FläktGroup ETCE/ETCS Installation guide

Type
Installation guide
INSTALLATION, OPERATION AND MAINTENANCE
FIRE DAMPERS
ETCE and ETCS
FläktGroup DC_9503GB 20230621_R4 Specifications are subject to alteration without notice.
Fire Damper ETCE and ETCS - Instructions for Installation, Operation and Maintenance
2
Installation
Fire dampers ETCE and ETCS (with stainless steel casing)
must be installed according to this installation manual, see
pages 4-9.
General instructions for using hangers
The fire damper must be supported so that the ductwork
connected to the damper does not impose any load on the
damper body.
In practice, a good way to fit the product centrally in the
installation opening is to hang the ductwork prior to sealing.
If the subsequent sealing is done using grouting concrete,
also other types of support can be used during installation
until the concrete has dried.
It is essential that no stress is imposed on the fire damper
or the duct. The hanging and fixing solution must be ade-
quate in the event of fire. The hanger must be located either
at the fire damper or immediately after the duct connection.
Designing the use of hangers is the responsibility of a
structural engineer.
Operation and function testing
According to CE marking, a fire damper must always be
equipped with a tripping mechanism based on
temperature. Fire dampers can be delivered equipped with
either a fuse mechanism or an actuator.
ETCE motorized fire dampers may additionally be linked to
a smoke detection based tripping mechanism. A tripping
system based on smoke detection is easy to install using
FläktGroup’s FICO control and monitoring system. The FICO
system can also be used for automatic function tests of fire
dampers.
The function testing for the motorized damper can be per-
formed by cutting off the power supply by using the switch
of the thermal trip connected to the motor. The spring
should then close the damper. The function testing can also
be done by means of the control and monitoring system
FICO, either manually or automatically. The recommended
automatic function testing interval for the motorized model
is 48 hours.
The operation of the fuse mechanism is tested by
pushing the red test button – the spring should close the
blade. Beware of the reset handle as it will rotate rapidly
during test operation. To reset the mechanism, turn the
handle until the mechanism clicks.
The function testing interval is always determined
separately for each building, but testing must be carried
out at least twice a year according to product standard EN
15650:2010.
Maintenance
According to product standard EN 15650:2010, fire damp-
er installations and function are to be checked every six
months (see example of check list beside).
WARNING! Never put your hands inside the damper while
it is closing.
Clean the fire damper by means of a vacuum cleaner. Avoid
chemical cleaning agents.
Fire damper identifier
Date of inspection
Check actuator wiring for damage (where applicable)
Check limit-switch wiring for damage (where applicable)
Check damper cleanliness and clean where necessary
Check the condition of blades and seals, rectify and report where
necessary
Confirm the safety closure operation of the fire damper according
to the manufacturer’s instructions
Confirm operation of damper to OPEN and CLOSE by use of the
control system and physical observation of the damper, rectify and
report where necessary
Confirm operation of OPEN and CLOSED limit-switches, rectify and
report where necessary
Confirm that the damper is working as a part of the
monitoring system (where applicable)
Confirm that the damper is left in its normal working position
NOTE! A fire damper is usually part of a larger system. As this is
the case, the whole system should be checked to comply with the
operation and maintenance requirements for the system.
Maintenance Check List:
Spare parts
Actuator: see type specification on the actuator.
Fuse part ETFF-99-1
Fuse part replacement, see page 11.
011CPR2022-09-30
018CPR2022-05-31
FläktGroup DC_9503GB 20230621_R4 Specifications are subject to alteration without notice.
Fire Damper ETCE and ETCS - Instructions for Installation, Operation and Maintenance
3
Electrical wiring for motorized fire damper
Only a trained electrician is allowed to perform the elec-
trical wiring according to separate drawings and wiring
diagrams. Wiring diagram for fire damper actuator is
shown below.
Tf Tf LE D
S1 S2 S3 S4 S5 S6
<5° <80°
21
+
T
~
Status data of limit switches
Thermal trip
Power supply
AC 230 V
AC 24 V
DC 24 V
Microswitch (fuse mechanism operated
fire damper)
The microswitch does not affect fire damper triggering, it
just indicates the position of the fire damper blade. The fire
damper closes when the thermal trip activates.
Status data from the microswitch can be provided from
either an opening or a closing switch.
Proper functioning of the microswitch must be checked and
proper indication verified.
