FläktGroup LQRA Rotary heat exchanger Installation guide

Type
Installation guide
FläktGroup DC_9207GB 20180412_R0 Specifications are subject to alteration without notice
LQRA ROTARY HEAT EXCHANGER,
CONSTANT SPEED
MAINTENANCE
ELECTRICAL INSTALLATION – CONSTANT SPEED
MOTOR SPECIFICATION
Size Rating
W
Voltage 1)
V
Rated current
A
60–84 750 230 VD
400 VY
3,3
1,9
1)
The motor is always wired at the factory for a 380 V star power supply
N.B.
To test the motor alone, lift the belt off the pulley. Always check the
direction of rotation, which is shown on the casing.
DELIVERY
The delivery includes a heat exchanger with a drive motor.
IMPORTANT!
Regarding the control logic and operation: During start
up and after each time the AHU has been stopped, it is
recommended that the exhaust fan operates during
1 minute before the supply fan is started.
CIRCUIT DIAGRAM (GENERALIZED)
-Q1
L1
L2 1
3
5
2
4
6
L3
N
PE
-F1
-K1
135
246
-K1:1
UVW
M
3-
M
-SB
135
UVW PE
13
24614
95 97
96 98
400/230 V
50 Hz
12
34
56
13 14
-K1
A1 A2
135
246
-F2
-GX1
a
b
-GTD
-GT1
-GX1
-GX1
b
a
12
-K:FF-SB
13 14 13 14
0
Aut
GX
Man
-S1
-K1:1
95 96
21 22
31 32
43 44
230 V
N
K1:k
-H1
12
-K1
43 44
L1
L2
L3
N
PE
SYMBOLS USED
F1 Fuses
F2 Control circuit fuse
GT1 Thermostat
GTΔ Differential thermostat
GX1 Timeswitch, a = 7-day dial with contacts
(intermittent operation), b = 24-hour dial
with contacts (purging)
H1 Indicating lamp
K:FF Interlocks, e.g. exhaust air fan
K1 Heat exchanger contactor
K1:1 Overcurrent protection
K1:K Interlock contacts in K1. Used in systems with speed detector
M Drive motor
Q1 Main switch in equipment cubicle
S1 Selector switch
SB Safety isolating switch