Sunricher SR-2300TR-RGBW-US-DT6 User manual

Type
User manual
DALI RGBW Touch Controller 09.230WU6.04158
012
3
4
5
6
7
89
012
3
4
5
6
7
89
(x10)
(x1)
Rotary switches for setting start
DALI address number (0-63),
the number equals to tens
position plus units position
D2 D2
43.58 mm
65.58 mm
Function introduction
Important: Read All Instructions Prior to Installation
Front side
Back side
DALI signal output
DALI Wall Panel
Controller
83.00 mm
19.4 mm
Product Data
DO NOT install with power applied to device.
DO NOT expose the device to moisture.
Safety & Warnings
10*(0~9) for setting
tens position
1*(0~9) for setting
units position
D1D1
75x120x29.1mm
Output DALI signal
Operation Current 4mA
Operating temperature 0-40°C
Relative humidity 8% to 80%
Dimensions
Power Supply Supply By DALI Bus
Waterproof grade Ip20
ON/OFF button
Red channel: click to turn ON/OFF,
press and hold down to
increase/decrease light intensity
RGB color wheel
Blue channel: click to turn ON/OFF,
press and hold down to
increase/decrease light intensity
Green channel: click to turn ON/OFF,
press and hold down to
increase/decrease light intensity
White channel: click to turn ON/OFF,
press and hold down to
increase/decrease light intensity
Play/Pause button, click to
play/pause running effects, press
and hold down to speed up/down
Click to get CW, NW, WW
mixed by RGB
Brightness button, press and hold
down to increase/decrease light
intensity
Scene button, press and hold down
to save a scene, click to recall
Touch sensitive.
• Glass interface(white & black).
• Comply to DALI standard protocol IEC 62386-102, IEC
62386-207 and in compliance with DALI products from
other international incorporation.
• 1 light zone is available for switch, dimming and RGB
color control, each zone can control 4 DALI addresses.
• Enable to set start DALI address number (0-63) for the 4
zones by rotary switches on the back.
• Built-in 8 Color Sequences
Wiring diagram
AC Power
50/60Hz
L
N
G
V+
V-
OUTPUT
INPUT
12V/24V/36V
CV PSU
DALI BUS
D1
D2
123
4
GND
Connect wi th R GBW LED Strip
V+ V+
R- R-
G- G-
B- B-
W- W-
123
4
GND
Connect wi th R GBW LED Strip
V+ V+
R- R-
G- G-
B- B-
W- W-
012
3
4
5
6
7
89
012
3
4
5
6
7
89
(x10)
(x1)
D2 D2
DALI Wall Pa nel
Contr oller
D1D 1
Installation
Operation
Set start DALI address number for the light zone by rotary switches on the back:
Set the number as X (0-63), the light zone will control DALI addresses X, X+1, X+2 and X+3.
Note: if X is set as 63, the zone will control DALI address 63, 00, 01 and 02.