Trend TW/P Installation guide

Type
Installation guide
TW/P Wireless Plant Temperature Sensor Installation Instructions TG200782 Issue 2 10/07/08
1
Installation Instructions
TW/P
Wireless Plant Temperature Sensor
Important: Retain these instructions
INSTALLATION
UNPACKING
TW/P Installation
Instructions TG200782
Dimensions
1
Requirements
2
a
63 mm (2.48”)
45 mm (1.77”)
40 mm (1.57”)
27 mm (1.06”)
Follow the requirements of plant sensor in which board is to be fitted.
TB/TC Installation Instructions TG200726
TE/TC Installation Instructions TG102385
TB/TI/S, TB/TI/L Installation Instructions TG200727
TE/TI Installation Instructions TG102386
TE/TD/S, TE/TD/L Installation Instructions TG102387
TB/TO Installation Instructions TG200725
TE/TO Installation Instructions TG102384
TW/P Installation Instructions
TW/P Wireless Plant Temperature Sensor Installation Instructions TG200782 Issue 2 10/07/08
2
INSTALLATION (continued)
Requirements (continued)
2
b
H O
2
-10 °C
-14 °F
+50 °C
+122 °F
0 %RH
95 %RH
-30 °C
-22 °F
+110 °C
+230 °F
c
Remove Lid
3
d
Protection IP20 (in box)
• Avoid using many other devices on
frequency range 433.05 to 434.79 MHz
• Keep away from sources of interference
(e.g. computer >1 m (1 yd), microwave
ovens, switch mode power supplies).
• Mount above partition height if possible.
XW/R/IQ
75 m (82 yds)
(maximum)
ambient limits (box & electronics)
measurement range
Note for ambient limits of probe see plant sensor installation instructions as in ‘a’ above.
Remove terminal block
from lead
4
Unscrew M20 Gland
5
Screw in Blanking Plug
6
Note that range may be affected
by environmental characteristics,
e.g. partitions, walls, building
structure etc.
discard in an environmentally
friendly manner
discard in an
environmentally friendly manner
See step 6
TW/P Wireless Plant Temperature Sensor Installation Instructions TG200782 Issue 2 10/07/08
3
Installation Instructions TW/P
INSTALLATION (continued)
Note Identification Number
8
Fit board into mounting slots
9
000016746
00016746
000016746
00016746
Connect thermistor
7
Removeable identification label for installers own use
000016746
00016746
‘location’
Install and Configure XW/
R/IQ Receiver
11
XW/R/IQ Installation Instructions TG200783
Replace Lid
10
TW/P Installation Instructions
TW/P Wireless Plant Temperature Sensor Installation Instructions TG200782 Issue 2 10/07/08
4
Trend Control Systems Limited
P.O. Box 34, Horsham, West Sussex, RH12 2YF, UK. Tel:+44 (0)1403 21888 Fax:+44 (0)1403 241608 www.trend-controls.com
Trend Control Systems USA
6670 185th Avenue NE, Redmond, Washington 98052, USA. Tel: (425)897-3900, Fax: (425)869-8445 www.trend-controls.com
Please send any comments about this or any other Trend technical publication to [email protected]
© 2008 Honeywell Technologies Sàrl, ECC Divison. All rights reserved. Manufactured for and on behalf of the Environmental and Combustion Controls
Division of Honeywell Technologies Sàrl, Ecublens, Route du Bois 37, Switzerland by its Authorized Representative, Trend Control Systems Ltd.
Trend Control Systems Limited reserves the right to revise this publication from time to time and make changes to the content hereof
without obligation to notify any person of such revisions or changes.
IQ
WEEE Directive :
At the end of their useful life the packaging,
product, and batteries should be disposed
of by a suitable recycling centre.
Do not dispose of with normal household waste.
Do not burn.
Test System
13
Δ T
e.g. TB/TI/..
XW/R/IQ
INSTALLATION (continued)
Configure IQ
12
MAINTENANCE
The battery has a minimum life of 5 years. If the battery runs down the XW/R/IQ receiver will set an alarm
bit in the status data sent with the value. This corresponds to bit 1 (Low alarm). When the battery has run
down, the unit should be returned to the IQ system supplier for battery replacement.
TW/.., PCW/.., XW/R/IQ Data Sheet TA200780
For IQ3 the sensor’s target analogue node must
be created using SET. An example strategy
including decoding of alarm bits is given in the
TW/.., PCW/.., XW/R/IQ Data Sheet
DISPOSAL
2 min.
Check for alarm bits
BIT1 : Low Battery
BIT2 : Sensor fail
BIT3 : Loss of reception
see TW/.., PCW/.., XW/R/IQ Data Sheet, for
decoding of alarm bits.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4

Trend TW/P Installation guide

Type
Installation guide