HT/ST Space Humidity and Temperature Sensor Installation Instructions TG200921 Issue 1/B 30/08/06
2 - 1
Installation Instructions - Sheet 2
HT/ST
Space Humidity and Temperature Sensor
Switch off supply
1
2.1 Maintenance
Over time, the sensing element may get covered in dust. The dust can be removed using compressed
air. Under no circumstances should water or cleansing agents be used on the sensing elements.
It is recommended that the accuracy of the sensor is verified every 12 months. If the sensor falls outside
the quoted accuracy, or the sensor tip is damaged, replace the tip as shown below.
Open housing
2
Unscrew board
3
Remove old sensor tip
4
a
b
Caution: This unit contains static sensitive
devices. Suitable ant-static
precautions should be taken
throughout the operation to
prevent damage to the units.
BS EN100015/1 Basic Specifications:
protection of electrostatic sensitive devices.
J P R 4
L P 2 - P W R
T H
I 2 - N / T H
I 1 - N
I 1 - P
E A R T H
O
I
J P R 4
L P 2 - P W R
T H
I 2 - N / T H
I 1 - N
I 1 - P
E A R T H
hold sides of sensor tip near base of sintered filter
JPR4
LP2-PWR
TH
I2-N/TH
I1-N
I1-P
EARTH
discard old tip, see 2.2
HT/ST Installation Instructions - Sheet 2
HT/ST Space Humidity and Temperature Sensor Installation Instructions TG200921 Issue 1/B 30/08/06
2 - 4
Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sàrl, Ecublens, Route
du Bois 37,Switzerland by its Authorized Representative, Trend Control Systems Limited.
Trend Control Systems Limited reserves the right to revise this publication from time to time and make changes to the content hereof
without obligation to notify any person of such revisions or changes.