This manual must be available to the boiler operator at all times. RB-RBC-IOMM-2017-2
INSTALLATION, OPERATION AND MAINTENANCE MANUAL
RB / RBC Series
Gas / Oil / Dual Fuel Horizontal Steam Boilers
RB-RBC-IOMM-2017-2
Fulton Ltd
Page II
RB-RBC-IOMM-2017-2
Fulton Ltd
Page III
TABLE OF CONTENTS
SECTION 1 - INTRODUCTION
1.1 General 1
1.2 Product Overview 1
1.3 Technical Data 1
SECTION 2 - INSTALLATION
2.1 General 3
2.2 Pre-Installation 3
2.2.1 Siting 4
2.3 Ventilation 4
2.4 Major Components 6
2.5 Flue Outlet 7
2.6 Blowdown Valves 8
2.6.1 Main Boiler Blowdown Valve 8
2.6.2 Water Level Gauge Set (sight glass) 9
2.7 Main Steam Valve 9
2.8 Steam Safety Valve 10
2.9 Water Supply 11
2.10 Fuel Supply 12
2.10.1 Gas Supply 12
2.10.2 Oil Supply 12
2.10.3 Dual Fuel Supply 13
2.11 Electrical Requirements 13
2.12 Cleaning Steam Lines and Pressure Vessels 14
SECTION 3 - OPERATION
3.1 General 15
3.2 Controls 15
3.2.1 System Controls 15
3.2.2 Steam Pressure Controls 16
3.2.2.1 Adjusting Steam Pressure Controls 17
3.2.3 Boiler Control Panel 18
3.2.4 Burner Control Panel 21
3.3 Filling the Boiler-all models 22
3.4 Draining the Boiler 23
3.5 Boiler Start-Up (from cold)-all models 24
3.5.1 Boiler Start-Up Following Short Term Shut-Down 25
3.6 Boiler Shut-Down 25
3.6.1 Short Term Shut-Down (hours) 25
3.6.2 Medium Term Shut-Down (days) 25
3.6.3 Long Term Shut-Down (weeks) 25
3.7 Internal Economiser (If Fitted) 26
SECTION 4 - MAINTENANCE
4.1 Boiler Platform (if Fitted) 27
4.2 Visual Checks 28
4.3 Burner Flame Sensor Test 28
4.4 Water Level and Low Water Safety Control Procedures 29
4.4.1 Feedwater Pump Test 29
4.4.2 1st Low Water Level Check-Standard 30
4.4.2.1 1st Low Water Level Check-With Economiser Fitted 31
4.4.3 2nd Low Water Level Check-Standard 32
4.4.3.1 2nd Low Water Level Check-With Economiser Fitted 33
4.4.4 Evaporation Check 33
4.5 Blowdown Procedures 34
4.5.1 Main Boiler Blowdown 34
4.5.2 Water Level Gauge (Sight Glass) Blowdown 35
4.6 Boiler Internal Inspection 36
4.7 Fitting New Gaskets To Boiler Inspection Holes 37
4.7.1 Important Information 37
4.7.2 Fitting Procedure 38
4.8 Front Access Door 39
4.8.1 Front Access Door Adjustment and Seal 39
4.8.2 Front Access Door Insulation 40
4.9 Feedwater Disperser 41
4.10 Service Inspection of Welded Joints (UK Only) 42
4.11 Schedule of Operator Tests and Checks 43
4.11.1 Daily 44
4.11.2 Weekly-in addition 44
4.11.3 Three Monthly-in addition 45
4.11.4 Six Monthly-in addition 45
4.11.5 Annually-in addition 47
4.12 Maintenance Record Keeping 48
4.12.1 Troubleshooting-boiler 49
4.12.2 Troubleshooting-feedwater pump 51
APPENDIX A - TI SHEETS
 RBDimensions&Specication 54
 RBCDimensions&Specication 56
RB Probe Lengths 58
RBC Probe Lengths 59
Recommended Water Conditions 60
Boiler Water Sample Cooler 61
Water Level Probes 62
Auto TDS Blowdown Systems 64
Electrical diagrams supplied separately
RB-RBC-IOMM-2017-2
Fulton Ltd
Page IV
WARNINGS
The Pressure System Safety Regulations 2000
Fulton boilers fall within the scope of the Pressure Systems Examination Scheme.