Electric specification:
Operating temperature -25 °C ... +70 °C
I
max
= 0,1 A
U
max
= 30 V (AC/DC)
1 Test button
2 Cover
3 Cable clamp
4 Microswitches
(under cover)
5 Handle
Wiring diagram for microswitch
Wiring digram shows the situation where damper blade is
in closed position and microswitch (0°) is activated.
2
5
4
3
1
1 2
90°
3 4 5 6
FläktGroup DC_9503GB 20230621_R4 Specifications are subject to alteration without notice.
Fire Damper ETCE and ETCS - Instructions for Installation, Operation and Maintenance
4
Installation into building elements with fire classification EI 60 (Ø100 - Ø1000)
M
S
1
2
1
t
t
ØD
ØD
3
3
4
4
*)
*)
2
Figure 1.
*) Ø500 - Ø1000
Remove the blade supports when installation is
finalized.
Figure 2.
Figure 4.Figure 3.
≥ 116 mm
S
~ 100 mm
S
2
M
S
1
2
1
t
t
ØD
ØD
3
3
4
4
*)
*)
2
t (mm)
EI 60 S 116
t (mm)
100-400 500-1000
EI 60 S 120 140
t (mm)
EI 60 S 100
min. 200 mm
≥ 200 mm
t
M
1
3
4*)
2
FläktGroup DC_9503GB 20230621_R4 Specifications are subject to alteration without notice.
Fire Damper ETCE and ETCS - Instructions for Installation, Operation and Maintenance
5
Size ØD (mm) Installation opening Ø (mm)
100
125
150
160
200
250
300
315
400
500
630
800
1000
175 – 195
175 – 195
200 – 220
210 – 230
250 – 270
300 – 320
350 – 370
365 – 385
450 – 470
550 – 570
680 – 700
850 – 870
1050 – 1070
Size ØD (mm) Installation opening Ø (mm)
100
125
150
160
200
250
300
315
400
500
630
800
1000
135 – 137
135 – 137
160 – 162
170 – 172
210 – 212
260 – 262
310 – 312
325 – 327
410 – 412
510 – 512
640 – 642
810 – 812
1010 – 1012
Installation into rigid building elements
(walls and intermediate floors) with fire
classification EI 60 (Fig. 1 and Fig. 4)
1.
Installation opening in the rigid wall or intermediate floor
must comply with the dimensions given in the table below.
Installation into flexible building elements
(gypsum board walls or similar) with fire
classification EI 60 (Fig. 2 and Fig. 3)
1. Installation opening in the flexible wall must comply with
the dimensions given in the table below.
2. The fire damper blade must be closed during installation.
NOTE! The blade supports may not be removed
before completed grouting.
3. Place the fire damper centrally in the opening. Fire
damper positioning:
a.
The fire damper must be placed so that the blade is cen-
trally inside the opening in the intermediate floor or wall.
b. The marking (1) on the actuator side shall align with
the building element surface.
c. The damper axle can be placed in any position (Ø100
- Ø400) or in horizontal position when mounted in the
wall (Ø500 - Ø1000).
4. Support the damper properly in the opening. Fasten the
damper with the angle brackets (2), 1-4 pcs depending
on damper size. Use Ø5 mm screws suitable for rigid
construction to lock the position.
5. Completely fill the gap M between the damper and the
building element using incombustible, rock based, fine-
grained gypsum or concrete cast. Protect the damper
whilst infilling.
6. Remove the blade supports (4) when finished grouting
(Ø500 - Ø1000).
2. The fire damper blade must be closed during installa-
tion. NOTE! The blade supports may not be removed
before completed grouting.
3. Place the fire damper centrally in the opening. Fire
damper positioning:
a. The fire damper must be placed so that the blade is
centrally inside the opening in the wall.
b. The marking (1) on the actuator side shall align with
the building element surface.
c. The damper axle can be placed in any position (Ø100
- Ø400) or in horizontal position when mounted in the
wall (Ø500 - Ø1000).
4. Support the damper properly in the opening. Fasten the
damper with the angle brackets (2), 1-4 pcs depending
on damper size. Use Ø5 mm screws or anchors suitable
for flexible construction to lock the position.
5. Completely fill the gap S between the fire damper and
the wall opening on both sides by using fire-resistant
mass, e.g. Silacoll 100. The depth of the filling must cov-
er the total thickness of the boards (Figure 3).
