3 Device Description
Pos: 18.1 /Serie 750 (W AGO-I/O-SYSTEM)/Gerätebeschrei bung/Einleitung/An wendung/DI/Anwendung 7 50-x4x x DI @ 3\mod_12 33762736718_21.doc x @ 27108 @ @ 1
The digital input module 750-407 (2DI 220V DC 3.0ms) receives control signals
from digital field (e.g. of sensors, transmitters, switches or proximity switches).
Pos: 18.2 /Serie 750 (W AGO-I/O-SYSTEM)/Gerätebeschrei bung/Einleitung/I /O-Beschreibung/DI /I/O-Beschrei bung 750-0407 2 DI 2-/3-/4-Leiter (DI, 220 V, 0 V und Er de) @ 7\mod_1274862216081_21. docx @ 57033 @ @ 1
The I/O module has 2 input channels, providing a direct connection to 2-, 3- or 4-
wire sensors.
The sensors are connected to the following CAGE CLAMP
®
terminals: DI 1,
220 V, 0 V and ground, or DI 2, 220 V, 0 V and ground.
Pos: 18.3 /Serie 750 (W AGO-I/O-SYSTEM)/Gerätebeschreibung/Ei nleitung/I/O-Besc hreibung/Allge mein/Verweis auf Kapit el "Anschlüsse" @ 8\mod_1 276775378035_21.d ocx @ 57956 @ @ 1
The assignment of the connections is described in the “Connectors” section.
Pos: 18.4 /Serie 750 (W AGO-I/O-SYSTEM)/Gerätebeschrei bung/Einleitung/I /O-Beschreibung/A llgemein/Verweis auf Kapitel "Geräte ansc hließen" > "Anschluss beispiel(e)" @ 5\mod_1 246015203281_21.doc x @ 36298 @ @ 1
Connection examples are shown in section “Connecting Devices” > … >
“Connection Example(s)”.
Pos: 18.5 /Serie 750 (W AGO-I/O-SYSTEM)/Gerätebeschrei bung/Einleitung/I /O-Beschreibung/DI /I/O-Beschrei bung 750-x4xx DI RC-Filter 3, 0 ms @ 3\mod_1233755071062_21.doc x @ 27080 @ @ 1
Each input channel has a RC noise rejection filter with a time constant of 3.0 ms.
Pos: 18.6 /Serie 750 (W AGO-I/O-SYSTEM)/Gerätebeschrei bung/Einleitung/LE D-Anzeige/LED Zustan d Signal @ 3\mod_12337552585 78_21.docx @ 27087 @ @ 1
A green LED indicates the switched status of each channel.
Pos: 18.7 /Serie 750 (W AGO-I/O-SYSTEM)/Gerätebeschreibung/Ei nleitung/LED-Anzei ge/Verweis auf Kapi tel "Anzeigeelemente" @ 5\mod_1246010525000_2 1.docx @ 36194 @ @ 1
The meaning of the LEDs is described in the “Display Elements” section.
Pos: 18.8 /Serie 750 (W AGO-I/O-SYSTEM)/Wichtige Erläuterun gen/Sicherheits- und sonstige Hinweise/ Hinweis/Hinweis: Einspeiseklemme f ür Versorgung ungleic h 24 V einsetzen @ 5\mod_12470326093 40_21.docx @ 36784 @ @ 1
Only connect to I/O modules with the same field power supply!
The I/O module 750-407 requires a field supply not equal to 24 VDC.
Therefore, this I/O module 750-407 shall only be connected to modules having
the same field power supply.
If using an adjacent I/O module designed for another field power supply, place an
appropriate supply module between this adjacent module and the I/O module 750-
407.
Failure to observe these instructions may result in damage to properties or injuries
to people.
Pos: 18.9 /Serie 750 (W AGO-I/O-SYSTEM)/Gerätebeschrei bung/Einleitung/Ver sorgung/Versorgung DC 220 V, 0 V, Erde über Lei stungskontakte @ 5\mod_1246870 311688_21.doc x @ 36640 @ @ 1
The I/O module receives the 220 VDC potential, the 0 V potential and the earth
potential for the field level from an upstream I/O module via the power contacts
used as blade contacts. It then provides this potential to subsequent I/O modules
via the power contacts used as spring contacts.
Pos: 18.10 /Serie 750 (W AGO-I/O-SYSTEM)/Wichtige Erläuter ungen/Sicherhei ts- und sonstige Hinweise/ Achtung/Achtung: M aximaler Strom Leistungsk ontakte 10 A @ 3\mod_122649 9143500_21.doc x @ 25029 @ @ 1
Do not exceed maximum current via power jumper contacts!
The maximum current to flow through the power jumper contacts is 10 A.
Greater currents can damage the contacts.
When configuring your system, ensure that this current is not exceeded. If
exceeded, insert an additional supply module.
Pos: 18.11 /Serie 750 (W AGO-I/O-SYSTEM)/Gerätebeschrei bung/Einleitung/Ver sorgung/Galvanisc he Trennung Feld/Syst em @ 3\mod_1233756478 750_21.docx @ 27102 @ @ 1
The field voltage and the system voltage are electrically isolated from each other.
Pos: 18.12 /Serie 750 (W AGO-I/O-SYSTEM)/Gerätebeschrei bung/Einleitung/Ver sorgung/Anordn ung unter Berücksichti gung der Leistungskon takte beliebig @ 3\mod_12 33756233468_21.doc x @ 27099 @ @ 1
With consideration of the power jumper contacts, the individual modules can be
arranged in any combination when configuring the fieldbus node. An arrangement
in groups within the group of potentials is not necessary.