Regular inspections are therefore required by a competent person.
The scope of the examination and the actual intervals between examinations is at the discretion of the competent
person.
It is the responsibility of the user to provide a written scheme of examination for those parts of the system in which
a defect may give rise to danger.
Instructions in this manual are provided for the safe operation and maintenance of the boiler and do not cover
periodic statutory inspections.
For further information contact:
(a) SAFed
SAFETY ASSESSMENT FEDERATION Limited.
Nutmeg House,
60 Gainsford Street,
Butlers Wharf,
London, SE1 2NY.
(b) HealthandSafetyExecutivelocalofce.
(c) Your Competent Person.
For your safety!
The following WARNINGS, CAUTIONS and NOTES appear in various sections of this manual.
WARNINGS must be observed to prevent serious
injury or death to personnel.
CAUTIONS must be observed to prevent damage
or destruction of equipment or loss of operating
effectiveness.
Notes: must be observed for essential and
effective operating procedures, conditions and as
a statement to be highlighted.
It is the responsibility and duty of all personnel involved
in the operation and maintenance of this equipment
to fully understand the WARNINGS, CAUTIONS and
NOTES by which hazards are to be eliminated or
reduced.
Personnel must become familiar with all aspects of
safety and equipment prior to operation or
maintenance of the equipment.
CAUTION
In case of emergency
This boiler has been designed and constructed to meet all of the essential requirements of the applicable
European Directives and subject to proper maintenance should not give occasion to any hazardous conditions.
If such a condition should occur during commissioning or during subsequent operation of this product,
whatever the cause, then the fuel supply to the boiler should be isolated immediately, until the fault has been
investigatedbyacompetentpersonandrectied.
!
WARNING
Steam boilers are a potential hazard, possibly fatal if not properly maintained.
CAUTION
It is vitally important that the instructions given in this manual are strictly adhered to. Failure to carry
out the routine maintenance checks could result in a drastic reduction in the life expectancy of the
system and increase the possibility of re, explosion, property damage, personal injury or loss of life.
!
!
RB-RBC-IOMM-2017-2
Fulton Ltd
Page V
WARNINGS
SAFETY
The instructions provided for the operation and maintenance of the boiler MUST be observed. Failure to do so could result in
damage to the heater and serious personal injury.
!
WARNING
Do not try to do repairs or any other maintenance work
you do not understand. Obtain a service manual from
Fulton Ltd or call a Fulton service engineer.
It is the responsibility of the installer to ensure all parts
suppliedwiththeboilerarettedinacorrectandsafe
manner.
Understand the electrical circuit before connecting
or disconnecting an electrical component. A wrong
connection can cause injury and or damage.
A defective boiler can injure you or others. Do not
operate a boiler which is defective or has missing
parts. Make sure that all maintenance procedures are
completed before using the boiler.
Do not change the boiler fuel without consulting the
boiler manufacturer.
LIFTING EQUIPMENT
Make sure that lifting equipment complies with all local
regulations and is suitable for the job. You can be injured
if you use faulty lifting equipment. Make sure the lifting
equipment is in good condition.
Operating the boiler beyond its design limits can damage
the boiler, it can also be dangerous. Do not operate the
boiler outside its limits. Do not try to upgrade the boiler
performancebyunapprovedmodications.
Non-approvedmodicationscancauseinjuryand
damage. Contact your Fulton dealer before modifying
the boiler.
Only qualied persons should be allowed to
operate and maintain the boiler and its equipment.
Boilers should always be drained through an approved
blowdown vessel.
The installation of gas appliances including the
uesystemshouldonlybecarriedoutbyGasSafe
registered engineers.
Steam boilers have high temperature surfaces, that if
touched may cause serious burns. Only competent and
qualiedpersonnelshouldworkonorinthelocalityof
a steam boiler and ancillary equipment. Always ensure
theworkingareaandoorareclearofpotentialhazards,
work slowly and methodically.
DoNOTstoreinammablematerialsneartheboiler.
The importance of correct boiler water and feedwater
cannot be over emphasised, see the relevant section in
this manual.
