FläktGroup DC_9503GB 20230621_R4 Specifications are subject to alteration without notice.
Fire Damper ETCE and ETCS - Instructions for Installation, Operation and Maintenance
7
Installation into rigid building elements
(walls and inter mediate floors) with fire
classification EI 90 / EI 120 (Fig. 5 and Fig. 8)
1. Installation opening in the rigid wall or intermediate floor
must comply with the dimensions given in the table be-
low.
Installation into flexible building elements
(gypsum board walls or similar) with fire
classification EI 90 / EI 120 (Fig. 6 and Fig. 7)
1. Installation opening in the flexible wall must comply with
the dimensions given in the table below. Make an open-
ing to the wall with beams.
2.
The fire damper blade must be closed during installation.
NOTE! The blade supports may not be removed before
completed grouting.
3. Place the fire damper centrally in the opening. Fire
damper positioning:
a.
The fire damper must be placed so that the blade is cen-
trally inside the opening in the intermediate floor or wall.
b. The marking (1) on the actuator side shall align with
the building element surface.
c. The damper axle can be placed in any position (Ø100
- Ø400) or in horizontal position when mounted in the
wall (Ø500 - Ø1000).
d. Ensure that fire damper casing remains in horizontal
position during installation.
4. Support the damper properly in the opening. Fasten the
damper with the angle brackets (2), 1-4 pcs depending
on damper size. Use Ø5 mm screws suitable for rigid
construction to lock the position.
5. Completely fill the gap M between the damper and the
building element using incombustible, rock based, fine-
grained gypsum or concrete cast. Protect the damper
whilst infilling.
6. Remove the blade supports (4) when finished grouting
(Ø500 - Ø1000).
2.
The fire damper blade must be closed during installation.
NOTE! The blade supports may not be removed before
completed grouting.
3. Place the fire damper centrally in the opening. Fire
damper positioning:
a. The fire damper must be placed so that the blade is
centrally inside the opening in the wall.
b. The marking (1) on the actuator side shall align with
the building element surface.
c. The damper axle can be placed in any position (Ø100
- Ø400) or in horizontal position when mounted in the
wall (Ø500 - Ø1000).
d. Ensure that fire damper casing remains in horizontal
position during installation.
4. Support the damper properly in the opening. Fasten the
damper with the angle brackets (2), 1-4 pcs depending
on damper size. Use Ø5 mm screws or anchors suitable
for flexible construction to lock the position. Attach one
additional gypsum board (5) to work as grouting support.
5. Completely fill the gap M between the damper and the
building element using incombustible, rock based, fine-
grained gypsum or concrete cast. Protect the damper
whilst infilling. Attach the other additional gypsum board
(5). Fill the gap S between the fire damper and the gyp-
sum board on both sides by using fire-resistant mass,
e.g. Silacoll 100. (Figure 7).
6. Remove the blade supports (4) when finished grouting
(Ø500 - Ø1000).
Size ØD (mm) Installation opening Ø (mm)
100
125
150
160
200
250
300
315
400
500
630
800
1000
185 – 205
185 – 205
210 – 230
220 – 240
260 – 280
310 – 330
360 – 380
375 – 395
460 – 480
560 – 580
690 – 710
860 – 880
1060 – 1080
Size ØD
(mm)
Installation opening
Ø (mm)
Gypsym plate dim. (mm)
min. thickness 12,5 mm
100
125
150
160
200
250
300
315
400
500
630
800
225 x 225
225 x 225
250 x 250
260 x 260
300 x 300
350 x 350
400 x 400
415 x 415
500 x 500
600 x 600
730 x 730
900 x 900
405 x 405
405 x 405
430 x 430
440 x 440
480 x 480
530 x 530
580 x 580
595 x 595
680 x 680
780 x 780
910 x 910
1080 x 1080
7. Check the functioning of the fire damper and proper
movement of the blade. Clean the damper, if necessary.
Place plastic covers on the openings and keep them
covered, until ducts are connected to the damper.
8. To reset the fuse mechanism: Turn the handle towards
the OPEN position until the mechanism clicks and the
blade locks into position.
9. Manual function testing of the motorized fire damper can
be performed with the tool delivered with the
actuator. When connected to a power supply, function
testing is done by using the switch of the thermal trip
(3). NOTE! If you open the damper blade manually with
the tool, be sure to release the damper back to the
closed position before switching on power.
10. Connect ducts to the damper according to the instruc-
tions provided by the designer and the manufacturer.
Access panel should be placed next to the fire damper
to enable necessary cleaning and inspection. Suspend
the ducts according to instructions from the manufac-
turer and ensure that the ductwork does not cause any
load on the damper installation.
11. If the fire damper is used as an air transfer or air termi-
nal device, it must be equipped with a protective grille.
The distance between the grille and the damper blade
in the open position must be at least 30 mm. In case of
large fire dampers, an extension piece must be installed
between the grille and the damper blade. A circular duct
of suitable length can be used as an extension piece.
12. When dampers are to be mounted next to one another,
the distance between the dampers should be ≥200mm
(Figure 8).