions require it, additional protection may be
added.
The hatch of the product must be closed during the storage.
During long time storage indoor premises must be used.
TRANSPORT
Smoke Master SMHA HATCH - Installation, operation and maintenance
7
FläktGroup DC_10507GB 20210129_R0 All rights reserved.
INSTALLATION
Like smoke hatches, JMHT HATCH can be installed on a roof or a car
park deck in one lift. The product can be mounted directly onto con-
crete or a similar surface, or onto a specially designed base – what is
important is that there is even support across the entire surface. The
fan is fully weather-protected throughout the construction project.
The possibility of condensation must be prevented in smoke extrac-
tion in damp areas by proper installation.
The recommended size for the penetration in the slab is
D + 200mm, and for ease of connection to ducting, the penetration
should preferably be square in shape.
JMHT Hatch allows two alternative connection methods. If the product
is to be duct-mounted, it is delivered with a matching flange at the
bottom. If the fan is meant to draw in air freely from the space below,
the product is delivered with a safety mesh at the bottom. In the latter
case, all that needs to be done to install the unit is to fix it to the roof
structure and connect it to the mains.
The maximum roof slope must be 12°.
Fixing angle irons to the base with at least four 5x40 screws or
with at least four screws to the roof structure:
- to concrete 4-6 psc HILTI HPS-1 6/5x30
- to timber 4-6 pcs wood screws 5x50
- to reinforced concrete 4-6 pcs self-drilling screws 5,5x25
Fig. 1 Fig. 2
1. Opening hatch
2. JMHT fan casing
3. Impeller
4. Motor
5. Protective mesh/flange
6. Hatch motors 2 pcs
7. Protective mesh on exhaust
8. Roof structure
9. Installation into roof structure with
angle irons (g. 1) or directly on the
base with flanges (fig. 2)
16
7
5
9
3
4
2
8
Smoke Master SMHA HATCH - Installation, operation and maintenance
8
FläktGroup DC_10507GB 20210129_R0 All rights reserved.
SAFETY REGULATIONS
In case, when the hatch is open and maintenance
work for fan is done, there is a risk of fall through
the fan opening, especially in case, when the fan is
removed from its place. The care shall be taken to prevent fall during
the maintenance work.
ELECTRICAL CONNECTIONS
All electrical connections must be wired by authorised personnel only.
The necessary electrical and safety precautions must be taken into
account. The fan is equipped with 2 safety switches, one for the fan
motor and one for the opening motors. Electrical connections shall be
done as shown in picture. The hatch is equipped with switches show-
ing, if the hatch is closed or open.
Motor cable shall be fire proofed (40C / 2 h) and bushing through the
casing shall be sealed (400°C / 2 h).
The fan motor cable must be a fire resistant
cable. The cable glands in the casing must be
sealed with fire-resistive mass.
It is recommended to use the limit switch only
for the closing information of the hatch. The
starting signal of the motor must come from a
separate control. The starting method for the
fan is direct-on-line starting 30s after the start
of the linear motors.
NOTE! Linear motors must not be exposed to
the control voltage!
MOUNTING INSTRUCTIONS
Limit switch
Installed on site
Factory installation
Linear motor Linear motor
Smoke extract
fan motor
Safety switchSafety switch
Max 3 min run time
Black (L-OPEN)
Blue (N)
Yellow (DATA A)
Green (DATA B)
Brown (L-CLOSED)
Smoke Master SMHA HATCH - Installation, operation and maintenance
9
FläktGroup DC_10507GB 20210129_R0 All rights reserved.
PREPARATION
Open the hatch and connect the motor rods to fastenings. Connect the
mains to motors to close the hatch.
HUOM! Varmista luukun avaamisen mahdollistaminen myös ns.
tilapäisen virtalähteen käytön jälkeen (esim. irroita karamoottoreiden
akselit testikäytön jälkeen).
NOTE! Make sure that it is also possible to open the hatch after using a
temporary power supply (eg disconnect linear motor shafts after test
run).
SAFETY CHECKING
Rotate the shaft and check that the impeller can move freely. Make
sure that there are no foreign objects in the fan or in the ducting. Also
check that there is no unusual noise in the fan. Check that the installa-
tion work has been carried out in accordance with the relevant regula-
tions. All necessary protective devices must be installed.