!
CAUTION
Obey all laws and local regulations which affect you and
your boiler.
LOW FEEDWATER TEMPERATURE
Low feedwater temperature can result in thermal shock
to the boiler pressure vessel. Return the maximum
amount of condensate and if necessary preheat the
feedwater. If in doubt consult Fulton Ltd.
WATER SOFTENER and CHEMICAL TREATMENT
The chemicals required to operate the water softeners
and chemical treatment plants CAN BE SUPPLIED by
Fulton Ltd.
It is the responsibility of the operator to ensure adequate
supplies of chemical are available at all times
(including commissioning). Costly repairs could be
required should the plant operate without chemicals or
the wrong dosage of chemicals.
HYDRAULIC TEST - RISK OF BRITTLE FRACTURE
Hydraulic testing requires specialist equipment and
is normally only required by engineering surveyors /
inspectors. In order to ensure the material/ pressure
vessel does not suffer from brittle fracture, hydraulic
testing should not be carried out below 7 °C.
!
WARNING
DANGER FROM INCOMPLETE COMBUSTION
The importance of correct burner adjustment to achieve
lowemissions,safe,cleanandefcientcombustion
is paramount. Poor combustion, where unburnt gas
forms carbon monoxide is both a health hazard, and
the potential risk to the boiler from overheating, caused
byre-burningoftheunburntgasinthesecondaryue
passes.
Prior to the commencement of any work requiring the
removal of cover plates and the opening of control panel
box, the electrical supply to the boiler must be isolated.
!
RB-RBC-IOMM-2017-2
Fulton Ltd
Page VI
RB-RBC-IOMM-2017-2
Fulton Ltd
Page 1
INTRODUCTION - 1
SECTION 1 - INTRODUCTION
1.1 GENERAL
TheFultonRBandRBCSeriesfuelredsteamboilerservicemanualisagenericpublication,
providing information on standard boiler operation and maintenance.
Every care has been taken in the manufacture of the boiler to ensure that quality and reliability
standards are maintained. Satisfactory performance can only be ensured if the installation
recommendations, operating routines and maintenance schedules laid out in this manual are
adhered to.
1.3 TECHNICAL DATA
Forafullspecicationreferto:
RB
Appendix A - TI-135-RB Dimensions & Specication.
RBC
Appendix A - TI-109-RBC Dimensions & Specication.
1.2 PRODUCT OVERVIEW
TheFultonRBandRBCseriessteamboilersareconventional,reverse-red,three-pass,
wet-back boilers with an optional internal/external economiser constructed to BS 2790 1992.
The RB uses a naming system that refers to steam output.
The RBC uses a naming system that refers to kW rating.
The boiler is mounted on a skid frame and is equipped with control and combustion equipment
accordingtoindividualspecications.Thecontrolandcombustionequipmentcanbettedon
either side of the boiler to suit the installation.
Theboileristtedwithfrontandrearaccessdoorstothecombustionzonesforcleaningand
maintenance purposes. Waterside access is via a manhole in the crown of the boiler, while hand/
head holes are provided in the lower boiler shell to facilitate inspection. The optional economiser
isannedtubeheatexchangermountedintherearsmokeboxoftheboiler.
Boilercombustionisprovidedbygas,oilordualfuelredburnersdesignedforhigh/lowame
operation.Combustionairisnormallycontrolledbyamotorisedbutterydamperincorporatinga
proof of closure interlock.
Burnercontrolsandafuelpumpunit(oil-redmodelsonly)aremountedontheburner.
Note: Consult burner manufacturer’s Operation and Maintenance instructions for more details.
RB-RBC-IOMM-2017-2
Fulton Ltd
Page 2
Figure. 1 - General Arrangement
Boiler water
sample
cooler
Feedwater
pump
Feedwater
inlet
Water level
gauge set
(sight glass)
Boiler
blowdown
Boiler
control box
Burner
Top exit
ue(rear
exitue
optional)
Steam
safety valve
Boiler vent
valve
Main steam
valve
Pressure
gauge and
pressure
controller
connection
Steam
pressure
gauge
RB-RBC-IOMM-2017-2
Fulton Ltd
Page 3
INSTALLATION - 2
2.1 GENERAL
TheinstallationofanRB/RBCseriesfuelredsteamboilershouldbecarriedoutbycompetent
personnel in accordance with all relevant safety regulations. It is the responsibility of the installer
to ensure that these regulations are complied with.