6. Remove the blade supports (4).
7. Check the functioning of the fire damper and proper move-
ment of the blade. Clean the damper, if necessary. Place
plastic covers on the openings and keep them covered, until
ducts are connected to the damper.
8. To reset the fuse mechanism: Turn the handle towards the
OPEN position until the mechanism clicks and the blade
locks into position.
9. Manual function testing of the motorized fire damper can be
performed with the tool delivered with the
actuator. When connected to a power supply, function testing
is done by using the switch of the thermal trip (3). NOTE! If
you open the damper blade manually with the tool, be sure
to release the damper back to the closed position before
switching on power.
10. Connect ducts to the damper according to the instructions
provided by the designer and the manufacturer. Access
panel should be placed next to the fire damper to enable
necessary cleaning and inspection. Suspend the ducts
according to instructions from the manufacturer and ensure
that the ductwork does not cause any load on the damper
installation.
11. If the fire damper is used as an air transfer or air terminal
device, it must be equipped with a protective grille. The dis-
tance between the grille and the damper blade in the open
position must be at least 30 mm. In case of large fire damp-
ers, an extension piece must be installed between the grille
and the damper blade. A circular duct of suitable length can
be used as an extension piece.
12. When dampers are to be mounted next to one another, the
distance between the dampers should be 200mm (Fig. 4).
FläktGroup DC_9503GB 20230621_R4 Specifications are subject to alteration without notice.
Fire Damper ETCE and ETCS - Instructions for Installation, Operation and Maintenance
6
M
M
S
1
1
t
t
ØD
ØD
4
4
*)
*)
3
5
5
2
2
3
Figure 5. Figure 6.
Figure 8.Figure 7.
min. 200 mm
≥ 200 mm
t
M
2
1
3
4*)
M
M
S
1
1
t
t
ØD
ØD
4
4
*)
*)
3
5
5
2
2
3
t (mm)
EI 90 S 126
EI 120 S 126
t (mm)
EI 90 S 110
EI 120 S 110
t (mm)
100-400 500-1000
EI 90 S 120 140
EI 120 S 120 140
Installation into building elements with fire classification EI 90 / EI 120
(walls Ø100 - Ø800 and intermediate floors Ø100 - Ø1000)
≥ 116 mm
S
~ 100 mm
SS
M2
5
*) Ø500 - Ø1000
Remove the blade supports when installation is
finalized.
FläktGroup DC_9503GB 20230621_R4 Specifications are subject to alteration without notice.
Fire Damper ETCE and ETCS - Instructions for Installation, Operation and Maintenance
7
Installation into rigid building elements
(walls and inter mediate floors) with fire
classication EI 90 / EI 120 (Fig. 5 and Fig. 8)
1. Installation opening in the rigid wall or intermediate floor
must comply with the dimensions given in the table be-
low.
Installation into flexible building elements
(gypsum board walls or similar) with fire
classication EI 90 / EI 120 (Fig. 6 and Fig. 7)
1. Installation opening in the flexible wall must comply with
the dimensions given in the table below. Make an open-
ing to the wall with beams.
2.
The fire damper blade must be closed during installation.
NOTE! The blade supports may not be removed before
completed grouting.
3. Place the fire damper centrally in the opening. Fire
damper positioning:
a.
The fire damper must be placed so that the blade is cen-
trally inside the opening in the intermediate floor or wall.
b. The marking (1) on the actuator side shall align with
the building element surface.
c. The damper axle can be placed in any position (Ø100
- Ø400) or in horizontal position when mounted in the
wall (Ø500 - Ø1000).
d. Ensure that fire damper casing remains in horizontal
position during installation.
4. Support the damper properly in the opening. Fasten the
damper with the angle brackets (2), 1-4 pcs depending
on damper size. Use Ø5 mm screws suitable for rigid
construction to lock the position.
5. Completely fill the gap M between the damper and the
building element using incombustible, rock based, fine-
grained gypsum or concrete cast. Protect the damper
whilst infilling.
6. Remove the blade supports (4) when finished grouting
(Ø500 - Ø1000).
2.
The fire damper blade must be closed during installation.
NOTE! The blade supports may not be removed before
completed grouting.