Check also, that there is big enough air flow to compensate fan
air flow. Check, that all other regulations related to fire safety are
followed.
The fan may only be commissioned after all proper procedures have
been followed and all necessary inspections have been carried out.
TEST RUN
Briey switch on the power supply to the motor to check whether the
fan impeller rotates in the correct direction. If the impeller is rotating in
the correct direction shown with the arrow, the fan may be switched
on. Check that no abnormal mechanical sound and no surging occurs.
COMMISSIONING
Smoke Master SMHA HATCH - Installation, operation and maintenance
10
FläktGroup DC_10507GB 20210129_R0 All rights reserved.
WARRANTY
A precondition of the warranty is that regular maintenance has been
carried out. Defects under warranty must immediately be notified to
the manufacturer or the importer. The warranty does not cover service
work or indirect damages.
MAINTENANCE
BEFORE MAINTENANCE
Switch off the power supply to the fan and hatch motors at the safety
isolating switches. The hatch is staying open, when the safety switch
is turned off from mains. However, make sure, that hatch cannot be
falling down during the maintenance.
INSPECTION INTERVALS
Inspection intervals can be defined by local authorities. If nothing
else is mentioned, the fan shall be tested according to the intervals in
table, but at least once a year. The annual inspection must be done by
authorized persons only. Also follow the separate JMHT fan mainte-
nance instructions.
Pos. Description Commisioning 6 months 12 months
Fan
1. Control, that hatch can be opened freely. x x x
2. Control, that fan motor will start 30 s after hatch opening motors. x x x
3. Control the correct rotation direction of fan. x x x
4. All installed warning lights are OK. x x
5. All labels are available and can be seen. x x
6. Fan motor and hatch opening motors are visually OK. x x
7. Test run of the fan. x  x
8. Whole product is visually checked against failures. x x x
Make the control protocol. x
Make or fill the maintenance protocol. x x
Motor
1. Check bearing noise during test run. x
2. Lubricate bearing if needed. x
3. Check proper rotation of impeller. x
4. Visual control. xx
MAINTENANCE
CHECKING THE MOTOR BEARINGS
The motors are meant to be operated in emergency conditions only.
The motor bearings have to be lubricated in accordance with the
instructions that accompany the motor, latest at 3 years intervals.
Replacements of bearings are to be done in accordance with the
motor manufacturers instructions.
IMPELLER
The impeller shall be clean.
Smoke Master SMHA HATCH - Installation, operation and maintenance
11
FläktGroup DC_10507GB 20210129_R0 All rights reserved.
MAINTENANCE
REPLACING THE MOTOR AND THE IMPELLER
The fan will have to be disconnected from the unit before the motor
can be replaced.
SMHA-040,050,080,100-066,100-106
1. Check that the fan motor and hatch-motors are disconnected
from mains.
2. Remove outlet guard.
3. Remove impeller from motor shaft by opening locking screw
from shaft end.
4. Remove impeller from the shaft, take care, that the key is not
dropping down.
5. Motor rotor can be lifted up and bearings can be checked.
SMHA-sizes 100-180 and all size 125 versions
1. Remove complete fan and lift it outside the casing for
maintenance.
2. Follow instructions of JMHT for maintenance.
FINAL INSPECTION
Check that:
The impeller is mounted for the correct direction of rotation.
All screws and nuts have been tightened.
No foreign objects have been left in the fan or in the ducting.
The mechanical opening of the hatch works.
The mechanical opening of the hatch is intended for situations where
the door has to be opened without electrical current for one reason or
another.
The door can be opened mechanically by pulling the wires under the
hatch. There are two wires and they are located on both sides of the
linear motors. Pulling on the wire requires some force, so you have to
use an aid, such as an iron pipe (see picture).
After the mechanical opening, reattach the linear motor shafts to the
mounting lugs and make sure that the cover seals are intact.
Smoke Master SMHA HATCH - Installation, operation and maintenance
12
FläktGroup DC_10507GB 20210129_R0 All rights reserved.
FA U LT S
If any faults occur during inspection which cannot be repaired by
maintenance personnel, please contact the service department at
FläktGroup.