SECTION 2 - INSTALLATION
2.2 PRE-INSTALLATION
Prior to delivery of the boiler, consideration should be given to the following:
(Planning regulations may call for more consents than those listed below, always check with your
Local Planning Authority).
A. Local Planning consents where appropriate.
B. Consideration given to access for delivery and positioning of the boiler.
C. Preparation of a suitable base, which must be able to support the total weight of the system
under operating conditions.
The locations of services to the site required for the system, under operating conditions.
D. Electricity supply, check the loading required/available.
E. Drainage system, check the suitability of the drainage system.
F. Local regulations for discharge into existing drains.
G. Suitable access for delivery and off-loading.
H. Safe access to the plant when installation is complete.
RB-RBC-IOMM-2017-2
Fulton Ltd
Page 4
INSTALLATION - 2
2.3 VENTILATION
Adequatefresh,cleanairisnecessaryforsafeandefcientcombustion,andshouldbeprovided
at high and low level in accordance with BS 6644 1991 and IGE/UP/10 Part 1 Communication
1676.
Note: Ensure that there is adequate ventilation in the boiler room. Lack of ventilation will create a high
temperature and cause control lockout. There is a minimum ventilation requirement to supply the air for
combustion.
Note: Do not keep exhaust fans running with windows, doors and vents closed, this will interfere with the
necessary boiler draught.
Note: Do not store chemicals such as perclorethylene in the boiler house, the fumes may damage the boiler and
ue and cause the burner to lock out on ame failure.
Note: see Appendix A - TI-135-RB Dimensions & Specication & TI-109-RBC Dimensions & Specication
for low and high level values.
2.2.1 SITING
(Reference should be made to Utilisation Procedures as stated in IGE/UP/10 Part 1
Communication 1676, and in particular to Section 5, Location of Appliances).
Theboilerhouseshouldbesufcientlysizedtoalloweasyandsafeaccesstoallpartsofthe
boiler for operational and maintenance purposes.
Reference should be made to Appendix A - TI-135-RB Dimensions & Specication &
TI-109-RBC Dimensions & Specication to ascertain the relevant dimensions and weights.
Theooringmustbelevel,laidinanon-combustiblematerialandbeofsufcientstrengthto
support the boiler.
WARNING
Lifting Equipment
Make sure that lifting equipment complies with all local regulations and is suitable for the job.
You can be injured if you use faulty lifting equipment.
Make sure the lifting equipment is in good condition.
!
RB-RBC-IOMM-2017-2
Fulton Ltd
Page 5
Figure. 2 - Typical Installation
Boiler Water Level
Overflow
Stainless steel
feedwater and
condensate
return tank
Vent
Blowdown
separator
Overflow
to drain
Drain
Drain
Isolating
gate/ball
valve
Strainer Plugged drains
Make-up feedwater
supply
Condensate
return (no flex)
Sight
glass/Ancillary
blowdown line
Feedwater
pump
Steam
supply
Pipe safety
valve to a
safe area,
using unions
and drain as
required.
Boiler
blowdown line
Boiler
blowdown valve
Boiler
feedwater
line
Drain
D
H
Flue
Cowl
D = Diameter of flue
H = 1.5 X D
Standard boiler trim
supplied with boiler
Clean-out
door
Flue spigot
Draught stabiliser
(when fitted)
Note: Ball float or solid state water
level controls available.
RB-RBC-IOMM-2017-2
Fulton Ltd
Page 6
INSTALLATION - 2
2.4 MAJOR COMPONENTS
Main steam valve.Steamoutletstopvalvettedcentrallyonthetopcentrelineoftheboiler.
Steam vent valve. Fitted to the rear, on the top centre line of the boiler.
Safety valve. Fitted to the rear, on the top centre line of the boiler.
Boiler control box
Steam pressure gauge. Fitted to the control box mounting plate on the side of the boiler.
Main boiler blowdown valve. A main boiler blowdown valve connected to pipework at the front
of the boiler on the underside centre line.
Automatic timed blowdown valve (optional). Connected to the manual main boiler blowdown
valve.
Water level gauge set (sight glasses)
Boiler feedwater pump (Grundfos). 1 x Grundfos feedwater pump is provided for the boiler
feedwater mounted to side rear of the boiler supporting frame.
For more information on the feedwater pump, please refer to the Grundfos OEM literature.
Feedwater valve. Water supply inlet stop valve mounted on the side of the boiler.
Feedwater non-return (check) valve. Water supply NRV mounted on the side of the boiler
directly under the main feedwater inlet valve.
Boiler water sample valve. Fitted behind the feedwater inlet on the control side of the boiler.
Boiler water sample cooler. 1 x boiler water sample cooler is mounted to the rear of the boiler
on the controls side.
For more information on the water sample cooler, please refer to Appendix A - TI-122-Boiler
Water Sample Cooler.
TDS Blowdown System (optional)
Burner. Mounted to the front access door.
Note: For detailed burner information, see burner manufacturers Installation & Maintenance manual.
Burner Programmer. Is located in the burner mounted control panel.
Gas Train Assembly. Consists of pilot and main supply lines, each line having a manual cock, a
governor and solenoid operated valves.
Gas booster
Flame sensor (UV photocell)
Burner sequence control
RB-RBC-IOMM-2017-2
Fulton Ltd
Page 7
INSTALLATION - 2
2.5 FLUE OUTLET
Figure. 3 - Boiler Flue Flange
Theheightandtypeofuewillbesubjecttolocalplanningregulationsandapprovals,andtothe
requirements of the Clean Air Act or similar local regulations.
Note: Before erecting a ue, Public Health Authority and Planning permission must be obtained.
Thefollowinginformationisintendedtoprovideassistancewheretheinstallationofasimpleue
is required.Wheremulti-boileruesarenecessary,ordifcultiescouldbeexperienced,specialist
advice must be obtained.
Boilersarettedwithaangedueoutlet.Theuemanufacturer/installermustbeconsultedatan
earlystagetoensureacorrectmatingcomponentforueconnection(seeFigure.3).
Theuediametermustbethesameorlargerthantheboilerueoutlet.Areductioninue
diameter will cause additional resistance which could have an adverse effect on combustion.
Note: Avoid tting 90° short radius elbows, 90° tees and long horizontal runs wherever possible.
Note: All horizontal ue runs should have a rising pitch of 15° minimum to prevent condensate build-up and
subsequent corrosion.
Note: Oil-red boiler installations are generally more critical because of the sulphur content in the fuel and the
higher dew-point temperature.
Note: Specialist advice should be obtained on ue material and insulation.
A
B
C
12 mm
RBC Flue Connection
Holes 15mm dia. equi-spaced
Material mild steel
RB Flange
Model A B C (PCD) Holes
1600 400 300 360 6
2600 450 350 410 6
3400 550 450 510 6
4800 600 500 560 8
5500 650 550 610 8
RBC Flange
Model A B C (PCD) Holes
600 350 250 310 6
750 400 300 360 6
1000 400 300 360 6
1250 450 350 410 6
1500 500 400 460 6
1850 550 450 510 6
2100 550 450 510 6
2500 600 500 560 8
3000 650 550 610 8
RB-RBC-IOMM-2017-2
Fulton Ltd
Page 8
INSTALLATION - 2
2.6 BLOWDOWN VALVES
Figure. 4 - Automatic Boiler Blowdown
2.6.1 MAIN BOILER BLOWDOWN VALVE
There are three blowdown valves on the boiler, the boiler blowdown valve at the front underside
of the boiler and two water level gauge (sight glass) blowdown valves.
All of these valves must be connected to a blowdown receptacle of approved design.
Regulations exist covering such items and care must be taken to ensure compliance with these
regulations.
If in doubt regarding blowdown arrangements, consult Fulton Ltd or Health and Safety Executive
Guidance Note PM60 which covers blowdown tanks and associated pipework installation.