3. Place the fire damper centrally in the opening. Fire
damper positioning:
a. The fire damper must be placed so that the blade is
centrally inside the opening in the wall.
b. The marking (1) on the actuator side shall align with
the building element surface.
c. The damper axle can be placed in any position (Ø100
- Ø400) or in horizontal position when mounted in the
wall (Ø500 - Ø1000).
d. Ensure that fire damper casing remains in horizontal
position during installation.
4. Support the damper properly in the opening. Fasten the
damper with the angle brackets (2), 1-4 pcs depending
on damper size. Use Ø5 mm screws or anchors suitable
for flexible construction to lock the position. Attach one
additional gypsum board (5) to work as grouting support.
5. Completely fill the gap M between the damper and the
building element using incombustible, rock based, fine-
grained gypsum or concrete cast. Protect the damper
whilst infilling. Attach the other additional gypsum board
(5). Fill the gap S between the fire damper and the gyp-
sum board on both sides by using fire-resistant mass,
e.g. Silacoll 100. (Figure 7).
6. Remove the blade supports (4) when finished grouting
(Ø500 - Ø1000).
Size ØD (mm) Installation opening Ø (mm)
100
125
150
160
200
250
300
315
400
500
630
800
1000
185 – 205
185 – 205
210 – 230
220 – 240
260 – 280
310 – 330
360 – 380
375 – 395
460 – 480
560 – 580
690 – 710
860 – 880
1060 – 1080
Size ØD
(mm)
Installation opening
Ø (mm)
Gypsym plate dim. (mm)
min. thickness 12,5 mm
100
125
150
160
200
250
300
315
400
500
630
800
225 x 225
225 x 225
250 x 250
260 x 260
300 x 300
350 x 350
400 x 400
415 x 415
500 x 500
600 x 600
730 x 730
900 x 900
405 x 405
405 x 405
430 x 430
440 x 440
480 x 480
530 x 530
580 x 580
595 x 595
680 x 680
780 x 780
910 x 910
1080 x 1080
7. Check the functioning of the fire damper and proper
movement of the blade. Clean the damper, if necessary.
Place plastic covers on the openings and keep them
covered, until ducts are connected to the damper.
8. To reset the fuse mechanism: Turn the handle towards
the OPEN position until the mechanism clicks and the
blade locks into position.
9. Manual function testing of the motorized fire damper can
be performed with the tool delivered with the
actuator. When connected to a power supply, function
testing is done by using the switch of the thermal trip
(3). NOTE! If you open the damper blade manually with
the tool, be sure to release the damper back to the
closed position before switching on power.
10. Connect ducts to the damper according to the instruc-
tions provided by the designer and the manufacturer.
Access panel should be placed next to the fire damper
to enable necessary cleaning and inspection. Suspend
the ducts according to instructions from the manufac-
turer and ensure that the ductwork does not cause any
load on the damper installation.
11. If the fire damper is used as an air transfer or air termi-
nal device, it must be equipped with a protective grille.
The distance between the grille and the damper blade
in the open position must be at least 30 mm. In case of
large fire dampers, an extension piece must be installed
between the grille and the damper blade. A circular duct
of suitable length can be used as an extension piece.
12. When dampers are to be mounted next to one another,
the distance between the dampers should be 200mm
(Figure 8).
FläktGroup DC_9503GB 20230621_R4 Specifications are subject to alteration without notice.
Fire Damper ETCE and ETCS - Instructions for Installation, Operation and Maintenance
8
Installation of ETCE fire damper outside building elements with fire classification
EI 60 (Ø100 - Ø800)
Figure 9.
Figure 10.
Figure 11.
M
6
2
3
6
ØD
M
≥100 mm
1
ØD
M
≥100 mm
1
M
1
ØD
4*)
2
3
1
4*)
3
M
1
t
ØD
4*)
2
3
M
2
3
2
21
M
≥100 mm
ØD
1
3
≥116 mm
S
≥116 mm
ØD
1
S
M
S
1
t
ØD
4*)
3
5
52
ØD
1
3
ETCZ-1
ETCZ-1
ETCZ-1
ETCZ-1
FläktGroup DC_9503GB 20230621_R4 Specifications are subject to alteration without notice.
Fire Damper ETCE and ETCS - Instructions for Installation, Operation and Maintenance
9
Installation of ETCE fire damper outside building elements with fire classification
EI 60 (Fig. 9-11)
1. Install the duct in the usual manner so that it pene-
trates the building element, and seal the openings (M or
S) using an approved method.