Examples of faults can include the following issues:
foreign particles inside fan
corrosive media inside
too high vibrations
not correct maintenance
hatch not opening
Possible problems generated:
bearing damage
corrosion damage
vibration generated damage
SPARE PARTS
Use only genuine spare parts supplied/accepted by FläktGroup. If
other spare parts are used, no warranty or EN-certification is valid.
Spare parts:
fan motor
hatch motor
PRODUCT CODE
Smoke extract fan SMHA - aaa - bbb - cc - dd
Size = aaa
040, 050, 080, 100, 125
Fan motor rating = bbb
048 = 4.8 kW
etc.
Inlet = cc
10 = safety mesh on the inlet (no duct on the inlet side)
20 = matching flange on the inlet (ducted installation)
Pitch angle = dd
The required pitch angle is obtained by dimensioning.
FAULTS, SPARE PARTS AND PRODUCT CODE
Smoke Master SMHA HATCH - Installation, operation and maintenance
13
FläktGroup DC_10507GB 20210129_R0 All rights reserved.
DECLARATION OF PERFORMANCE
No. 017CPR2019-04-09
1. Unique identification code of the product-type:
Powered smoke and heat exhaust ventilator SMHA with accessories
2. Type, batch or serial number or any other element allowing identification of the construction product as required
under Article 11(4):
Powered smoke and heat exhaust ventilator SMHA-aaa-bbb-cc-dd with accessories
3. Intended use or uses of the construction product, in accordance with the applicable harmonised technical
specification, as foreseen by the manufacturer:
Powered smoke and heat exhaust ventilator
4. Name, registered trade name or registered trade mark and contact address of the manufacturer as required
pursuant Article 11(5):
FläktGroup Finland Oy, Kalevantie 39, 20520 Turku, Finland
Tel. +358204423000, Email: info.fi@flaktgroup.com
5. System or systems of assessment and verification of constancy of performance of the construction product as set
out in Annex V:
System 1
6. Eurofins Expert Services Oy, Finland, Nr. 0809
Performed determination the product type on the basis of type testing; initial inspection of the manufacturing
plant and of factory production control; continuous surveillance, assessment and evaluation of the factory
production control (FPC) under system 1 and issued: Certificate of constancy of performance 0809-CPR-
19001010.
7. Declared performance:
8. The performance of the product identified in points 1 and 2 is in conformity with the declared performance in point
7. This declaration of performance is issued under the sole responsibility of the manufacturer identified in point 4.
Signed for and on behalf of FläktGroup by:
Jari Hokkanen, R&D Manager Turku 9.4.2019
…………………………………………...........
Essentialcharacteristics Harmonized
technical
specification
Responsedelay:
‐openingunderwindloadwithinagiventime
‐openingundersnowloadwithinagiventime
Operationalreliability:
‐Applicationcategories
Motorrating
Effectivenessofsmoke/hotgasextraction
Gasflowandpressuremaintenanceduring
smokeandheatextractiontest
Resistancetofire:
Abilitytoopenunderenvironmentalconditions:
‐Openingunderwindloadwithinagiventime
‐Openingundersnowloadwithinagiventime
Durabilityofoperationalreliability NPD
EN12101‐3:2015
≤30s
SL500
F
400
(120)
Performance
≤30s
SL500
Smokeextraction
NPD
10%≤Flow≤+25%
FG_DC_10507GB_SMHA HATCH_IN-MA_20210129_R0 © Copyright 2021 FläktGroup
SMHA HATCH 10507
WWW.FLAKTGROUP.COM
» Learn more on www.flaktgroup.com
or contact one of our offices
FläktGroup is the European market leader for smart and energy efficient Indoor Air
and Critical Air solutions to support every application area. We offer our customers
innovative technologies, high quality and outstanding performance supported by more
than a century of accumulated industry experience. The widest product range in
the market, and strong market presence in 65 countries worldwide, guarantee
that we are always by your side, ready to deliver Excellence in Solutions.
PRODUCT FUNCTIONS BY FLÄKTGROUP
Air Treatment | Air Movement | Air Diffusion | Air Distribution | Air Filtration
Air Management & ATD’s | Air Conditioning & Heating | Controls | Service
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14