Boiler blowdown
isolation valve
Automatic boiler
blowdown valve
Pneumatic
actuator
WARNING
Never discharge blowdown from the boiler directly to a drain. Where a high level of blowdown or automatic
blowdownsystemsareinstalled,seriousconsiderationshouldbegiventottingaBlowdownAfterCooling
System.
!
Amanualboilerblowdownvalveisttedtotheblowdownpipeworkasstandardandanautomatic
boiler blowdown valve can be added to it.
RB-RBC-IOMM-2017-2
Fulton Ltd
Page 9
INSTALLATION - 2
2.6.2 WATER LEVEL GAUGE SET (SIGHT GLASS)
AllRB/RBCseriesboilersarettedwithtwo,‘Clifton’type(unlessotherwisespecied)reex
water level gauges.
Thewaterlevelgaugeblowdownvalvesshouldbeconnectedtotheauxiliaryblowdownline;nal
connection to the blowdown valves being via soft copper tubing.
Thevalvettingsare6mm.
Figure. 5 - Water Level Gauges
2.7 MAIN STEAM VALVE
Distribution pipework should be run
from the main steam valve on top
of the boiler to the steam delivery
point(s). Care should be taken to
ensure that adequate condensate
drainage and expansion facilities are
provided within the pipework run(s).
To prevent excessive loads being
imposed on the main steam isolating
valve, the pipework should be secured
near the boiler, ensuring adequate
exibilityexistsinthepipework
between the steam valve and the
securing point, to minimise any loads
imposed on the valve.
Main steam valve
Steam distribution
ange
Figure. 6 - Main Steam Valve
RB-RBC-IOMM-2017-2
Fulton Ltd
Page 10
INSTALLATION - 2
2.8 STEAM SAFETY VALVE
Safetyvalvesarefactoryttedandpre-set,theyMUSTNOTbeadjusted.Thedischargeoutlet
should be piped to a safe discharge point and the piping so arranged that any condensate
trapped in the pipework will drain away from the valve.
Note: Safety Valve Outlet connections should be piped two sizes larger than the inlet connection size, this will
ensure there are no accumulation issues.
a) The lift pressure is indicated on the safety valve (do not adjust).
b) Thesafetyvalvettedtotheboilerisdesignedtopreventtheboilerexceedingitsdesign
pressure.
c) Any system connected to the boiler not capable of accepting boiler pressure must be protected
by a separate safety valve set to the required pressure.
WARNING
Factory tted safety valves are pre-set to protect the boiler only and must not be used to protect any
other items not capable of accepting boiler pressure.
!
Figure. 7 - Safety Valve
RB-RBC-IOMM-2017-2
Fulton Ltd
Page 11
INSTALLATION - 2
2.9 WATER SUPPLY
Figure. 8 - Boiler Feedwater Inlet Valve
The quality of the feedwater will affect the life and performance of a steam boiler.
Steamisproducedbyheattransferfromtheheatsourceintothewaterconnedwithintheboiler
cylindrical shell, by the passage of hot gases through the furnace and tubes. It should be noted
that solids entering the boiler with the feedwater can rapidly concentrate at areas of high heat
transfer. Such deposits can restrict heat transfer and consequently raise mean metal temperature,
which can cause corrosion and reduce safety margins possibly to the point of failure.
It is therefore strongly recommended that a reputable water treatment specialist is consulted prior
to putting the boiler into service.
Note: See Appendix A - TI-140-Recommended Water Conditions.
WatercharacteristicsaregenerallyasspeciedinBS24861997“TreatmentofWaterforSteam
Boilers and Water Heaters”, Table 2.
Boilers operating in areas with high residual hardness, high levels of Bicarbonate (temporary)
hardnessandlowcondensatereturnrates,willhavedifcultyinmaintainingTotalandCaustic
Alkalinity(TDS)gures,withinthespeciedlimitswhenbaseexchangesofteningisused.
This will result in a tendency of the boiler water to foam causing unstable water level conditions
possibly leading to priming and carry over. In these instances particular care should be taken to
establish a suitable water treatment programme and blowdown schedule in consultation with your
water treatment specialist.
Cold feedwater contains high levels of dissolved oxygen which is highly corrosive when released
within a steam boiler. Always pre-heat the feedwater to 80 °C - 85 °C to reduce dissolved oxygen
to a minimum and prevent thermal shock. Water treatment chemicals should be used to remove
the remainder of the dissolved oxygen.
Failure to do so will result in premature failure of the boiler tubes which will not be covered by
guarantee.
Feedwater inlet
check valve
Feedwater inlet valve
CAUTION
WATER SOFTENER and CHEMICAL TREATMENT
The chemicals required to operate the water softeners and chemical treatment plants
CAN BE SUPPLIED by Fulton. It is the responsibility of the operator to ensure adequate supplies
of chemical are available at all times (including commissioning). Costly repairs could be required
should the plant operate without chemicals or the wrong dosage of chemicals.
!
RB-RBC-IOMM-2017-2
Fulton Ltd
Page 12
INSTALLATION - 2
2.10.2 OIL SUPPLY
Oil-redboilersaresuppliedwitha
matched, automatic high/low oil burner
suitable for use with 35 SRNI fuel oil.
A single-pipe system can be used where
thesuctionisfullyooded,however,for
systemswhere‘lift’isrequired,itwillbe
necessary to install a two-pipe system.
For more details consult the burner
manufacturer’sinstructionmanual.
The following points should be observed:
a) Alwaysinstallanoillter.
b) Useexiblepipeworkforthenaloil
connections to the oil pump.
c) Fit isolating valves to the pump.
d) Ensure that the supply pipework is
sized to cause a minimum pressure
drop.
Figure. 10 - Oil Burner Installation
Note: Installation will change with the type of
burner tted.
2.10 FUEL SUPPLY
WARNING
Do not change the boiler fuel without consulting the boiler manufacturer.
!
2.10.1 GAS SUPPLY
The gas/pressure requirement varies
according to the burner size and the gas
train selected.
Verify that the type and pressure of the
gas available on the site is suitable for the
burnertted.
If the site gas pressure is too low, it will be
necessarytotagasboostersystem.
Consult Fulton Ltd if in doubt.
To minimise pressure drops, eliminate
all unnecessary bends and elbows in the
pipework between the gas meter and the
inlet to the gas train.
Ensure that a gas cock of the correct size
is installed as close as possible to the gas
train.
All gas pipework must be installed by
‘CompetentPersons’inaccordancewith
the gas regulations.
Figure. 9 - Gas Burner Installation
Note: Installation will change with the type of
burner tted.
RB-RBC-IOMM-2017-2
Fulton Ltd
Page 13
INSTALLATION - 2
An individual wiring diagram for the boiler is located on the inside cover of the control box.
Whenreferringtotheelectricalspecicationoftheboiler,thereferencenumberlocatedonthe
rear inside wall of the control box and the wiring diagram number should be quoted.
The audible alarms provided are mounted on the front of the control panel, if not audible they
should be repositioned where they can be heard by a person competent to take the appropriate
action should the alarm be activated.
A 3-phase, neutral and earth isolated supply is required; this should be connected to the supply
terminals of the main isolator in the boiler control panel.
Note: The power ratings and requirements are given in Appendix A - TI-135-RB Dimensions & Specication &
TI-109-RBC Dimensions & Specication.
2.11 ELECTRICAL REQUIREMENTS
2.10.3 DUAL FUEL SUPPLY
Figure. 11 - Dual Fuel Burner Installation
Note: Installation will change with the type of burner tted.
CAUTION
Anyelectricalworkshouldbeundertakenbyaqualiedelectriciantocurrentlocalregulations.
!
RB-RBC-IOMM-2017-2
Fulton Ltd
Page 14
INSTALLATION - 2
2.12 CLEANING STEAM LINES AND PRESSURE VESSELS
Duringtherstweekofboileroperation,cleanalloilanddirtfromtheboiler,thesteamlineand
condensate return line.
1. Disconnect the condensate return pipe adjacent to the condensate return tank.
2. Directthereturnstoaoordrainorothersafedischargepointandmakesafe.
3. Leaveinthispositionforoneweektoallowallimpuritiestoushthrough.
4. Drain the boiler completely each day.
5. Aftertheweekiscompleted,drainandushthecondensatereturntank,removingall
installation sediment. Reconnect the condensate return pipe to the condensate return tank.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74