2. Prepare the fire damper for remote of wall installation:
Place the supplied accessory clamp collar ETCZ-1-
aaa-1 (3) as shown in Figure 11 over the taping on the
fire damper and tighten it in place with the screws on
the clamp collar. NOTE. The custom-built clamp collar is
a mandatory accessory for installation outside building
elements.
3. Connect damper to duct according to the instructions
provided by the designer or manufacturer and remove
the blade supports. Use rivets of sufficient length (e.g.
DIN 7337 4x10 or shorter) to lock fire damper to the
duct. Note! Always check that damper blade can rotate
freely and rivets/screws are out of the way. Access
panel should be installed next to the damper to enable
necessary cleaning and inspection.
4. Support the duct installation so that there is no extra
load on the fire damper. In horizontal installation (Fig-
ures 9-10) the dimensioning of threaded rod hangers
(1) can be done based on the following table. In vertical
installation (Figure 11) use shaft hangers (6) or other
approved methods to stabilize the damper according
to instructions from structural engineer. NOTE! The fire
damper brackets (2) shall not be used for suspending
in the installation outside building elements.
Threaded rod Max load (kg)
t EI 60
M8
M10
M12
33,6
53,2
77,3
5. Insulate the duct between wall and base for motor, as
shown in figures 9-11, so that the fire classification
EI 60 is met.
6. Check the functioning of the fire damper and proper
moving of the blade. Clean the damper, if necessary.
Place plastic covers on the openings and keep them
covered, until ducts are connected to the damper.
7. To reset the fuse mechanism: Turn the handle towards
the OPEN position until the mechanism clicks and the
blade locks into position.
8. Manual function testing of the motorized fire damper
can be performed with the tool delivered with the
actuator. When connected to a power supply, function
testing is done by using the switch of the thermal trip.
NOTE! If you open the damper blade manually with the
tool, be sure to release the damper back to the closed
position before switching on power.
9. The fixings used to secure the fire damper and ventila-
tion duct must have a fire resisting capacity that is at
least as high as the fire classification of the penetrated
building element (the fire resistance rating of a class
EI60 element is R60, etc.).
10. If the fire damper is used as an air transfer or air
terminal device, it must be equipped with a protective
grille. The distance between the grille and the damper
blade in the open position must be at least 30 mm. In
case of large fire dampers, an extension piece must be
installed between the grille and the damper blade.
FläktGroup DC_9503GB 20230621_R4 Specifications are subject to alteration without notice.
Fire Damper ETCE and ETCS - Instructions for Installation, Operation and Maintenance
10
Replacing fuse part ETFF-99-1
NOTE! Safety gloves should be used when replacing the
fuse part.
1. Release the mechanism with the test button (1) – close
the fire damper. Figure 12.
2. Remove the fuse part mounting screw (6). Figure 13.
3. Holding the test button, pull out the complete fuse part
(7). Figure 14.
4. Correctly install the new fuse part and fasten it with the
screw (6).
5. Test the function of the product and reset the fire damp-
er. Turn the handle towards the OPEN position until
the mechanism clicks and the blade locks into OPEN
position. To test the operation of the fuse mechanism,
push the red test button (1) – the spring should close the
blade. Beware of the turning reset handle!
1
6
6
7
6
Figure 12.
Figure 13.
Figure 14.
FläktGroup DC_9503GB 20230621_R4 Specifications are subject to alteration without notice.
Fire Damper ETCE and ETCS - Instructions for Installation, Operation and Maintenance
11
FG_DC_9503GB_ETCE_ETCS_IN-MA_20230621_R4 © Copyright 2023 FläktGroup
WWW.FLAKTGROUP.COM ETCE, ETCS 9503
»
Learn more on www.flaktgroup.com
or contact one of our oices
FläktGroup is the European market leader for smart and energy eicient Indoor Air
and Critical Air solutions to support every application area. We oer our customers
innovative technologies, high quality and outstanding performance supported by
more than a century of accumulated industry experience. The widest product range
in the market, and strong market presence in 65 countries worldwide, guarantee
that we are always by your side, ready to deliver Excellence in Solutions.
PRODUCT FUNCTIONS BY FLÄKTGROUP
Air Treatment | Air Movement | Air Diusion | Air Distribution | Air Filtration
Air Management & ATD’s | Air Conditioning & Heating | Controls | Service
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12

FläktGroup ETCE/ETCS Installation guide

Type
Installation guide

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI